80
Expert Power Control 8042
© 2020 GUDE Systems GmbH
Specifications
linesensor {line_num} {energy_sensor} events
show
shows if events are enabled
linesensor {line_num} {energy_sensor} events
type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2
,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER
=5}"
enables different event types
linesensor {line_num} {energy_sensor} events
type show
shows what event types are enabled
linesensor {line_num} {energy_sensor} phonebook
sms events set "{1..20}"
sets for what phonebook entries SMS are sent
linesensor {line_num} {energy_sensor} phonebook
sms events show
shows for what phonebook entries SMS are sent
linesensor {line_num} {energy_sensor} maxval set
{float}
sets maximum value for line meter
linesensor {line_num} {energy_sensor} maxval
show
shows maximum value for line meter
linesensor {line_num} {energy_sensor} minval set
{float}
sets minimum value for line meter
linesensor {line_num} {energy_sensor} minval
show
shows minimum value for line meter
linesensor {line_num} {energy_sensor} hyst set
{float}
sets hysterese value for line meter
linesensor {line_num} {energy_sensor} hyst show shows hysterese value for line meter
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port set {port_num}
sets Port for Power Port Switching actions
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port show
shows Port for Power Port Switching actions
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state set {OFF=0|ON=1|
DISABLED=2}
sets Port state for Power Port Switching actions
linesensor {line_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state show
shows Port state for Power Port Switching actions
linesensor {line_num} events set {OFF=0|ON=1}
LEGACY - enables events on/off
L
linesensor {line_num} events show
LEGACY - shows if events are enabled
L
linesensor {line_num} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2
,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER
=5}"
LEGACY - enables different event types
L
linesensor {line_num} events type show
LEGACY - shows what event types are enabled
L
linesensor {line_num} maxval set {float}
LEGACY - sets maximum value for line meter
L
linesensor {line_num} maxval show
LEGACY - shows maximum value for line meter
L
linesensor {line_num} minval set {float}
LEGACY - sets minimum value for line meter
L
linesensor {line_num} minval show
LEGACY - shows minimum value for line meter
L
linesensor {line_num} hyst set {float}
LEGACY - sets hysterese value for line meter
L
linesensor {line_num} hyst show
LEGACY - shows hysterese value for line meter
L
linesensor {line_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3}
port set {port_num}
LEGACY - sets Port for Power Port Switching ac-
tions
L
linesensor {line_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3}
port show
LEGACY - shows Port for Power Port Switching
actions
L
linesensor {line_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3}
state set {OFF=0|ON=1|DISABLED=2}
LEGACY - sets Port state for Power Port Switch-
ing actions
L
linesensor {line_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3}
state show
LEGACY - shows Port state for Power Port
Switching actions
L
linesensor beeper set {OFF=0|ON=1}
enables beeper for line meter alarms
linesensor beeper show
shows if beeper for line meter alarms is enabled
modbus
enters cmd group "modbus"
modbus enabled set <off=0/on=1>
enables Modbus TCP support
modbus enabled show
shows if Modbus is enabled
modbus port set <ip_port>
sets Modbus TCP port
modbus port show
shows Modbus TCP port
port
enters cmd group "port"
port {port_num} state set {OFF=0|ON=1}
sets port to new state
port {port_num} state show
shows port state
port all state set "{port_list}" {OFF=0|ON=1}
sets several ports in one cmd - e.g. port all state
set "1,3,5" 1
port all state {MODE0=0|MODE1=1|MODE2=2}
shows all port states in 3 different view modes
4
Содержание Expert Power Control 8042 Series
Страница 1: ...Manual 2020 GUDE Systems GmbH Manual Ver 1 0 3 from Firmware Ver 1 0 Expert Power Control 8042 Series ...
Страница 2: ...2 Expert Power Control 8042 2020 GUDE Systems GmbH ...
Страница 5: ...5 Expert Power Control 8042 2020 GUDE Systems GmbH Table of contents 94 Index ...
Страница 6: ...Device Description ...
Страница 15: ...Operating ...
Страница 35: ...Configuration ...
Страница 63: ...Specifications ...
Страница 91: ...Support ...
Страница 96: ...96 Expert Power Control 8042 2020 GUDE Systems GmbH Expert Power Control 8042 2020 GUDE Systems GmbH 3 5 2020 ...