7.4.4 "Current input, Contact input, Manual control, Target
value ext." modes
Checking the bypass water
• In the main menu, scroll to page 2 using the [ARROW RIGHT]
key.
• Switch to the "Service mode" menu using the [F3] key.
• In the "Service mode" menu, switch to the "Startup mode"
menu using the [F2] key.
Display with startup mode
• Use the [F2] key to switch to the "Bypass water" menu.
• Use the [F2] key to switch on the bypass water (solenoid valve
or bypass pump).
The target value is defined by the system choice. The actual
value shows the current water quantity flowing through the
bypass.
Starting of startup mode
• Use the [F3] key to switch to the "Startup/start" menu.
• Press the [Enter] key to start the startup mode.
The remaining time for the startup mode is shown on the display.
If it has expired, the system switches off automatically.
• Use the [Enter] and [Escape] key to return to the "Startup mode"
menu.
• Use the [Escape] key to return to the "Service mode" menu or to
the "Main menu".
7.5 Calibrating the dosing pumps
Fig. 22
Calibrating the dosing pump
• Shut the isolating valve (4) at the calibration tube (5).
The supply from the tank is now interrupted. The calibration
tube is slowly emptied.
• Using a stopwatch, time how long it takes for the dosing
volume of 0 to 10 ml (10-ml measuring glass) and of 0 to 5 ml
(5-ml measuring glass).
• Open the isolating valve (4) at the calibration tube (5).
• Calculate the dosing flow:
10-ml measuring glass: V (l/h) = 36/t (s)
5-ml measuring glass: V (l/h) = 18/t (s)
If the calibrated dosing volume deviates from the target value
(table), the dosing rate is corrected with the stroke adjustment
button (on the dosing pump) and checked once again.
If a pump deviation occurs, use the stroke adjustment button to
re-adjust it and re-calibrate it.
Consumption of components, see table in section
2.1.1 Performance and consumption data
.
If several calibration attempts are made, ensure that the suction
lines do not become filled with air. If necessary, deaerate the
pump again.
Dosing pumps for the systems OCD-164-220 to
OCD-164-2000
1. Calibration is made using calibration cylinders.
2. Fill both calibration cylinders with water up to a certain mark.
3. Place the suction lines into the calibration cylinders.
4. Use a stopwatch to determine the time required to dose a
particular quantity of liquid.
5. Remove the suction lines from the calibration cylinders, read
off the new value, and calculate the dosing performance.
6. If the calibrated dosing volume deviates from the setpoint
(table), the dosing rate is corrected with the stroke adjustment
button (on the dosing pump) and checked once again.
Consumption of components, see table in section
2.1.1 Performance and consumption data
7. If a pump deviation occurs, use the stroke adjustment button
to re-adjust it and re-calibrate it.
If several calibration attempts are made, ensure that the suction
lines do not become filled with air. If necessary, deaerate the
pump again.
Consumption of components, see table in section
2.1.1 Performance and consumption data
.
Startup mode
2 Bypass water
3 Start
2 Bypass water
<off>
target
XXX l/h
actual:
YYY l/h
1 limit:
-XX/+600 %
Startup mode
activated
Runtime
xxx s
Startup mode
finished
Caution
Details of the dosing rate required for the size of
installation in question can be found in the table in
2.1.1 Performance and consumption data
under
"Consumption of components".
As diluted chemicals are used in these installations,
the consumption data may be compared 1 : 1 with
water.
Calibration can be done with water.
Note
The dosing pumps with double head system can also
be calibrated at any time in regular mode without
interrupting the process sequence.
TM
04
82
11
4
510
Warning
Don't let the calibration tube run empty.
Re-open the isolating valve in good time.
Содержание Oxiperm OCD-164
Страница 2: ...2...
Страница 247: ...Fran ais FR 247 4 crou filtre PVC gris...
Страница 420: ...RU 420 1 10 1 10 1 20 TrinkwV 2001 0 4 1 10 2 1 10 3 EN 12671 D 15 7 5 DIN EN 938 9 0 DIN EN 939 HCl NaClO2...
Страница 422: ...RU 422 10 10...
Страница 430: ...RU 430 5 4 2 0 1 1 8 5 4 3 42 9 5 4 4 ClO2 ClO2 ClO2 2 3 3 TM04 8200 4510 11 1D O2 O TM04 8201 4510 1D O2 O...
Страница 431: ...RU 431 10 5 5 2 1 5 5 6 5 6 1 5 6 1 TM04 8202 4510 50 60 6 20 11 1D O2 O...
Страница 432: ...RU 432 5 6 2 1 2 3 20 20 4 11 4 5 4 4 5 4 6 5 6 5 6 TM04 8203 4510 1 20 2 3 4 5 6...
Страница 455: ...RU 455 34 HCl 35 HCl 36 NaClO2 37 NaClO2 38 H2O 39 H2O 40 ClO2 41 HCl 42 NaClO2 43 H2O 44 45 46 47...
Страница 526: ...526...