The  Modular  series  UPS  uses  forced  convection  cooling  by  internal  fans.  Cooling  air  enters  the  module 

through ventilation grills located at the front part of the cabinet and exhausted through grills located in the rear 

part of the cabinet. Please do not block the ventilation holes. 

If necessary, an extractor fans system should be installed to aid cooling-air flow.   

An  air  filter  should  be  used  when  the  UPS  is  to  operate  in  a  dirty  environment  and  should  be  regularly 

cleaned to maintain proper airflow.   

The cooling capacity of air conditioner should be selected according to the power loss data of UPS specified 

in 

Table.9-8

: Normal mode (VFI SS 111 double-conversion UPS) 

Note 1 : The UPS should be installed on a concrete surface or other surface that is not combustible. 

Note  2  :  Ensure  that  the  capacity  of  the  floor is  greater  than  the  weight  of  the  UPS and battery  cabinet  (if 

present), and verify that the floor is flat.   

1.3.2 External Battery Room 

The  battery  will  generate  some  amount  of  hydrogen  and  oxygen  at  the  end  of  charging,  so  the  fresh  air 

volume of the battery installation environment must meet EN50272-2001 requirements. 

The  environmental  temperature  of  the  battery  must  be  stable.  Ambient  temperature  is  a  major  factor  in 

determining the battery capacity and lifetime.   

The rated operating temperature of battery is 20°C. Operating above this temperature will reduce the battery 

life,  and  operation  below  this  temperature  will  reduce  the  battery  capacity.  If  the  average  operating 

temperature of battery is increased from 20ºC to 30ºC, then the service life of the battery will be reduced by 

50%. If the operating temperature of the battery is above 40ºC, then the battery service life will decrease in 

exponential rate.   

In a normal installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away 

from heat sources or air outlets. 

If external batteries are used, the battery circuit breakers (or fuses) must be mounted as close as possible to 

the batteries, and the connecting cables should be as short as possible. 

 

(*): The standard EN 50272-2   for air change envisages that the minimum opening must satisfy the following equation: 
 

A = 28 x Q = 28 x 0.05 x n x Igas x C10 (1/10³) [cm²]    

 

where:                          A =   free opening for air intake and outlet 

Q =       flow of air to be removed [m³/h] 
n      =    number of battery elements; 
C10 =   battery capacity over 10 hours [Ah] 
Igas =   current that produces gas [mA//Ah] 

                                      in accordance with the standard:       Igas = 1 VRLA type battery   
 
When the equation is applied for 240 element (40 battery)   hermetically-sealed lead batteries: 

A = 336 x C10 / 10³   [cm²] 

When using 120Ah batteries, the minimum aperture should be approximately: 

A =   41 [cm²] 

 

 

 

 

1.3.3 Storage 

If the equipment is not installed immediately, it must be stored in a room protected against excessive humidity 

and heat sources (see 

Table.9-2

). 

The battery needs to be stored in dry and cool place with good ventilation.   

The most suitable storage temperature is from 20 ºC to 25ºC. 

Preventing battery slow discharge 

警告

  

危 险

   

Содержание MUST400T

Страница 1: ...Quick Start Modular UPS MUST400T...

Страница 2: ...urer approved accessories only WARNING high earth leakage current Earth connection is critical before connecting the input supply include both utility supply and battery Earth leakage current introduc...

Страница 3: ...mal manner following the recommended operating procedures in this manual Battery voltage higher than 400Vdc All the battery maintenance and servicing procedures involving internal access need special...

Страница 4: ...xceed 400Vdc and is potentially lethal Follow the suggested actions here below Eye protection must be worn to prevent injury from accidental electrical arcs Remove rings watches and all metal objects...

Страница 5: ...re will reduce the battery life and operation below this temperature will reduce the battery capacity If the average operating temperature of battery is increased from 20 C to 30 C then the service li...

Страница 6: ...20 C to 25 C The batteries are at maximum efficiency in this temperature range for information about the battery storage and transportation as well as the environment refer to Table 9 2 This equipmen...

Страница 7: ...power terminals inside the UPS and all service activity it is recommended to leave enough free space to enable the passage of personnel with the doors fully opened It is important to leave a distance...

Страница 8: ...Quick start_MUST400T_ENG_REV00 8 a 10 module cabinet b 6 module cabinet Fig 1 1 UPS Structure...

Страница 9: ...xing holes on both sides of the front panel of the module See fig 1 2 Fig 1 2 Power Module Installation Diagram 1 4 9 Cable Entry Cables can enter into the UPS system both from bottom and top Cable en...

Страница 10: ...e RCD device installed upstream of the input supply should be comply with Sensitive to DC unidirectional pulses class A in the network Insensitive to transient current pulses Have an average sensitivi...

Страница 11: ...ermining the size of the output and bypass neutral cable as the current circulating on the neutral cable may be greater than nominal current in the case of non linear loads which is usually 1 732 time...

Страница 12: ...ut Connections 4 For common bypass and rectifier inputs connect the AC input supply cables to the UPS bypass terminals X2 L21 L22 L23 X1 N1 Refer to Fig 4 11 and tighten the connections to 5 Nm M6 Bol...

Страница 13: ...d the critical load and tighten the terminals screws to 5Nm M6 Bolt or to 13Nm M8 Bolt or to 25Nm M10 Bolt Note ENSURE CORRECT PHASE ROTATION WARNING If the load equipment will not be ready to accept...

Страница 14: ...an die USV abschlie en Ein Differentialschutz ist ratsam Conectar el cable de tierra a el SAE Se aconseja la protecction con el interruptor diferencial Attenzione batterie interne non aprire pericolo...

Отзывы: