4. Electrical Connection
12
PNEG-1499
Digital High/Low Thermostat
Thermostat Connection to Standard Terminal Strip on Heaters Built
in 2007 to Present
1.
Connect power cord to fan control box.
2. Connect the BLACK 120 VAC power wire to the ON/OFF switch. Make this connection so this switch
will also control the thermostat power.
3. Connect the WHITE Neutral wire to terminal 8.
4. Connect the GREEN Stage 1 Common wire to terminal 6.
5. Connect the RED Stage 1 N.O. wire to the high/low light and cycle solenoid.
6. Connect the ORANGE Stage 2 Common wire to terminal 1.
7. Connect the BLUE Stage 2 N.O. wire to high limit circuit on the incoming L1 power.
NOTE:
Terminal strip may or may not be present in heater to connect wires in thermostat circuits.
Figure 4B Heaters Built in 2007 using HH-1089E Time Delay