Features 

 

Providing two tones. 

 

Initiated by shorting external terminals, not affected 
by loop power cut. 

 

Polarity insensitive signal loop and power loop, with 
features of cable checking in case of power cut.   

 

Standard: EN 54-3. 

Description 

I-9404  Intelligent  Sounder  is  a  kind  of  audible  alarm 
device  initiated  by  control  panel  or  manual  call  point  in 
fire  room  or in the  field. It can  give  audible  alarm  when 
applied to warn people in field. 

The sounder can use shallow base with 25.5mm high or 
deep  base  with  40mm  high,  it  employs  deep  base  if 
there is no special statement in this manual.

 

Connection and Wiring 

Terminals on the base are shown in Fig. 2. 

G

1

K

1

D

D

2

1

2

Z

2

K

S

Z

97.5mm

80mm

55mm

Arch knock off Hole

5mm

       

Fig. 1                                      Fig. 2

 

Z1(2),  Z2(4):  Signal  loop  of  control  panel,  polarity 
insensitive.   
D1 (9), D2 (7): To 24VDC power, polarity insensitive. 
S(5), G(10): Controlled volt-free input.   

Recommended Wiring 

1.5mm

2

 or above fire cable for D1, D2, S, and G.   

1.0mm

2

 or above fire cable for other terminals, subject to 

local codes. 

Installation 

 

When  the  sounder  is  inside  the  wall,  it  can  be 

mounted on the electrical box, using a shallow base or a 
deep  base.  When  the  sounder  is  on  the  surface  of  the 
wall,  it  should  be  mounted  on  the  locations  where  it  is 
0.2m from the ceiling, using a deep base only. Knock the 
knock-off  hole  (Fig.  1),  then  connect  with  the  cable 
conduit. When using a deep base, refer to Fig. 2 for hole 
spacing  and  direction,  and  Fig.  3a  and  Fig.  4  for  its 
mounting  method.  When  using  a  shallow  base,  the 
sounder has to be mounted in the wall, shown in Fig.3b. 

 

The  base  and  the  sounder  are  twisted  together. 

When  mounting,  remove  the  sounder,  thread  cables 
through  the  cable  entry  in  the  base  and  connect  with 
corresponding terminals, then twist the sounder onto the 
base. 

 

If the sounder is required anti-removal, knock down 

the arch knock-off hole as shown in Fig. 1 and fix it with 
ST2.9

×

6.5  tapping  screws  (in  this  case,  it  must  be 

removed by special tools). 

Sounder 

Knock-off Hole

Conduit

Electrical Box

 

Fig. 3a 

Sounder

Conduit

Electrical Box

 

Fig. 3b 

                           

Conduit

Sounder

 

            Fig. 4 

Application 

Address  can  be  programmed  through  programmer. 
Refer  to  P-9910B  Hand  Held  Programmer  Installation 
and Operation Manual for further details.   

 

When device type of the sounder is 121, it occupies 

two  consecutive  addresses;  when  device  type  is  other 

I-9404 

  Intelligent Sounder

 

 