background image

C-9102 (UL)

 

Conventional Photoelectric Smoke Detector

 

              

                             

 

                

Installation and Operation Manual

 

  

                                                  

      

    

 

 

Page 5  

1)  Field testing can be done by Trut300 Smoke Detector Sensitivity Tester of No Climb 

Products  Ltd.  (for  detailed  description,  please  refer  to  Trutest  Smoke  Detector 

Sensitivity  Tester  User  Manual  Issue2.1c)  or  similar  smoke  generating  tools.    If 

Trut300  is  used,  adjust  its  obscuration  to  1.7%  /ft  to  2.6%  /ft  according  to  the 
manual,  start  testing  until  the  detector  alarms.  If  the  tester  shows  “pass”,  the 
detector passes the test.   

2)  You can also use similar smoke generating tools (cigarette or smoke gun) and blow 

the smoke at the smoke-in hole (Fig. 6) into the detector until it alarms. 

Note: This test is only used for verifying the ability of the detector to alarm after smoke 

enters.  It cannot be used to test its sensitivity. 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6 Testing 

4.  After testing, reset the detector by power-cut over 5s.  Notify the proper authorities 

the system is back in operation. 

5.  If a detector fails in testing, clean it as described in "Maintenance" and test again.  If 

it still fails, please return it for repair. 

VII Troubleshooting 

In  case  of  any  fault,  check  connecting  cables  and  fixing  screws  first,  then  open  the 

housing to see if there is loose soldering or blown parts. 

Possible trouble and solution during operation are as follows: 

1. 

No alarm:  

Check whether the detector is securely installed on the base.  There should be DC24V 

voltage on terminals No. 1 and 3 of the base, if not, check the cable with the FACP open 

or not. 

2. 

Nuisance alarm:  

Check the LED on the detector lit or not. If not, check the polarity of wiring and whether 

there are short circuits on terminating resistor.  If it's lit, check whether the chamber in 

the detector is too dirty and needs to be cleaned.  Otherwise, the circuit may be broken. 

LED 

Smoke in 

Recess 

Содержание C-9102

Страница 1: ...C 9102 UL Conventional Photoelectric Smoke Detector Installation and Operation Manual Issue 1 04 July 2012...

Страница 2: ...Installation and Operation Manual CONTENTS I General 1 II Features 1 III Technical Specifications 1 IV Structure and Operation Principle 2 V Mounting and Wiring 2 VI Testing 4 VII Troubleshooting 5 VI...

Страница 3: ...ons 1 Operating Voltage 12VDC 28VDC 2 Operating Current Standby Current 60 A Alarm Current 10mA I 30mA Note The alarm current depends on the current limit of the FACP It s not allowed to power the det...

Страница 4: ...rticles In smokeless condition it only receives very weak infrared light When smoke particles enter the received light signal increases by scattering When smoke reaches certain density it can output a...

Страница 5: ...There are four terminals with numbers on the base 1 connects with the anode of the output end of compatible FACP 2 connects with terminal No 1 of the next base as output 3 connects with terminal No 3...

Страница 6: ...this function only when necessary to avoid trouble in maintenance and repair 5 Location and Spacing 1 The horizontal distance from the detector to the wall or the girder should not be less than 0 5m...

Страница 7: ...s sensitivity Fig 6 Testing 4 After testing reset the detector by power cut over 5s Notify the proper authorities the system is back in operation 5 If a detector fails in testing clean it as described...

Страница 8: ...totally cleaned you can take down the sensing chamber and pull out the insect net along axle clean or replace the insect net then remove the dust on the sensing chamber by vacuum pump or cleaner and...

Страница 9: ...ions and relative national code 9 The detector should be tested regularly at least once a year X Quality Warranty This detector is approved by UL as a recognized component It s strongly recommended th...

Страница 10: ...Gulf Security Technology Co Ltd No 80 Changjiang East Road QETDZ Qinhuangdao Hebei P R China 066004 Tel 86 0 335 8502434 Fax 86 0 335 8502532 service gst fs utc com www gst com cn 30302468...

Отзывы: