Temperaturschalter TS 1000
menu sTep n3 – Turn-on delay
dL
2,0
Identified by the
dl
. This step will show you the turn-on delay of the relay. The
value can be selected by pressing
56
. The selection is confirmed by pres-
sing
seT
and the display will switch to the next step.
This setting is useful if ON and OFF switching temperature are very close to-
gether. Setting a turn-on delay avoids too frequent switching of only slightly
changing temperatures. Settings range: 0…999.9 seconds
menu sTep n4 – hIghesT measured TemperaTure
Hi
25,1
Identified by the
hi
. This step will show you the highest measured temperature.
The value can be selected by pressing
56
. The selection is confirmed by
pressing
seT
and the display will switch to the next step.
menu sTep n5 – loWesT measured TemperaTure
Lo
-5.4
Identified by the
lo
. This step will show you the lowest measured temperature.
The value can be selected by pressing
56
. The selection is confirmed by
pressing
seT
and the display will switch to display mode.
If no new temperatures have been measured, the display will show four
dashes:
End
----