background image

 

 

 

 

 

 

C-9102 (UL) Conventional 

Photoelectric Smoke Detector 

Installation and Operation Manual

 

(Issue 1.04, July 2012)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание C-9102

Страница 1: ...C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual Issue 1 04 July 2012...

Страница 2: ...Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 2 VI Testing 4 VII Troubleshooting 5 VI...

Страница 3: ...ons 1 Operating Voltage 12VDC 28VDC 2 Operating Current Standby Current 60 A Alarm Current 10mA I 30mA Note The alarm current depends on the current limit of the FACP It s not allowed to power the det...

Страница 4: ...rticles In smokeless condition it only receives very weak infrared light When smoke particles enter the received light signal increases by scattering When smoke reaches certain density it can output a...

Страница 5: ...There are four terminals with numbers on the base 1 connects with the anode of the output end of compatible FACP 2 connects with terminal No 1 of the next base as output 3 connects with terminal No 3...

Страница 6: ...this function only when necessary to avoid trouble in maintenance and repair 5 Location and Spacing 1 The horizontal distance from the detector to the wall or the girder should not be less than 0 5m...

Страница 7: ...s sensitivity Fig 6 Testing 4 After testing reset the detector by power cut over 5s Notify the proper authorities the system is back in operation 5 If a detector fails in testing clean it as described...

Страница 8: ...totally cleaned you can take down the sensing chamber and pull out the insect net along axle clean or replace the insect net then remove the dust on the sensing chamber by vacuum pump or cleaner and...

Страница 9: ...ions and relative national code 9 The detector should be tested regularly at least once a year X Quality Warranty This detector is approved by UL as a recognized component It s strongly recommended th...

Страница 10: ...Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 86 0 335 8502434 Fax 86 0 335 8502532 service gst fs utc com www gst com cn 30302468...