C-9102 (UL)

 

Conventional Photoelectric Smoke Detector

 

              

                             

 

                

Installation and Operation Manual

 

  

                                                  

      

    

 

 

Page 7  

detectors before beginning construction or other dust producing activity. Be sure to 

notify the proper authority for the removal of the detectors. 

3. 

In maintenance, note to be careful to avoid damage to the detector. 

4. 

The detector may not sense fire that starts where smoke cannot reach it such as in 

chimneys, in walls, on roof, or on the other side of closed doors. 

5. 

The detector cannot detect fire beyond its monitoring area. 

6. 

The detector may not  alarm in time for fire caused  by inadequate fire protection 

measures, explosion, gas leakage, arson and children playing with fire. 

7. 

In  high  velocity  environment,  the  alarm  may  be  delayed  by  dilution  of  smoke 

density due to frequent and fast air exchange. 

8. 

The detector has a limited life.  To ensure the detector is always in good operation 
state, please maintain it according manufacturer’s recommendations and relative 
national code. 

9. 

The detector should be tested regularly, at least once a year. 

X  Quality Warranty  

This  detector 

is  approved  by  UL  as  a  recognized  component.  It’s  strongly 

recommended that fire alarm control panel manufacturers intending to use this detector 

in their fire alarm systems to verify system compatibility before application in order to 

avoid system failure.  

Gulf  Security  Technology  Co.,  Ltd.

  warrants  that  the  detector  will  be  free  from 

defects in design, materials and workmanship. The warranty is valid for a period of 2 

years from time of dispatch

.  This warranty shall not apply to any product that is found 

to  have  been  improperly  installed  or  used  in  any  way  not  in  accordance  with  the 

instructions supplied with the product.   Anybody, including the agents, distributors or 

employees, is not in the position to amend the contents of this warranty. Products not 

covered by this warranty shall also be returned for repair.  Please return the products 

together with a description of fault and possible reason to 

No.80 Changjiang East Road, 

QETDZ, Qinhuangdao, Hebei, P.R. China, Gulf Security Technology Co., Ltd. Postcode: 

066004. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание C-9102

Страница 1: ...C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual Issue 1 04 July 2012...

Страница 2: ...Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 2 VI Testing 4 VII Troubleshooting 5 VI...

Страница 3: ...ons 1 Operating Voltage 12VDC 28VDC 2 Operating Current Standby Current 60 A Alarm Current 10mA I 30mA Note The alarm current depends on the current limit of the FACP It s not allowed to power the det...

Страница 4: ...rticles In smokeless condition it only receives very weak infrared light When smoke particles enter the received light signal increases by scattering When smoke reaches certain density it can output a...

Страница 5: ...There are four terminals with numbers on the base 1 connects with the anode of the output end of compatible FACP 2 connects with terminal No 1 of the next base as output 3 connects with terminal No 3...

Страница 6: ...this function only when necessary to avoid trouble in maintenance and repair 5 Location and Spacing 1 The horizontal distance from the detector to the wall or the girder should not be less than 0 5m...

Страница 7: ...s sensitivity Fig 6 Testing 4 After testing reset the detector by power cut over 5s Notify the proper authorities the system is back in operation 5 If a detector fails in testing clean it as described...

Страница 8: ...totally cleaned you can take down the sensing chamber and pull out the insect net along axle clean or replace the insect net then remove the dust on the sensing chamber by vacuum pump or cleaner and...

Страница 9: ...ions and relative national code 9 The detector should be tested regularly at least once a year X Quality Warranty This detector is approved by UL as a recognized component It s strongly recommended th...