77
Expert Net Control 2302
© 2021 GUDE Systems GmbH
Specifications
"Current" at first PowerSrc: 0 * 2 + 1 = 0x8241
Offset
Sensor Field
Unit
0
Voltage
0.01 V
1
Current
mA
Residual Current Monitor Type B (RCMB):
Devices with a Residual Current Monitor Type B (RCMB) module separately measure
the RMS and DC fault current components of the input supply. The values are returned
as signed 16-bit integers. The following formulas are used for the address (the module
number starts at zero):
Bank: ModuleNo * 8 + Offset.
Examples:
"Residual Current DC" at first module: 0 * 8 + 1 = 0x8281.
"Output DC" for second module: 1 * 8 + 3 = 0x828b
Offset
Sensor Field
Unit
0
Residual Current RMS Type B
0.1 mA
1
Residual Current DC Type B
0.1 mA
2
Output RMS
bool
3
Output DC
bool
4
Module State
Whether a Residual Current Monitor Type B (RCMB) module is present depends
on the particular device model.
Holding Registers
Device Resource
Start
End
Function
Bank Power Source
0x000 0x00f
Sets Power Source for Bank
Fan Mode
0x010 0x01f
0 = Automatic / 1 = Maximum
Device Identification
Returns manufacturer name and device identification:
Request Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Object Id
1 Byte
0x00
Response Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Conformity Level
1 Byte
0x01
More Follows
1 Byte
0x00
Содержание Expert Net Control 2302
Страница 1: ...Manual Expert Net Control 2302 2021 GUDE Systems GmbH Manual Ver 1 3 0 from Firmware Ver 1 3 ...
Страница 2: ...2 Expert Net Control 2302 2021 GUDE Systems GmbH ...
Страница 5: ...Device Description ...
Страница 13: ...Operating ...
Страница 23: ...Configuration ...
Страница 51: ...Specifications ...
Страница 82: ...Support ...
Страница 88: ...88 Expert Net Control 2302 2021 GUDE Systems GmbH Expert Net Control 2302 2021 GUDE Systems GmbH 11 18 2021 ...