background image

C-9102 (UL)

 

Conventional Photoelectric Smoke Detector

 

              

                             

 

                

Installation and Operation Manual

 

  

                                                  

      

    

 

 

Page 3  

 

 

 

 

 

 

 

 

 

 

Fig. 2 

 

Mounting 

2.  Bottom and base of the detector is shown in Fig. 3 and Fig. 4. 

 

 

 

 

 

 

 

 

 

 

Fig. 3

 

Bottom of the detector             Fig. 4

 

Orientation base 

3.  Wiring Method 

The base of the detector is DZ-03 Base produced by GST.  The bottom of the detector 

and  the  orientation  base  are  shown  in  Fig.  3  and  4.    There  are  four  terminals  with 
numbers on the base, “1” connects with the anode of the output end of compatible FACP,  
“2” connects with terminal No. “1” of the next base as output,  “3” connects with terminal 
N

o. “3” of the next base and the cathode  of the output end of compatible FACP, “4” 

doesn’t  connect  to  any  wires  but  is  used  to  fix  the  detector  accessorily.  A  4.7k/1w 
terminal resistor can be connected between terminal “2” and “3” of the last base in a 
loop.  System connection is shown in Fig. 5. 

 

 

 

 

 

 

 

 

探测器底部

防尘罩

迷宫

螺钉

防虫网

上盖

Wiring Tube

Orientation Base

Detector

Embedded Box

C

Record Label

0

Mounting Hole

3

B

-Z

D

A

Содержание C-9102

Страница 1: ...C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual Issue 1 04 July 2012...

Страница 2: ...Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 2 VI Testing 4 VII Troubleshooting 5 VI...

Страница 3: ...ons 1 Operating Voltage 12VDC 28VDC 2 Operating Current Standby Current 60 A Alarm Current 10mA I 30mA Note The alarm current depends on the current limit of the FACP It s not allowed to power the det...

Страница 4: ...rticles In smokeless condition it only receives very weak infrared light When smoke particles enter the received light signal increases by scattering When smoke reaches certain density it can output a...

Страница 5: ...There are four terminals with numbers on the base 1 connects with the anode of the output end of compatible FACP 2 connects with terminal No 1 of the next base as output 3 connects with terminal No 3...

Страница 6: ...this function only when necessary to avoid trouble in maintenance and repair 5 Location and Spacing 1 The horizontal distance from the detector to the wall or the girder should not be less than 0 5m...

Страница 7: ...s sensitivity Fig 6 Testing 4 After testing reset the detector by power cut over 5s Notify the proper authorities the system is back in operation 5 If a detector fails in testing clean it as described...

Страница 8: ...totally cleaned you can take down the sensing chamber and pull out the insect net along axle clean or replace the insect net then remove the dust on the sensing chamber by vacuum pump or cleaner and...

Страница 9: ...ions and relative national code 9 The detector should be tested regularly at least once a year X Quality Warranty This detector is approved by UL as a recognized component It s strongly recommended th...

Страница 10: ...Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 86 0 335 8502434 Fax 86 0 335 8502532 service gst fs utc com www gst com cn 30302468...

Отзывы: