GST301 Extinguishing Control Panel
Installation and Operation Manual
Page 9
(8) Aux +, Aux -: Aux power supply (100mA/24VDC).
(9) Standby +, - / Primary +, -: Gas release output connecting with primary and
standby cylinder. 2A/24VDC active output can be set to NO/NC type. 2 to 45
seconds adjustable pulse output.
(10) K2, K1: Pressure switch input connecting with cylinder pressure switch. Dry
contact input.
(11) Stage 2: Pre-release remote output. NO dry contact.
(12) Discharge: Gas discharge remote indication output. NO/NC dry contact.
(13) Fire: Fire remote indication output. NO/NC dry contact.
(14) Fault: Fault remote indication output. NO/NC dry contact.
5
Wiring
1) Recommended cabling
a) 227 IEC 02 fire cable with cross section not less than 1.5mm
2
for Zone,
Sounder, Remote Output, Emergency Start/Abort button and AUX Power.
b) 1.5mm
2
or above 227 IEC 02 fire cable for Cylinder Output (Primary & Standby)
and Battery connection. If the cable length is more than 50 meters, 2.5mm
2
or
above 227 IEC 02 fire cable should be used.
2) Wiring in the loop of detector
a) Wiring diagram when using Active End of Line unit is shown in Fig. 8.
Zone
Input
Terminals
Panel
+
-
470
Ω
(normal)
A.E.O.L
MCP
-
+
Fig. 8 Wiring diagram when using Active End of Line unit
b) Wiring diagram when using End of Line resistor is shown in Fig. 9.
Zone
Input
Terminals
Panel
+
-
470
Ω
(normal)
MCP
470
Ω
(normal)
MCP
4.7k
Ω
Resistor
No Diode
Fig. 9 Wiring diagram when using End of Line resistor
c) Wiring method of gas override control is shown in Fig. 10.