21

7. Start-up

Prior to start-up, the connection and DIP switch setting must have 
been carried out according to sections 

3.

 to 

6.

Start-up must be carried out by authorized personnel.
Proceed as follows:
1. Check whether the float switches have been connected 

according to the wiring diagram for the actual application.

2. Check that the pump inlets are submerged in the liquid to be 

pumped.

3. Set the motor protection relays to the rated current stated on 

the nameplates.

4. Warning:

5. Switch on the electricity supply.

Three-phase pumps only:

 Check for wrong phase sequence, 

(the pump cannot be started if the phase sequence is wrong!).

6. Start the pumps, see section 

3.5

4.5

5.5

 or 

6.5

.

7. Check that the pumps are not running dry. The risk of dry 

running can be eliminated by a renewed time setting by means 
of the DIP switch according to section 

3.2

4.2

5.2

 or 

6.2

 

and/

or

 by moving the float switches.

8.

Three-phase pumps only:

 Check whether the direction of 

rotation of the pumps is correct according to the installation 
and operating instructions for the pump in question.

9. Select the required operating mode by means of the ON-OFF-

AUTO selector switch, see section 

3.5

4.5

5.5

 or 

6.5

.

8. Maintenance

During normal application and operation, the controller LCD 108 
is maintenance-free.

However, it is advisable to carry out minor checks of the LCD 108 
controller, pump pits, tanks, pumps, etc. at suitable intervals. 
These checks should be carried out by authorized personnel. 
• Check the gaskets of the LCD 108 cabinet front and those of 

the Pg cable entries.

• Check the cable entries for the explosion hazard area.
• Check for possible deposits/sludge build-up in the pump pit/

tank. Sludge may settle in areas with almost stagnant liquid.

• Check for beginning sludge build-up around the float switches. 
• Check for possible blockage on the suction side of the pump. 

A blockage will typically be a large solid object.

• If the LCD 108 has been installed in a particularly aggressive 

environment, it is advisable to check the motor protection con-
tacts in order to identify possible chemical attack resulting in 
corrosion. In typical installations, the motor protection contacts 
will work for several years and do not require any inspection.

Note:

 The list above is 

not

 complete. The LCD 108 may be 

installed in systems, installations and/or environments which 
require thorough and regular maintenance.

9. Technical data

Voltage variants, nominal voltages

• 1 x 230 V.
• 3 x 415 V.

Voltage tolerances for LCD 108

–15 %/+10 % of nominal voltage.
See also installation and operating instructions for the pump in 
question.

Mains frequency for LCD 108

50/60 Hz. See also installation and operating instructions for the 
pump in question.

Supply system earthing

For TN systems and TT systems.

Rated insulation voltage, U

i

4 kV.

Rated impulse withstand voltage, U

imp

4 kV.

Short-circuit protection of supply

Depending on variant, see nameplate.

Control circuit fuse

Fine-wire fuse: 250 mA / F / 32 mm x 

6 mm.

Ambient temperature

• During operation: –30 to +50 °C

(must not be exposed to direct sunlight).

• In stock: –30 to +60 °C.

Enclosure class

IP 65. 

EMC (electromagnetic compatibility)

According to EN 61 000-6-2 and EN 61 000-6-3.

Cabinet LCD 108 for direct-on-line starting

• External dimensions (including glands): 

Height = 590 mm, width = 380 mm, depth = 220 mm.

• Material: ABS (Acrylonitrile butadiene styrene).
• Weight: Approx. 5 kg, depending on variant, see nameplate.

Outputs for alarm devices

Max. 230 VAC / max. 2 A / min. 10 mA / AC1.

Before starting any work on pumps used to pump 
liquids which could be constituted as being 
hazardous to health, thorough cleaning/venting of 
pumps, pits, etc. must be carried out according to 
local regulations.
Before making any connections in the LCD 108 or 
work on pumps, pits, etc., it must be ensured that the 
electricity supply has been switched off and that it 
cannot be accidentally switched on. 

Ensure that the short-circuit protection is suitable for 
the installation.

Before starting any work on pumps used to pump 
liquids which could be constituted as being 
hazardous to health, thorough cleaning/venting of 
pumps, pits, etc. must be carried out according to 
local regulations.
Before making any connections in the LCD 108 or 
work on pumps, pits, etc., it must be ensured that the 
electricity supply has been switched off and that it 
cannot be accidentally switched on. 

Содержание LCD 108

Страница 1: ...LCD 108 GRUNDFOS INSTRUCTIONS Installation and operating instructions...

Страница 2: ...these Council directives on the approximation of the laws of the EC member states Machinery Directive 98 37 EC Standard used EN 809 2000 Low Voltage Directive 2006 95 EC Standards used EN 60335 1 2002...

Страница 3: ...conditions indication of liquid level alarm indication of inadmissibly high liquid level overload via motor protection relay overtemperature via PTC resistance or thermal switch in motor wrong phase s...

Страница 4: ...n which it will be used All cables wires must be fitted through the Pg cable entries and gaskets IP 65 Maximum back up fuse is stated on the controller nameplate If required according to local regulat...

Страница 5: ...hanged the controller must be switched off for at least 1 minute Switch 10 automatic restarting When the DIP switch setting is changed the controller must be switched off for at least 1 minute Pos Des...

Страница 6: ...osition AC It is possible to connect 3 electrodes 1 as reference electrode and 2 float switches The controller transmits a 13 to 18 VAC signal Operation with float switches Selector switch in position...

Страница 7: ...97 3902 Pos Description 1 Green indicator light for pump 1 and 2 indicating starting delay flashing and pump operation permanently on 2 Red indicator light for pump 1 and 2 Flashing Fault in PTC resis...

Страница 8: ...registers overtemperature the pump will not be switched off Note It is the user s responsibility to decide how long the pump is to run with this fault indication Over a long period the pump will be d...

Страница 9: ...restarting When the DIP switch setting is changed the controller must be switched off for at least 1 minute Pos Description Terminal number 1 Float switch for common stop 11 12 2 Float switch for sta...

Страница 10: ...0 V AC DC G 3 4 AC 1 2 13 18 VAC 0 V AC DC G 3 4 AC 1 2 12 VDC 0 V AC DC G 3 4 TM01 6397 3902 Pos Description 1 Green indicator light for pump 1 and 2 indicating starting delay flashing and pump opera...

Страница 11: ...the second orange indicator light from the top will be permanently on If the starting delay function and automatic test run were selected switch 4 of the DIP switch the start up will be delayed after...

Страница 12: ...4 2 Consequently the pump cannot be started when the PTC resistance thermal switch of the motor registers overtemperature OFF middle position The pump cannot start when the selector switch has been s...

Страница 13: ...nd 28 The module CU 212 has a 10 pole DIP switch in the bottom right corner see fig 8 Note During setting the controller must be off circuit for at least 1 minute to ensure the correct configuration d...

Страница 14: ...on with the actual application 100 standby operation pages 27 and 28 but this setting must be maintained This setting ensures automatic resetting of alarm signals to external alarm devices and the bui...

Страница 15: ...TM01 6397 3902 Pos Description 1 Green indicator light for pump 1 and 2 indicating starting delay flashing and pump operation permanently on 2 Red indicator light for pump 1 and 2 Flashing Fault in PT...

Страница 16: ...quently the pump cannot be started when the PTC resistance thermal switch of the motor registers overtemperature OFF middle position The pump cannot start when the selector switch has been set to this...

Страница 17: ...operation pages 29 and 30 The module CU 212 has a 10 pole DIP switch in the bottom right corner see fig 11 Note The controller must be off circuit to ensure the correct configuration during start up...

Страница 18: ...ignal is given until the pump is stopped It must be ensured that the pump is not running dry 0 sec 60 sec 15 sec 90 sec 30 sec 120 sec 45 sec 180 sec Switch 8 has no function in connection with the ac...

Страница 19: ...tor light is flashing TM01 6397 3902 Pos Description 1 Green indicator light for pump 1 and 2 indicating starting delay flashing and pump operation permanently on 2 Red indicator light for pump 1 and...

Страница 20: ...equently the pump cannot be started when the PTC resistance thermal switch of the motor registers overtemperature OFF middle position The pump cannot start when the selector switch has been set to thi...

Страница 21: ...e chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The list above is not complete The LC...

Страница 22: ...h into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control circuit fuses see pos 6 in fig 1 or fig 3 d The motor protection relays have cut out the...

Страница 23: ...C G NO G COM G NC 11 12 21 22 31 32 41 42 M M P1 P2 LC 108 ON DIP 2 3 1 1 2 3 4 5 6 7 8 9 10 Ext max 230V max 2A TM04 0278 2308 1N2 1U2 2N2 2U2 T22 T12 T21 T11 N1 U1 L 1 1 P1 P2 TM04 0277 2308 1W2 1V2...

Страница 24: ...TM01 8146 2308 W1 V1 U1 1U2 N1 2U2 1V2 2V2 T11 T21 T12 T22 3U2 3V2 3W2 4U2 4V2 4W2 1W2 2W2 P1 P2 ON DIP 1 2 3 4 5 6 7 8 9 10 LCD 108 Ext 3 2 1 L1 L2 L3 N PE PE max 230V max 2A H NC H COM H NO G NC G...

Страница 25: ...max 230V max 2A T11 T21 T12 T22 H NO H COM H NC G NO G COM G NC 11 12 21 22 31 32 41 42 TM04 0278 2308 1N2 1U2 2N2 2U2 T22 T12 T21 T11 N1 U1 L 1 1 P1 P2 TM04 0277 2308 1W2 1V2 1U2 2V2 2U2 2W2 L3 L2 L...

Страница 26: ...26 Fig B2 TM01 8147 2308 P1 P2 W1 V1 U1 1U2 N1 2U2 1V2 2V2 T11 T21 T12 T22 3U2 3V2 3W2 4U2 4V2 4W2 1W2 2W2 4 3 2 1 max 230V max 2A H NC H COM H NO G NC G COM G NO L1 L2 L3 N PE PE LCD 108...

Страница 27: ...T22 T12 T21 T11 H COM H NC G NO G COM G NC 11 12 21 22 31 32 41 42 max 230V max 2A ON DIP 1 2 3 4 5 6 7 8 9 10 TM04 0278 2308 1N2 1U2 2N2 2U2 T22 T12 T21 T11 N1 U1 L 1 1 P1 P2 TM04 0277 2308 1W2 1V2...

Страница 28: ...2308 W1 V1 U1 1U2 N1 2U2 1V2 2V2 T11 T21 T12 T22 3U2 3V2 3W2 4U2 4V2 4W2 1W2 2W2 P1 P2 L1 L2 L3 N PE LCD 108 Ext 4 3 2 1 ON DIP 1 2 3 4 5 6 7 8 9 10 max 230V max 2A H NO H COM H NC G NO G COM G NC 11...

Страница 29: ...T11 H COM H NC G NO G COM G NC 11 12 21 22 31 32 41 42 LCD 108 Ext ON DIP 1 2 3 4 5 6 7 8 9 10 max 230V max 2A TM04 0278 2308 1N2 1U2 2N2 2U2 T22 T12 T21 T11 N1 U1 L 1 1 P1 P2 TM04 0277 2308 1W2 1V2...

Страница 30: ...D2 TM01 8464 2308 W1 V1 U1 1U2 N1 2U2 1V2 2V2 T11 T21 T12 T22 3U2 3V2 3W2 4U2 4V2 4W2 1W2 2W2 P1 P1 ON DIP 1 2 3 4 5 6 7 8 9 10 L1 L2 L3 N PE LCD 108 4 3 2 1 max 230V max 2A H NC H COM H NO G NC G CO...

Страница 31: ...gotanda Shiagawa ku Tokyo 141 0022 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2...

Страница 32: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 97502178 0609 GB...

Отзывы: