background image

 

Quick start_MUST400T_ENG_REV00 

10 

1.5.1 Rectifier and Bypass Input Supply of the UPS 

Over currents 

Install suitable protective devices in the distribution unit of the incoming mains supply, considering the power 

cable current-carrying capacity and overload capacity of the system (

see Tab. 9-7

). Generally, the magnetic 

circuit  breaker  with  IEC60947-2  tripping  curve  C  (normal)  at  the  125%  of  the  current  listed  in  Tab.  9-7  is 

recommended.   

Dual input: In case of double mains used, separate protective devices should be installed for the rectifier input 

and bypass input in the incoming mains distribution panel. 

 

Note: The rectifier input and bypass input must use the same neutral line

So don’t remove the neutral common copper bridge present between input and bypass terminals     

 

 

Protection against earth faults (RCD devices): 

The RCD device installed upstream of the input supply should be comply with: 

Sensitive to DC unidirectional pulses (class A) in the network 

Insensitive to transient current pulses 

Have an average sensitivity that is adjustable between 0.3A and 1A. 

 

 

Fig.1- 3: The Symbols of RCCB 

 

When using the RCD in the split bypass system or parallel system, the RCD should be installed upstream of 

the input distribution to avoid wrong alarm. 

The residual current introduced by RFI filter in the UPS is between 3.5mA and 1000mA. It is recommended to 

confirm the sensitivity of each RCD of upstream input distribution and downstream distribution (to load). 

1.5.2 External Battery 

The  DC  compatible  circuit  breaker  provides  over  current  protection  for  UPS  system  and  battery,  which  is 

provided by the external battery cabinet.   

1.5.3 UPS Output 

In case of an external distribution cabinet is used for load distribution, the selection of protective 

devices must provide discrimination with those that are used at the input to the UPS   

(

see Tab. 9-7

). 

 

 

 

 

 

 

 

 

 

Содержание MUST400T

Страница 1: ...Quick Start Modular UPS MUST400T...

Страница 2: ...urer approved accessories only WARNING high earth leakage current Earth connection is critical before connecting the input supply include both utility supply and battery Earth leakage current introduc...

Страница 3: ...mal manner following the recommended operating procedures in this manual Battery voltage higher than 400Vdc All the battery maintenance and servicing procedures involving internal access need special...

Страница 4: ...xceed 400Vdc and is potentially lethal Follow the suggested actions here below Eye protection must be worn to prevent injury from accidental electrical arcs Remove rings watches and all metal objects...

Страница 5: ...re will reduce the battery life and operation below this temperature will reduce the battery capacity If the average operating temperature of battery is increased from 20 C to 30 C then the service li...

Страница 6: ...20 C to 25 C The batteries are at maximum efficiency in this temperature range for information about the battery storage and transportation as well as the environment refer to Table 9 2 This equipmen...

Страница 7: ...power terminals inside the UPS and all service activity it is recommended to leave enough free space to enable the passage of personnel with the doors fully opened It is important to leave a distance...

Страница 8: ...Quick start_MUST400T_ENG_REV00 8 a 10 module cabinet b 6 module cabinet Fig 1 1 UPS Structure...

Страница 9: ...xing holes on both sides of the front panel of the module See fig 1 2 Fig 1 2 Power Module Installation Diagram 1 4 9 Cable Entry Cables can enter into the UPS system both from bottom and top Cable en...

Страница 10: ...e RCD device installed upstream of the input supply should be comply with Sensitive to DC unidirectional pulses class A in the network Insensitive to transient current pulses Have an average sensitivi...

Страница 11: ...ermining the size of the output and bypass neutral cable as the current circulating on the neutral cable may be greater than nominal current in the case of non linear loads which is usually 1 732 time...

Страница 12: ...ut Connections 4 For common bypass and rectifier inputs connect the AC input supply cables to the UPS bypass terminals X2 L21 L22 L23 X1 N1 Refer to Fig 4 11 and tighten the connections to 5 Nm M6 Bol...

Страница 13: ...d the critical load and tighten the terminals screws to 5Nm M6 Bolt or to 13Nm M8 Bolt or to 25Nm M10 Bolt Note ENSURE CORRECT PHASE ROTATION WARNING If the load equipment will not be ready to accept...

Страница 14: ...an die USV abschlie en Ein Differentialschutz ist ratsam Conectar el cable de tierra a el SAE Se aconseja la protecction con el interruptor diferencial Attenzione batterie interne non aprire pericolo...

Отзывы: