Quick start_MUST400T_ENG_REV00 

Safety Precautions 

This  manual  contains  information  concerning  the  installation  and  operation  of  Modular  UPS.  Please  carefully  read  this 

manual prior to installation. 

The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its 

agent).    Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty. 

The UPS has been designed for commercial or industrial use only, and is not intended for use in any life support application. 

This is a CLASS C Uninterruptible Power Supply (UPS) product. In a domestic environment, this product may cause radio 

interference, in which case, the user may be required to take additional measures. 

 

 

Conformity and standards 

This  product  complies  with  2006/95/EC  ,CE73/23  &  93/68  (low  voltage  safety)  and  2004/108/EC,  89/336  (EMC),  and  the 

following UPS product standards: 

*IEC62040-1 General and safety requirements for use in operator access area 

*IEC/EN62040-2 EMC requirements CLASS C 

*IEC62040-3 Performance requirements and test methods 

Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories 

only. 

 

 

WARNING: high earth leakage current 

Earth connection is critical before connecting the input supply (include both utility supply and battery). 

"Earth leakage current introduced by the UPS, in any  configuration from 10kW to 200kW, exceeds 3.5 mA and is less than 1000 

mA and complies with the requirements of IEC/EN 62040-1 / IEC/EN 60950-1" Transient and steady-state earth leakage currents, 

which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices. 

Residual Current Circuit Breakers ( RCCBs) must be selected sensitive to DC (class  B) and insensitive to transient current pulses 

Type S. 

Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. 

This equipment must be earthed in accordance with local electrical authority codes of practice. 

 

 

WARNING: backfeeding protection 

This  system  has  a  control  signal  available  for  use  with  an  automatic  device,  externally  located,  to  protect  against  backfeeding 

voltage through the mains Static Bypass circuit. If this protection is not used with the switchgear that is used to isolate the bypass 

circuit, a label must be added to the switchgear to advise service personnel that the circuit is connected to a UPS system. 

The text has the following meaning or is equivalent to: Isolate the UPS before working on the circuit of this UPS. 

 

 

 

警告

  

危 险

   

警告

  

危 险

   

警告

  

危 险

   

Содержание MUST400T

Страница 1: ...Quick Start Modular UPS MUST400T...

Страница 2: ...urer approved accessories only WARNING high earth leakage current Earth connection is critical before connecting the input supply include both utility supply and battery Earth leakage current introduc...

Страница 3: ...mal manner following the recommended operating procedures in this manual Battery voltage higher than 400Vdc All the battery maintenance and servicing procedures involving internal access need special...

Страница 4: ...xceed 400Vdc and is potentially lethal Follow the suggested actions here below Eye protection must be worn to prevent injury from accidental electrical arcs Remove rings watches and all metal objects...

Страница 5: ...re will reduce the battery life and operation below this temperature will reduce the battery capacity If the average operating temperature of battery is increased from 20 C to 30 C then the service li...

Страница 6: ...20 C to 25 C The batteries are at maximum efficiency in this temperature range for information about the battery storage and transportation as well as the environment refer to Table 9 2 This equipmen...

Страница 7: ...power terminals inside the UPS and all service activity it is recommended to leave enough free space to enable the passage of personnel with the doors fully opened It is important to leave a distance...

Страница 8: ...Quick start_MUST400T_ENG_REV00 8 a 10 module cabinet b 6 module cabinet Fig 1 1 UPS Structure...

Страница 9: ...xing holes on both sides of the front panel of the module See fig 1 2 Fig 1 2 Power Module Installation Diagram 1 4 9 Cable Entry Cables can enter into the UPS system both from bottom and top Cable en...

Страница 10: ...e RCD device installed upstream of the input supply should be comply with Sensitive to DC unidirectional pulses class A in the network Insensitive to transient current pulses Have an average sensitivi...

Страница 11: ...ermining the size of the output and bypass neutral cable as the current circulating on the neutral cable may be greater than nominal current in the case of non linear loads which is usually 1 732 time...

Страница 12: ...ut Connections 4 For common bypass and rectifier inputs connect the AC input supply cables to the UPS bypass terminals X2 L21 L22 L23 X1 N1 Refer to Fig 4 11 and tighten the connections to 5 Nm M6 Bol...

Страница 13: ...d the critical load and tighten the terminals screws to 5Nm M6 Bolt or to 13Nm M8 Bolt or to 25Nm M10 Bolt Note ENSURE CORRECT PHASE ROTATION WARNING If the load equipment will not be ready to accept...

Страница 14: ...an die USV abschlie en Ein Differentialschutz ist ratsam Conectar el cable de tierra a el SAE Se aconseja la protecction con el interruptor diferencial Attenzione batterie interne non aprire pericolo...

Отзывы: