NS3000 UPS 60KVA~120KVA User Manual
43
91
Bypass CAN Fail
The CAN bus between bypass module and cabinet is
abnormal.
92
Dust
Filter
Expired
Dust filter need to be clear or replaced with a new one
102
Wave Trigger
Waveform has been saved while UPS fail
103
Bypass CAN Fail
Bypass and cabinet communicate with each other via CAN
bus. Check
If connector or signal cable is abnormal.
If monitoring board is abnormal.
105
Firmware Error
Manufacturer used only.
106
System Setting
Error
Manufacturer used only.
107
Bypass
Over
Temp.
Bypass module is over temperature. Please check
If bypass load is overload
If ambient temperature is over 40°C
If bypass SCRs are assembled correctly
If bypass fans are normal
108
Module
ID
Duplicate
At least two modules are set as same ID on the power
connector board, please set the ID as correct sequence
Note
Different colors of the words represent different level of events:
(a)Green, an event occurs
;
(b)Grey, the event occurs then clears
;
(c)Yellow, warning occurs
;
(d) Red, faults happen.
4.3.5 Operate
Touch the icon
(At the bottom of the screen), and the system enters the page of
the “Operate”, as it is shown in Figure 4-10.
Содержание NS3000 Series
Страница 6: ......