Specifications
A unique value, greater than zero, for each receiver slot.
epc8042TrapAddr
.86.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
epc8042portNumber
.86.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc8042PortIndex
.86.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc8042PortName
.86.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc8042PortState
.86.1.3.1.2.1.3.x
INTEGER
RW
current state of a Relay Port
epc8042PortSwitchCount
.86.1.3.1.2.1.4.x
Integer32
RO
The total number of switch actions ocurred on a Relay Port. Does not
count switch commands which will not switch the ralay state, so just real
relay switches are displayed here.
epc8042PortStartupMode
.86.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc8042PortStartupDelay
.86.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc8042PortRepowerTime
.86.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repower port after switching off
epc8042Buzzer
.86.1.3.10.0
Integer32
RW
turn Buzzer on and off
epc8042ActivePowerChan
.86.1.5.1.1.0
Unsigned32
RO
Number of suppported Power Channels.
epc8042PowerIndex
.86.1.5.1.2.1.1.x
Integer32
RO
Index of Power Channel entries
epc8042ChanStatus
.86.1.5.1.2.1.2.x
Integer32
RO
0 = data not active, 1 = data valid
epc8042AbsEnergyActive
.86.1.5.1.2.1.3.x
Gauge32
RO
Absolute Active Energy counter.
epc8042PowerActive
.86.1.5.1.2.1.4.x
Integer32
RO
Active Power
epc8042Current
.86.1.5.1.2.1.5.x
Gauge32
RO
Actual Curent on Power Channel.
epc8042Voltage
.86.1.5.1.2.1.6.x
Gauge32
RO
Actual Voltage on Power Channel
epc8042Frequency
.86.1.5.1.2.1.7.x
Gauge32
RO
Frequency of Power Channel
epc8042PowerFactor
.86.1.5.1.2.1.8.x
Integer32
RO
Power Factor of Channel between -1.0 and 1.00
epc8042Pangle
.86.1.5.1.2.1.9.x
Integer32
RO
Phase Angle between Voltage and L Line Current between -180.0 and
180.0
epc8042PowerApparent
.86.1.5.1.2.1.10.x
Integer32
RO
L Line Mean Apparent Power
epc8042PowerReactive
.86.1.5.1.2.1.11.x
Integer32
RO
L Line Mean Reactive Power
epc8042AbsEnergyReactive
.86.1.5.1.2.1.12.x
Gauge32
RO
Absolute Reactive Energy counter.
epc8042AbsEnergyActiveReset-
table
.86.1.5.1.2.1.13.x
Gauge32
RW
Resettable Absolute Active Energy counter. Writing '0' resets all reset-
table counter.
epc8042AbsEnergyReactiveReset-
table
.86.1.5.1.2.1.14.x
Gauge32
RO
Resettable Absolute Reactive Energy counter.
epc8042ResetTime
.86.1.5.1.2.1.15.x
Gauge32
RO
Time in seconds since last Energy Counter reset.
epc8042ForwEnergyActive
.86.1.5.1.2.1.16.x
Gauge32
RO
Forward Active Energy counter.
epc8042ForwEnergyReactive
.86.1.5.1.2.1.17.x
Gauge32
RO
Forward Reactive Energy counter.
epc8042ForwEnergyActiveReset-
table
.86.1.5.1.2.1.18.x
Gauge32
RO
Resettable Forward Active Energy counter.
epc8042ForwEnergyReactiveRe-
settable
.86.1.5.1.2.1.19.x
Gauge32
RO
Resettable Forward Reactive Energy counter.
epc8042RevEnergyActive
.86.1.5.1.2.1.20.x
Gauge32
RO
Reverse Active Energy counter.
epc8042RevEnergyReactive
.86.1.5.1.2.1.21.x
Gauge32
RO
Reverse Reactive Energy counter.
epc8042RevEnergyActiveReset-
table
.86.1.5.1.2.1.22.x
Gauge32
RO
Resettable Reverse Active Energy counter.
Содержание Expert Power Control 8042 Series
Страница 1: ...Manual 2020 GUDE Systems GmbH Manual Ver 1 0 3 from Firmware Ver 1 0 Expert Power Control 8042 Series ...
Страница 2: ...2 Expert Power Control 8042 2020 GUDE Systems GmbH ...
Страница 5: ...5 Expert Power Control 8042 2020 GUDE Systems GmbH Table of contents 94 Index ...
Страница 6: ...Device Description ...
Страница 15: ...Operating ...
Страница 35: ...Configuration ...
Страница 63: ...Specifications ...
Страница 91: ...Support ...
Страница 96: ...96 Expert Power Control 8042 2020 GUDE Systems GmbH Expert Power Control 8042 2020 GUDE Systems GmbH 3 5 2020 ...