36
Expert Power Control 8042
© 2020 GUDE Systems GmbH
Configuration
3
Configuration
TCP/IP configuration by DHCP
After switching on the device is scanning on the Ethernet for a DHCP server and re-
quests an unused IP address. Check the IP address that has been assigned and ad-
just if necessary, that the same IP address is used at each restart. To turn off DHCP
use the software GBL_Conf.exe or use the configuration via the web interface.
To check the network settings with GBL_Conf.exe, start the program and choose
"All
Devices"
in the
"Search"
menu. From the list select the appropriate device. The lower
part of the left half of the window now shows the current network settings of the device.
If the IP address is displayed with the default settings (192.168.0.2), either no DHCP
server is present on the network, or there could be no free IP address assigned to it.
3.1
Power Ports
Choose Power Port to configure: This field is used to select the power ports to be con-
figured.
Label: You can assign a name up to 15 characters for each of the power ports. Using
the name, an identification of the the device connected to the port can be facilitated.
Start-up Monitoring
It is important, that if necessary the condition of the power ports can be restored after a
power failure. Therefore each port can be configured with Initialization status to a spe-
cific start-up state. This start-up sequence can be carried out delayed by the parameter
Initialization Delay. There is in any case a minimum one-second delay between switch-
ing of ports.
Initialization status(coldstart): This is the port state (on, off, remember last state) the
port should be set when the device is turned on. The setting "remember last state"
saves the last manually set state of the power port in the EEPROM.
Initialization delay: Here can be configured how long the port should wait to switch to its
defined state after the device is turned on. The delay may last up to 8191 seconds.
This corresponds to a period of approx. two hours and 20 minutes. A value of zero
means that the initialization is off.
Содержание Expert Power Control 8042 Series
Страница 1: ...Manual 2020 GUDE Systems GmbH Manual Ver 1 0 3 from Firmware Ver 1 0 Expert Power Control 8042 Series ...
Страница 2: ...2 Expert Power Control 8042 2020 GUDE Systems GmbH ...
Страница 5: ...5 Expert Power Control 8042 2020 GUDE Systems GmbH Table of contents 94 Index ...
Страница 6: ...Device Description ...
Страница 15: ...Operating ...
Страница 35: ...Configuration ...
Страница 63: ...Specifications ...
Страница 91: ...Support ...
Страница 96: ...96 Expert Power Control 8042 2020 GUDE Systems GmbH Expert Power Control 8042 2020 GUDE Systems GmbH 3 5 2020 ...