SERIES 2000 HEATER OPERATING PROCEDURE

PROGRAMMING SET

POINTS

multiple heaters may be done at any
heater control console.  The infor-
mation programmed is automatically
transmitted to all other heaters when
the programming is complete.

Hi Limit Set Point

--The upper

left cursor is flashing indicating the
mode.  If the plenum temperature
increases above this point, the flame
is shut off--"OFF-CYCLE" is dis-
played on screen.

Cycle Set Point

--The upper 2nd

from left cursor is flashing indicat-
ing the mode.  

If the dryer is not a

hi-lo dryer, this function is
skipped.

  If the plenum tempera-

ture increases above this point, the
flame reduces to "LO-FLAME".

Humidity Set Point

--The upper

2nd from right cursor is flashing in-
dicating the mode.  If the humidity is

Depressing the "PROGRAM" switch
(lower left) causes the display to en-
ter the program mode.  Each item
below is programmed by using the
up and down arrow switches.  Hold-
ing down these up and down arrow
switches for about 2 seconds will
cause the numbers to increase/de-
crease rapidly until the switch is re-
leased.  When finished program-
ming an item, depressing the "PRO-
GRAM" switch again will cause the
new setting to be entered into
memory, and the display will ad-
vance to the next function to be pro-
grammed.

Programming may be done at

anytime (unless an error condi-
tion exists) even while the dryer
is in operation.

Programming a system with

The limits are continuously

checked during the drying operation.
A limit switch open or any other er-
ror condition will cause the dryer to
shut down, and the fan will be shut-
down.  

If a limit opens, or an er-

ror condition occurs during dry-
ing, the control will lockup in the
error display mode. Power must
be shut off and back on to the
control to clear the error condi-
tion

--even if the error or limit that

caused the shutdown has been cor-
rected. 

This is to keep the display

locked up with the condition that
caused the error, allowing the opera-
tor time to determine what caused the
shutdown.

above this point the dryer operates
normally--flame on and off at the
high limit and cycle set points.  If the
humidity is below this point the dryer
goes into the "OFF-CYCLE" mode.

Note: At this time a true humidity
sensor has not been introduced.
To use this option, set the humid-
ity setting to 50% and use a hu-
midistat switch.

  When the humid-

ity is high the switch is closed, indi-
cating high humidity.  At this setting,
the dryer runs normally.

Temperature Differential

--The

upper right cursor is flashing indicat-
ing the mode.  If the flame shuts off
because the temperature is greater
than the high limit set point, the tem-
perature must fall below the (Set Point
minus Temperature Differential) for
the flame to come back on.

Programming the high-limit set point.

Содержание Airstream 2000 Series

Страница 1: ...1 Owner s Manual MANUAL PNEG 582 CGAApproved Series2000Heater InstallationAnd OperatingInstructions MODEL VHC __ __ __ __ 2 __ HIGH MODEL VLC __ __ __ __ 2 __ LOW...

Страница 2: ...CURRENT INSTALLATION CODES FOR GAS BURNING APPLIANCES AND EQUIPMENT CAN1 B149 1 AND B149 2 OR APPLICABLE PROVINCIAL REGULATIONS WHICH SHOULD BE CAREFULLY FOLLOWED IN ALL CASES AUTHORITIES HAVING JURI...

Страница 3: ...ane Vapor Models 12 Fuel Connection For Natural Gas Models 12 Series 2000 Operating Procedure 13 Power Up 13 Normal Operating Displays With Heater Not Running 14 Starting The Dryer 15 Setting Gas Pres...

Страница 4: ...e gauge _____ 9 Regulator adjusted _____ 10 Shut off valve operates correctly _____ 11 Vapor high limit _____ 12 Unit cycles ON to OFF _____ 13 Heat rise even across transition _____ 14 Unit cycles HI...

Страница 5: ...DIFICATIONS TO THE PRODUCT NOT SPECIFICALLY COVERED BY THE CONTENTS OF THIS MANUAL WILL NULLIFY ANY PRODUCT WAR RANTY THAT MIGHT HAVE BEEN OTHERWISE AVAILABLE THE FOREGOING WARRANTY SHALL NOT COVER PR...

Страница 6: ...vailable in both propane vapor and natural gas models The principal concern of the GSI Group Inc GSI is your safety and the safety of others associated with grain handling equipment This manual is wri...

Страница 7: ...r is supplied to your unit Safety decals should be read and understood by all people in the grain handling area The bottom right decal should be present on the inside bin door cover of the two ring do...

Страница 8: ...8 1128 7 32 Blue 2 20 3 4 2842 23 64 Aluminum 1 7 1 1 4 28 28 1 8 29 5 8 25 1 4 3000000 140 34 15 64 Aluminum 2 20 3 8 1253 15 64 Aluminum 2 20 3 4 3157 3 8 Aluminum 1 7 1 1 4 HIGH TEMPERATURE HEATER...

Страница 9: ...bs are vertical and the cord exits the housing horizontally 4 Usetwoselfdrillingscrewstomount the housing to the bin sidewall 5 Caulk between the housing and the sidewall to seal Plenum temperature se...

Страница 10: ...2 WIRING HEATER UNIT SERIES 2000 HEATER INSTALLATION 4 Third heater unit may also be added to system If adding third unit run connections to master unit 1 and connect them in parallel with secondary h...

Страница 11: ...lled by an electrician Ground rods and wires are not sup plied by Airstream It is recom mended that the rod not be driven into dry ground The following steps en sure proper ground rod installation 1 D...

Страница 12: ...RKING ON OR AROUND HEATER 1 Natural gas models are de signed to run directly off of a supply tank or from a separate external vaporizer 2 Run proper size line see speci fication on page 6 to pipe trai...

Страница 13: ...is con dition may be bypassed with the FAN BYPASS switch All safety and high limit switches are checked upon power up If a safety or limit is open the control displays it The control cannot operate wi...

Страница 14: ...The heater display with fan on airflow is displayed if air is flowing or not flowing RX TX receive transmit is displayed if multiple heaters are connected All safeties or high limits are continuously...

Страница 15: ...or 4 6 lbs for natural gas units use the charts on the following pages to set pressure 15 Press the PROGRAM TEM PERATURE button to change the high limit set point Press it again to change the CYCLE S...

Страница 16: ...14 10 8 4 180 9 6 3 17 11 4 3 26 22 11 8 18 16 13 11 5 20 18 13 10 5 GAUGE PRESSURE PSI REQUIRED TO MAINTAIN TEMPERATURE APPROXIMATE HIGH TEMP UNITS ONLY 2 102900 148370 Diameter 18 24 28 4 145970 210...

Страница 17: ...2 205200 251710 1 144100 177840 Operating Pressure PSI Diameter 18 24 28 60 1 1 low temp 1 1 low temp low temp 2 1 1 low temp 1 1 1 1 low temp 1 1 1 1 low temp Fan Model 3HP 18 7HP 24 10HP 24 15HP 26...

Страница 18: ...17 for setting the hi lo flame temperature If the temperature is above the high temperature setting the flame will be off the FLAME message will be out and the display will be flashing OFF CYCLE If t...

Страница 19: ...may be done at anytime unless an error condi tion exists even while the dryer is in operation Programming a system with The limits are continuously checked during the drying operation A limit switch o...

Страница 20: ...e shutdown mode Then the fan and heater shut down when the time expires This is indi cated by the lower left cursor flash ing Depressing the start switch again while holding in on the SHUTDOWN HOURS s...

Страница 21: ...aters Multiple heaters connected together through the serial link Master with one slave dip switch 7 on all others off Slave 1 dip switch one on all others off Master with two slaves dip switch 8 on a...

Страница 22: ...ay SLA on the main display and the RX TX symbols will be flashing If a limit switch error or one of the error numbers 1 through 8 occurs that error is displayed on the slave where the error originates...

Страница 23: ...Disconnect and lock out power to fan and heater Open control box lid and inspect all compo nents for moisture vibration or rodent damage Inspect and tighten all loose terminal con nections Replace any...

Страница 24: ...24 SERIES 2000 HEATER WIRING...

Страница 25: ..._____________________________________________________ ___________________________________________________________________________________________________ ______________________________________________...

Страница 26: ...26 1004 E Illinois St Assumption IL62510 phone217 226 4421 fax217 226 4498 June1996...

Отзывы: