Figure 2A - Installation Components.

Figure 2B - Installation Options.

Figure 2B shows the location of a pressure relief and/or
expansion tank if a check valve or pressure-reducing valve
is in the cold water supply to the house.
Use OPTION 1 or 2 whichever is more convenient. If pres-
sure relief valve is used, select one with a setting 172 kPa
(25 psi) below the T&P valve rating at tank.

Venting

Make certain to observe the vent location limitations com-
plying with the 

"Natural Gas and Propane Installation

Code" CAN/CSA-B149.1

or 

"National Fuel Gas Code"

ANSI Z223.1 (NFPA 54)

and/or local codes. There is some

important information shown in Figure 3.

For a second or more direct vent unit, the distance between
vent terminals must have a minimum of 305mm (12 in.).
INSPECT SHIPMENT –– There may be hidden damage
caused by transit. Check to be certain all parts of the vent-
ing system, as shown in Figures 3A through 3M, are pres-
ent. Inspect the upper and lower air inlet boxes, rear air tube
and all parts of the venting system (see Figure 2A).

CAUTION
If there are any damaged parts, DO NOT install this water
heater. Report any shortage to your distributor and damage
to your carrier.

Note:

The four fasteners that are required to secure the

vent terminal to the exterior wall are not provided. These
should be screw type (not nails) chosen for the type of con-
struction and obtained locally.

CAUTION
Cut edges of corrugated (flex) pipe are extremely sharp.
Wear gloves when handling.

OPTION 1

OPTION 2

SEDIMENT
TRAP

152mm (6 in.)

HOT WATER
OUTLET

GAS SUPPLY
MANUAL
SHUT-OFF
VALVE

GROUND-JOINT
UNION

FLOOR DRAIN

TEMPERATURE

& PRESSURE

RELIEF VALVE

COLD WATER
INLET

GAS CONTROL

UPPER AIR
INLET BOX

REAR AIR
TUBE

DRAIN PAN

EXPANSION TANK

WATER SUPPLY
TO HOME

WATER METER
WITH BACKFLOW
PREVENTER

P R E S S U R E
RELIEF VALVE

OVERFLOW

WATER SUPPLY
TO METER

FLOOR DRAIN

Figure 3 - Vent Location Limitations

Vent Terminal must be located at
least 305mm (12 in.) from
Windows, Doors, or any other
Opening through which flue
gases could enter the building.

Any Forced Air Inlet
into the building

V

ent 

Terminal must be located at least 457mm

(18 in.) from any overhang or building corner

or other irregularity

.

305mm (12 in.) Min.
above grade. Higher in
Areas of Heavy Snowfall

Within 1.8m (6 ft.)

915mm

(36 in.)

Min.

305mm

(12 in.)

Min.

Vent terminal must
be located at least
915mm (36 in.)
above any Forced Air
Inlet into the building
within 3m (10 ft.) of
the Vent Terminal

457mm (18 in.)

Min.

EXPANSION
TANK

LOWER AIR
INLET BOX

Содержание 61009 (09-03)

Страница 1: ...other flammable vapours and liquids in the vicinity of this or any other appliance Installation and service must be per formed by a qualified installer service agency or the gas utility Do not try to...

Страница 2: ...0 IV OPERATING INSTRUCTIONS 11 Lighting instructions Robertshaw 110R Lighting instructions White Rodgers 37C Special note on propane fuel Out of fuel Water Temperature Regulation 13 Exposure to water...

Страница 3: ...r any property damage personal injury or death resulting from improper sizing installation or failure to comply with these instructions The warranty on this water heater is in effect only when the wat...

Страница 4: ...nts T P All water heaters must be fitted with a proper temperature and pressure relief valve These valves must be certified as meeting the requirements of the Standard For Relief Valves For Hot Water...

Страница 5: ...minimum of 915mm 3 ft of clearance is required at the front control side of the heater for service For a closet installation the door at burner side should be openable and a minimum of 102mm 4 in cle...

Страница 6: ...tributor and damage to your carrier Note The four fasteners that are required to secure the vent terminal to the exterior wall are not provided These should be screw type not nails chosen for the type...

Страница 7: ...and terminal are assembled by the manufac turer as shown in Figure 3C There are springs fastened inside the corrugated pipe When the vent pipes are pulled to a required length the distances between t...

Страница 8: ...he vent pipe s level or slope again and adjust if required Offset vent pipe arrangement Figure 3K CONDITION 1 Where a straight vent pipe arrangement is impossible a horizontal 90 degree maximum bend c...

Страница 9: ...be installed ahead of the gas valve to permit easy removal of the unit All leak testing must be done with a soapy water solution NEVER USE A MATCH OR OPEN FLAME TO TEST FOR GAS LEAKS A FIRE OR EXPLOSI...

Страница 10: ...preventer or water pressure reducing valve This will create a closed water system During the heating cycle of the water heater the water expands caus ing pressure inside the water heater to increase...

Страница 11: ...setting 10 Replace the outer door 1 Set the thermostat to lowest setting Turn counter clockwise 2 Turn the gas control knob OFF Rotate clockwise WARNING If you do not follow these instructions exactly...

Страница 12: ...replace the outer burner door 12 Set thermostat to desired setting 13 If the pilot will not stay lit after several tries turn the gas control knob clock wise to OFF see Figure A If the appliance will...

Страница 13: ...burner and pilot flames The burner flames must be a soft blue flame with no yellow tips Yellow tips indicate a carbonizing flame which can depending on severity deposit carbon soot on the combustion c...

Страница 14: ...off at the inlet to the heater 2 Turn water off at the cold water inlet valve 3 Open a nearby hot water tap 4 Drain approximately one pail full of water from the heater 5 With a 1 1 16 in hexagon sock...

Страница 15: ...or space heating 5 If the space heating water system requires water with temperatures in excess of 60 C 140 F a mixing valve or other means must be installed in the potable hot water supply to temper...

Страница 16: ...cturer will furnish the Owner with a replacement for the defective part s This warranty is limited to one replacement component part for each original part 3 Return of Defective Water Heater and Compo...

Страница 17: ...rges for labour or other expenses incurred in the removal repair or replacement of the water heater or any component part s claimed to be defective or any expense incurred to remedy any defect in the...

Отзывы: