Fig. 11

Safety wire

16.Fix the supply cable to the lifting wire by means of a cable 

clamp approx. 0.8 m above the pump. This will prevent the 
cable from falling down and becoming entangled in the 
impeller during operation. Connect the cable clamp to the 
lifting wire above the wire clamp by means of a snap hook. 
See fig. 12. Attach the supply cable to the lifting wire by means 
of cable clamps placed at 1 m intervals.

Fig. 12

Attaching the supply cable to the lifting wire

17.Position the crane in the foot and mount the lifting wire in the 

drum of the winch. 

18.Lift the complete pump (pump rack with motor) using the crane 

and slide it over the column profile.

19.Slowly lower the pump into the tank and down to position on 

the connection flange.

20.Mount the cable sock (pos. 18) to the top fixation bracket 

using the shackle, and pull the motor cable through it to the 
desired position. See fig. 13. The supply cable should be 
slightly tightened.

Fig. 13

Top fixation bracket with lifting and safety wires and 
cable sock

21.Dismantle the lifting wire from the winch and fit it to the wire 

clamping (pos. 20) on the top fixation bracket. 

Use the lifting wire as a relief for the supply cable. For this 
reason, the lifting wire must always be tightened.

22.Connect the supply cable to the terminals in the control 

cabinet.

7. Electrical connection

The electrical connections must be carried out by a qualified 
electrician in accordance with local regulations.
All national and local regulations relating to safety and accident 
prevention must be observed.

The supply voltage and frequency are marked on the pump 
nameplate. Make sure that the pump is suitable for the power 
supply available at the installation site. 
The pump is supplied complete with a supply cable of 10 metres 
(standard length, suitable for up to 7 m deep tanks).
The motor is marked either with a Y (star) or 

Δ

 (delta). Make this 

connection in an external control panel using conductors 1 to 6 of 
the supply cable. 
Fig.14 shows a schematic drawing of these star and delta 
connections. See also section 

7.5 Wiring diagrams

If the pump is connected in delta during operation, the pump can 
be started in star-delta starting.

Fig. 14

Schematic drawing of delta and star connection

T

M

04 39

32 04

09

T

M

0

2

 493

8 180

2

Caution

Always leave at least three turns of wire on the 
drum. Otherwise the wire may break loose from 
the drum fixation.

Note

Consider and follow the separate installation and 
operating instructions for cranes.

T

M

04 3

929 0

409

15

Supply

cable

Wire clamp

Lifting wire  (15)

Snap hook

Cable

clamp  (17)

20

18

31

B

Caution

Dismantle the lifting wire from the crane before 
starting the pump.

Warning

Make sure the power supply to the control 
cabinet has been switched off.

Warning

Before making any electrical connections, make 
sure that the fuses have been removed or the 
mains switch has been switched to off. Make sure 
that the power supply cannot be accidentally 
switched on. 

Warning

The explosion protection classification applies 
only to versions for 400 V, 50 Hz.

The explosion protection classification is Ex e ck 
ib IIC T3.

The classification of the installation must be 
approved by the local authorities in each 
individual case.

The safety instructions in section 4.2 Explosion-
proof versions
 must be observed.

T

M

02

 4953 

2002

W2

U1

U2

V1

V2

W1

L1

L2

L3

W2

U1

U2

V1

V2

W1

L1

L2

L3

Star

Delta

Содержание SRP 70.30.814.25.Ex.5.1D.A

Страница 1: ...GRUNDFOS INSTRUCTIONS SRP 50 Hz Installation and operating instructions...

Страница 2: ......

Страница 3: ...121 Italiano IT Istruzioni di installazione e funzionamento 136 Lietuvi kai LT rengimo ir naudojimo instrukcija 150 Magyar HU Szerel si s zemeltet si utas t s 164 Nederlands NL Installatie en bedienin...

Страница 4: ...estimmt und mit einem separaten ATEX Typenschild und einem EG Pr fzeugnis ausgestattet sind Weitere Informationen siehe unten EE Vastavusdeklaratsioon Meie Grundfos deklareerime enda ainuvastutusel et...

Страница 5: ...l valamint rendelkeznek EK t pus vizsg lati bizonylattal is Tov bbi inform ci kat l sd alul NL Overeenkomstigheidsverklaring Wij Grundfos verklaren geheel onder eigen verantwoordelijkheid dat het prod...

Страница 6: ...2006 42 EC Kori en standard EN ISO 12100 2003 Direktiva niskog napona 2006 95 EC Kori eni standardi EN 60034 EN 60204 2006 EMC direktiva 2004 108 EC Kori eni standardi EN 61000 6 2 2005 EN 61000 6 3...

Страница 7: ...15 8 Start up 15 9 Service 16 9 1 Contaminated pump 16 9 2 Service chart 17 9 3 Oil 18 9 4 Oil change 18 10 Fault finding 19 11 Technical data 20 11 1 Motor 20 11 2 Gearbox 20 11 3 Shaft seals 20 11 4...

Страница 8: ...ch individual case Example SRP 70 30 814 25 Ex 5 1D A Type range SRP Submersible recirculation pump Motor output power P2 P2 Code from type designation 10 kW 70 7 kW Impeller diameter cm 30 30 cm Impe...

Страница 9: ...code 3 Impeller diameter 4 Liquid temperature range 5 Product number 6 Enclosure class according to IEC 7 Serial number 8 Insulation class 9 Rated voltage 10 Rated speed impeller 11 Weight 12 Nominal...

Страница 10: ...lifted when using the suspension point The lifting equipment supplied with the pump as well as the wire used for lifting and lowering the pump into the tank must not be used as universal lifting equip...

Страница 11: ...insulator pos C at the top fixation bracket A gap of 5 to 10 mm between collar of epoxy and column profile is optimal See fig 9 8 Remove the epoxy insulator and the turnable metal part by removing the...

Страница 12: ...nd frequency are marked on the pump nameplate Make sure that the pump is suitable for the power supply available at the installation site The pump is supplied complete with a supply cable of 10 metres...

Страница 13: ...cted to a Grundfos relay type ALR 20 A Ex The ALR 20 A Ex relay must be ordered separately Product number 96489569 For longer distance use an additional screened cable An external alarm indicator if a...

Страница 14: ...the motor the impeller should rotate clockwise An arrow on the motor housing shows the correct direction of rotation If the impeller rotates in the wrong direction interchange two phases of the mains...

Страница 15: ...een 50 and 75 of the gearbox If required fill oil into the gearbox through the oil filling hole pos 2 For oil quality and quantity see section 9 3 Oil If the pump has been in stock for a period before...

Страница 16: ...However any application for service no matter to whom it may be made must include details about the pumped liquid if the pump has been used for liquids which are injurious to health or toxic Warning B...

Страница 17: ...edy sleeve and wear ring and replace them in case of wear If the oil contains water replace the mechanical shaft seal Check the oil level twice a year If refilling is required See section 9 3 2 Oil qu...

Страница 18: ...ling hole pos 2 Quantity according to section 9 3 2 Oil quantity 8 Refit the screw pos 2 Fig 21 Position of oil drain and oil filling screws Type Gearbox l SRP 08 30 526 1 2 SRP 10 30 606 SRP 13 30 67...

Страница 19: ...Grundfos b Different phase voltages Call an electrician c Overload relay is set too low or is faulty Check the overload relay Set the relay to the rated current See section 7 3 Overload relays d Leak...

Страница 20: ...id surface Maximum number of starts per hour 20 Enclosure class IP68 Insulation class F Material motor housing Cast iron EN JL 1040 epoxy coated Ambient temperature 0 to 40 C Type Planetary gearbox Ge...

Страница 21: ...50 50 291 5 0 200 SRP 65 50 343 6 5 1119 855 996 824 66 670 230 25 240 SRP 80 50 378 8 0 240 SRP 100 50 412 10 250 SRP 70 80 263 7 0 1129 1237 1006 1225 66 1015 267 25 350 SRP 100 80 303 10 360 SRP 12...

Страница 22: ...Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA...

Страница 23: ...kes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark All r...

Отзывы: