8.5 Selection of control mode

8.5.1 Setpoint setting

The setpoint can be set by pressing 

 or 

 when 

the pump is in control mode:

proportional pressure,

constant pressure or 

constant-curve duty.

Set the setpoint so that it matches the system. 

A too high setting may result in noise in the system 
whereas a too low setting may result in insufficient 
heating or cooling in the system.

If AUTO

ADAPT 

is selected, the setpoint cannot be set.

8.6 Automatic nighttime duty

To be set on the control panel or with the R100, see 
section 9. Pump setup.

Once automatic nighttime duty has been activated, 
the pump automatically changes between normal 
duty and night-time duty (duty at low performance). 

Changeover between normal duty and nighttime duty 
is dependent on the flow-pipe temperature.

The pump automatically changes over to
nighttime duty when the built-in sensor registers a 
flow-pipe temperature drop of more than
18 °F - 27 °F (10 °C - 15 °C) within approx. 2 hours. 
The temperature drop must be at least 0.18 °F/min 
(0.1 °C/min).

Changeover to normal duty takes place without a 
time lag when the temperature has increased by 
approx. 18 °F (10 °C). 

System type

Description 

Select this 
control mode 

Typical heating 
systems

Grundfos recommends to let the pump remain in AUTO

ADAPT 

mode. 

This ensures optimum performance at the lowest possible energy 
consumption. 

AUTO

ADAPT 

Relatively great 
head losses in 
the distribution 
pipes and 
air-condition-
ing systems

1. Two-pipe 

heating
systems with 
thermostatic 
valves and:

• with a pump head higher than

10 ft (3 m),

Proportional 

pressure

• very long distribution pipes,

• strongly throttled pipe balancing valves,

• differential pressure regulators,

• great head losses in those parts of the system 

through which the total quantity of water flows 
(e.g. boiler, heat exchanger and distribution pipe 
up to the first branching).

2. Primary circuit pumps in systems with great head losses in the pri-

mary circuit.

3. Air-condition-

ing systems 
with

• heat exchangers (fan coils),

• cooling ceilings,

• cooling surfaces.

Relatively small 
head losses in 
the distribution 
pipes

1. Two-pipe 

heating sys-
tems with 
thermostatic 
valves and:

• with a pump head lower than

6.5 ft (2 m),

Constant

pressure

• with small head losses in those parts of the sys-

tem through which the total quantity of water flows 
(e.g. boiler, heat exchanger and distribution pipe 
up to the first branching) or

• modified to a high differential temperature 

between flow pipe and return pipe (e.g. district 
heating).

2. Underfloor heating systems with thermostatic valves.

3. One-pipe heating systems with thermostatic valves or pipe balanc-

ing valves.

4. Primary circuit pumps in systems with small head losses in the pri-

mary circuit.

1RWH

Automatic nighttime duty cannot be 
used in air-conditioning systems.

Содержание MAGNA 32-100

Страница 1: ...GRUNDFOS INSTRUCTIONS MAGNA Series 2000 MAGNA 32 60 32 100 Installation and operating instructions 3191277 4002198 Conforms to ANSI UL Std 778 Certified to CAN CSA Std E60335 2 51...

Страница 2: ...NTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHER CAUSES THERE ARE NO EXPRESS OR IMPLIED WARRANTIES INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WHICH EXTEND...

Страница 3: ...rable to optimize the setting of the pump duty point systems with variable flow pipe temperature 4 1 Pumped liquids Grundfos MAGNA is intended for pumping clean water not containing solid particles or...

Страница 4: ...allation Arrows on the pump housing indicate the liquid flow direction through the pump 5 1 Positioning GRUNDFOS MAGNA must be installed with the pump head in horizontal position see fig 2 Fig 2 Insta...

Страница 5: ...e This is especially important in proportional pressure control mode reduced head at low flow Fig 4 Non return valve 5 5 Frost protection If the pump is not used during periods of frost necessary step...

Страница 6: ...ly in accordance with the water demand in the system The desired setpoint can be set on the pump control panel Constant pressure control A constant head is maintained regardless of water demand The de...

Страница 7: ...modes can be combined with automatic night time duty see section 8 6 Automatic nighttime duty AUTOADAPT To be set on the control panel or with the R100 see section 9 Pump setup The control mode AUTOAD...

Страница 8: ...nsures optimum performance at the lowest possible energy consumption AUTOADAPT Relatively great head losses in the distribution pipes and air condition ing systems 1 Two pipe heating systems with ther...

Страница 9: ...on at liquid temperatures below 176 F 80 C or below 122 F 50 C These temperature limits are called Tmax The setpoint is reduced in relation to the head set 100 according to the characteristics below F...

Страница 10: ...10 LON interface Product number 605726 Fig 10 Connection to LON network 9 Pump setup For the setting of the pump use control panel R100 remote control bus communication not described in detail in thes...

Страница 11: ...Warning At high liquid temperatures the pump may be so hot that only the buttons should be touched to avoid burns Pos Description 1 Buttons for setting 2 Indicator lights for operating and fault indic...

Страница 12: ...ated Fig 15 Min curve 9 2 5 Start stop of pump To stop the pump press continuously until STOP illuminates When the pump is stopped the green indicator light will be flashing To start the pump press co...

Страница 13: ...3 INSTALLATION The number stated at each individual display in fig 16 refers to the section in which the display is described Fig 16 Menu overview 9 5 3 9 6 2 9 6 3 9 6 4 9 6 5 9 7 5 9 7 4 9 7 3 9 6...

Страница 14: ...de Stop Min min curve Normal AUTOADAPT proportional pressure constant pressure or constant curve Max max curve 9 5 3 Fault indications If the pump is in alarm status the cause will appear in this disp...

Страница 15: ...ours of the pump The value of operating hours is an accumulated value and cannot be set to zero 9 7 Menu INSTALLATION This menu shows the settings that should be considered when installing the pump 9...

Страница 16: ...stinguish between two or more pumps 9 8 Priority of settings The external forced control signals will influence the settings available on the pump control panel and with the R100 However the pump can...

Страница 17: ...ed in one of the following ways 1 With the button 2 With the R100 3 External on off switch in posi tion off 4 Via bus signal 1 Start the pump by pressing 2 Start the pump with the R100 or by pressing...

Страница 18: ...the expan sion tank if installed Air in the pump Set the pump to MAX by contin uously pressing the button or with the R100 After venting set the pump back to normal duty by pressing the buttons or wi...

Страница 19: ...0705 Switch off the electricity supply Open the connection box 2 TM03 0909 0705 Remove the supply wires L and N and the earth ground wire GND 3 TM03 0910 0705 Short circuit the wires L and N using a w...

Страница 20: ...llection service 2 If this is not possible contact the nearest Grundfos company or service workshop Signal output Internal potential free change over contact Maximum load 250 V 2 A AC1 Minimum load 5...

Страница 21: ...21 QJOLVK 86 Master pump TM03 0857 0605 Master definition...

Страница 22: ...22 QJOLVK 86 Slave pump TM03 0856 0605...

Страница 23: ...7 3400 Telefax 1 913 227 3500 Canada GRUNDFOS Canada Inc 2941 Brighton Road Oakville Ontario L6H 6C9 Phone 1 905 829 9533 Telefax 1 905 829 9512 M xico Bombas GRUNDFOS de M xico S A de C V Boulevard T...

Страница 24: ...tion is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark All rights reserved worldwi...

Отзывы: