Set analog scaling
Analog scaling refers to the assignment of the
current input value to the dosing flow.
Changes of analog scaling affect also the analog
output signal. See section
.
Analog scaling passes through the two reference
points (I
1
/Q
1
) and (I
2
/Q
2
), which are set in the "
Setup
>
Analog scaling
" menu. The dosing flow is
controlled according to this setting.
Example 1 (DDA 60-10)
Analog scaling with positive gradient:
Fig. 22
Analog scaling with pos. gradient
In example 1, the reference points I
1
= 6 mA, Q
1
= 20
l/h and I
2
= 16 mA, Q
2
= 60 l/h have been set.
From 0 to 6 mA analog scaling is described by a line
that passes through Q = 0 l/h, between 6 mA and 16
mA it rises proportionally from 20 l/h to 60 l/h and
from 16 mA onwards it passes through Q = 60 l/h.
Example 2 (DDA 60-10)
Analog scaling with negative gradient (Operation
mode 0-20 mA):
Fig. 23
Analog scaling with neg. gradient
In example 2, the reference points I
1
= 2 mA, Q
1
= 60
l/h and I
2
= 16 mA, Q
2
= 18 l/h have been set.
From 0 to 2 mA analog scaling is described by a line
that passes through Q = 0 l/h, between 2 mA and 16
mA it drops proportionally from 60 l/h to 18 l/h and
from 16 mA onwards it passes through Q
2
= 18 l/h.
Set analog scaling in the "
Operation
" menu
Analog scaling can also be modified after a security
prompt directly in the "
Operation
" menu. This is how
the dosing flow is directly modified for the current
flow input value. Please observe that changes also
have a direct effect on point I
2
/Q
2
(see fig.
Fig. 24
Set analog scaling ("
Operation
" menu)
7.4.4
Batch (pulse-based)
In this operation mode, the pump doses the
set batch volume in the set dosing time (t
1
). A
batch is dosed with each incoming pulse.
Fig. 25
Batch (pulse-based)
The setting range depends on the pump type:
*
Thanks to the digital motor control, dosing
quantities with a resolution of up to 1/8 of the
dosing stroke volume can be dosed.
TM
06
70
81
32
16
T
M
06
70
82
32
1
6
Q [l/h]
16
20
6
60
40
0
0
2
0
I [mA]
(I
2
/Q
2
)
(I
1
/Q
1
)
0
0
20
16
18
2
60
I [mA]
Q [l/h]
(I
2
/Q
2
)
(I
1
/Q
1
)
T
M
06
70
83
29
1
6
T
M
06
70
85
39
18
Type
Setting range per batch
from [ml]
to [l]
Resolution*
[ml]
DDA 60-10
5.56
999
0.694
DDA 120-7
11.6
999
1.45
DDA 200-4
19.3
999
2.41
4
0
20
100
0
Q [%]
I [mA]
new
actual mA
(I
2
/Q
2
)
(I
1
/Q
1
)
(I
2
/Q
2
)
Pulse
Batch volume
Pulse
Time
t
1
t
1