C-9102 (UL)
Conventional Photoelectric Smoke Detector
Installation and Operation Manual
Page 3
Fig. 2
Mounting
2. Bottom and base of the detector is shown in Fig. 3 and Fig. 4.
Fig. 3
Bottom of the detector Fig. 4
Orientation base
3. Wiring Method
The base of the detector is DZ-03 Base produced by GST. The bottom of the detector
and the orientation base are shown in Fig. 3 and 4. There are four terminals with
numbers on the base, “1” connects with the anode of the output end of compatible FACP,
“2” connects with terminal No. “1” of the next base as output, “3” connects with terminal
N
o. “3” of the next base and the cathode of the output end of compatible FACP, “4”
doesn’t connect to any wires but is used to fix the detector accessorily. A 4.7k/1w
terminal resistor can be connected between terminal “2” and “3” of the last base in a
loop. System connection is shown in Fig. 5.
探测器底部
防尘罩
迷宫
螺钉
防虫网
上盖
Wiring Tube
Orientation Base
Detector
Embedded Box
C
Record Label
0
Mounting Hole
3
B
-Z
D
A