GST301 Extinguishing Control Panel
Installation and Operation Manual
Page 14
Check the cables before connecting them to the panel. Ensure that there is no
problem of short circuit, open circuit, earth fault and cross connection, etc.
Note: If any zone, alarm circuit, or cylinder circuit is not used, an end of
line resistor must be connected to the corresponding terminal.
3
)
Configuration (refer to Clause 6 of Section 5)
Set the discharge/fire/fault/stage 2 remote output mode, NO or NC.
Set the sounder1/sounder2/cylinder output mode, ACTIVE, NO or NC.
Set emergency start with delay or without delay.
Set remote discharge output by pressure switch or by gas release output
action.
Set delay time and output pulse duration.
4
)
Power Up
Connect the A.C mains to the panel and turn on the break.
Note: Do not switch on the mains supply before connecting well.
5
)
Battery Connection. If the panel reacts well after mains on, you can disconnect
the mains and connect the batteries with correct polarity.
3
Manual Operations
1) Starting gas release from the panel
Press the “START” key on the panel will start the gas release output without
any delay. This operation is controlled under “Control Enable” switch (by key).
2) Starting gas release in field
Press the Emergency Start button on field will start the gas release output with
or without delay (configurable). This function is not inhibited by “Auto Enable”
setting.
3) Stopping gas release from the panel
During the gas release delay timing, press the
“STOP”
key will stop the timer.
The output terminal will be electronically isolated. This function is not inhibited
by “Auto Enable” and “CONTROL ENABLE” setting.
Note: if the timer is
finished and the panel is starting the gas release action, the stop
operation will not function.
4) Stopping gas release in field
During the gas release delay time, press the emergency abort switch will stop
the timer.
The output terminal will be electronically isolated. This function is not
inhibited by “Auto Enable” and “Control Enable” setting.
Note: if the timer is
finished and the panel is starting the gas release action, the stop
operation will not function.
5) Silencing the sounders & alarming panel
Press “Silence” key to stop sounder outputs and the buzzer of the
panel. This
operation is controlled under “Control Enable” switch.
Note: if the “Evacuate”
key is active, the “Silence” key
will not act.
(If it’s within gas release delay
time, pressing “Silence” will not stop the panel alarming. The sounder outputs
will be resumed in the last 15 seconds.)
.
6) Starting the sounders