1.1-1.7-2.2-3 kVA
Installation and operating manual
GB
004
DR
WNETR
T-XX
Страница 1: ...1 1 1 7 2 2 3 kVA Installation and operating manual GB 004 DRWNETRT XX...
Страница 2: ...esult in a reduction of the original warranty period The warranty on the product does not cover damage occasioned by thoughtlessness improper use wrong input power explosions excessive humidity temper...
Страница 3: ...NNECTIONS 13 5 CONNECTION OF BATTERY EXTENSION 14 5 1 Safety warnings 14 5 2 Connection of battery extension 14 6 MIMIC PANEL 16 7 OPERATING MODES 17 7 1 Battery recharge 17 7 2 Switching the Netys RT...
Страница 4: ...oreign objects into the cabinet If the appliance is to be scrapped it must be entrusted exclusively to a specialist waste disposal company These companies will split up and dispose of the various comp...
Страница 5: ...on the inside and outside of the equipment should be respected DANGER HIGH VOLTAGE BLACK YELLOW GROUND TERMINAL READ THE USER MANUAL BEFORE USING THE UNIT 085 DRWNETRT XX 1 1 Legend B Contactor solen...
Страница 6: ...k that the operating voltage and frequency settings are correct for the mains power supply at the installation site Details for the UPS will be found on the data plate affixed to the rear panel When m...
Страница 7: ...RTXX00 GB 00 ENGLISH 2 INSTALLATION 2 2 Vertical installation 2 2 1 UPS Installation 2 2 2 UPS Installation with 1 battery extension 4 4 2 1 3 026 DRWNETRT XX 031 DRWNETRT XX 035 DRWNETRT XX 059 DRWNE...
Страница 8: ...8 1 1 3 kVA Ref IOMNETRTXX00 GB 00 2 2 3 UPS Installation with multiple battery extensions 2 INSTALLATION 4 2 1 3 036 DRWNETRT XX 033 DRWNETRT XX 059 DRWNETRT XX 028 DRWNETRT XX...
Страница 9: ...3 kVA Ref IOMNETRTXX00 GB 00 ENGLISH 2 INSTALLATION 2 3 Horizontal installation on rack 2 3 1 Rotation of mimic pannel 038 DRWNETRT XX 043 DRWNETRT XX 042 DRWNETRT XX 041 DRWNETRT XX 039 DRWNETRT XX...
Страница 10: ...10 1 1 3 kVA Ref IOMNETRTXX00 GB 00 2 3 2 Fitting rack brackets 2 INSTALLATION 044 DRWNETRT XX 046 DRWNETRT XX 1 2 3 045 DRWNETRT XX...
Страница 11: ...ack 1 Adapt the length of the tracks to fit the rack 2 Secure the wing nuts 3 Fix the track to the rack 4 Slot in the UPS and tighten the screws 2 INSTALLATION MAX 100 kg MAX 100 kg MAX 100 kg MAX 100...
Страница 12: ...2200 VA G G G F F F E E E D D D B B B C C H H H L L L L M P L N N I I I A A A L O N Legend A Mains input socket IEC 320 B Fan C Output socket full power D Telephone socket input E Telephone socket ou...
Страница 13: ...lt whereas the external contact must be made between the common and input pins The external contact MUST be dedicated and voltage free so as not to cause permanent damage to the UPS 4 CONNECTIONS 1100...
Страница 14: ...rous to touch any part of the battery storage unit 5 2 Connection of battery extension WARNING Before commencing any operation make certain that the voltages of the UPS battery and of the battery exte...
Страница 15: ...ECT 40A 24V COM SLOT IN OUT LOAD 1 LOAD 2 RS232 BREAKER INPUT EPO SURGE PROTECT LOAD 3 INPUT 40A 48V COM SLOT 1100 VA 1700 VA 2200 VA 3000 VA IN OUT LOAD 1 LOAD 2 RS232 BREAKER INPUT EPO SURGE PROTECT...
Страница 16: ...Normal operation inverter in line D Red symbol lit Fault E ON TEST and buzzer override button F LED bar Depending on the situation this indi cates either the charge level figure 7 1 1 or the capacity...
Страница 17: ...ould occur the duration of the backup will be shorter 7 OPERATING MODES 3 sec 3 sec 7 1 1 7 2 1 1 7 2 2 1 7 2 1 2 7 2 2 2 Normal operation 7 2 1 3 Normal operation 7 2 Switching the Netys RT ON and OF...
Страница 18: ...tton to activate deactivate Battery mode the buzzer 7 OPERATING MODES UPS is off but battery remains on charge Shut down all loads one at a time Switch off mains power to shut down completely 10 sec 7...
Страница 19: ...or 1 second to exit the procedure 7 3 1 Standby mode 7 3 3 230 Vac mode 230 Vac mode 240 Vac mode 200 Vac mode 1 208 Vac mode 220 Vac mode 7 3 2 7 3 4 7 3 5 006 DRWNETRT XX 136 DRWNETRT XX 136 DRWNETR...
Страница 20: ...1 By pass mode 8 7 Overtemperature 8 10 Inverter undervoltage 8 13 DC BUS line overvoltage 8 4 Battery needs replacing 8 2 Overload 8 8 Battery charge failure 8 11 Inverter overvoltage 8 14 High AC i...
Страница 21: ...without the need to install any additional software Once connected recognition of the UPS occurs in the same way as for any other peripheral and the operating parameters can be managed by way of the...
Страница 22: ...t Tx Rx GND C SW1 SW2 GND R R1 General alarm R2 No mains R3 Battery low R4 On by pass R5 Overload R6 Overtemperature 9 5 1 1 9 5 1 3 9 5 1 2 SW1 SW2 relay contact OFF OFF NO ON OFF NC GND R Relay grou...
Страница 23: ...99 seconds maximum 3 Press 3 to configure NO or NC operation of each relay Shift SW2 to the ON position to activate the settings If SW2 is returned to the OFF position SW1 can be used to check the NO...
Страница 24: ...f 8 hours UPS in overload Disconnect non essential loads Depleted batteries The batteries will degrade quickly if used fequently or in high operating temperatures Should the batter ies have reached th...
Страница 25: ...ut output RJ11 or RJ45 Technology On line double conversion VFI SS 111 Batteries Type Maintenance free sealed lead life expectancy 3 5 years Typical backup 7 minutes 7 minutes 7 minutes 8 minutes Comm...
Страница 26: ...wowiejska St 21 25 00 665 Warszawa Tel 48 0 22 2345 223 Fax 48 0 22 2345 223 ups poland socomec com PORTUGAL Rua Moinho do Cuco Bloco A Lj Dta Paz 2640 566 MAFRA Tel 351 261 812 599 Fax 351 261 812 57...