EXTERNAL CONTROL
127
Sequence Mode Setting (
:
SEQ:MOD)
This command controls a sequence operation. It can start, stop or
pause a sequence.
Setting
:SEQ:MOD <value>
<value> is as shown below:
0: Stops sequence operation.
1: Pause sequence operation – Waits for start.
2: Runs sequence operation (Executes sequence).
Application
example
:SEQ:MOD 2
Runs the sequence.
Query
:SEQ:MOD?
Inquires about the setting.
Response
example
2
Indicates that sequence operation is being executed. This
command causes an error if the sequence function is
running.
Remark
None
Sequence Jump Setting (:SEQ:STEP)
This command jumps to a specified step in the sequence operation.
Setting
:SEQ:STEP <value>
The <value> range is from 0 to 99.
This command can only be executed when a sequence is
paused.
Application
example
:SEQ:STEP 2
Jumps to step 2.
Query
:SEQ:STEP?
Inquires about the setting.
Response
example
2,1
Indicates that step 2 is selected and the repetition
frequency is 1(looped one time).
Remark
This command causes an error if the sequence function is
running.
All manuals and user guides at all-guides.com