background image

8

3.4 Battery back-up functions

Systems with 2 levels (3 electrodes), page 97.

If a back-up battery for CU 213 (accessory for certain variants) is 
installed, the following functions will be carried out if the normal 
electricity supply to the LC 110 fails (see also the illustrations 
below):

The common alarm is active, the 

red

 indicator light is on – 

cannot

 be reset!

If

 the 

external 

alarm device for common alarm is supplied from 

an external power source, this device will be active – 

cannot 

be reset by means of the reset button!

The built-in buzzer (only certain variants) is activated – can be 
reset by means of the reset button!

If

 the liquid level in the pit rises above the level for high-level 

alarm, the top 

orange

 indicator light will be 

flashing 

and the 

second 

orange

 indicator light from the top will be permanently 

on.

If

 the starting delay function and automatic test run were 

selected (switch 4 of the DIP switch), the start-up will be 
delayed after the electricity supply has been switched on when 
the liquid level is sufficiently high, see section 

3.2

.

The table below shows the situations which may occur if the nor-
mal electricity supply to the LC 110 fails and a back-up battery is 
connected:

 = the indicator light is off.

 = the indicator light is on.

 = the indicator light is flashing.

3.5 Reset button and ON-OFF-AUTO selector switch

Systems with 2 levels (3 electrodes), page 97.

Mains supply failure:

• The common alarm is active. 

The 

red 

indicator light is on. 

• The green indicator light (electricity 

supply switched on) is 

off

.

Mains supply failure 

and 

high-level alarm:

• The common alarm is active. 

The 

red 

indicator light is on.

• The top 

orange

 indicator light is 

flashing

.

• The second 

orange

 indicator light from 

the top is on.

• The green indicator light (electricity 

supply switched on) is 

off

.

1

1

The 

reset button 

is a push-button for manual resetting of alarm signals to 

external 

alarm devices and the built-in 

buzzer (i.e. 

not 

for resetting of the alarm memory as this is reset by means of the ON-OFF-AUTO selector switch, 

see position OFF

 

( )).

Even if the fault condition still exists, the 

external 

alarm devices and the built-in buzzer will be reset when the reset 

button is pressed.

The 

ON-OFF-AUTO selector switch

 has three different positions:

ON ( )

, top position:

• The pump will start when the selector switch is pushed into this position (unless the motor protection relay has cut 

out the pump).

• If the motor thermal switch registers overtemperature, the pump will be switched off.

In explosion hazard areas, switch 10 of the DIP switch 

must

 be set as stated in section 

3.2

. Consequently, the 

pump 

cannot 

be started when the motor thermal switch registers overtemperature.

OFF (

)

, middle position:

• The pump 

cannot 

start when the selector switch has been set to this position.

• The alarm memory is reset by pushing the selector switch into position OFF

 

( ). The alarm memory is the light in-

dication of a fault condition which has disappeared. If a fault condition still exists when the selector switch is 
pushed into position ON ( ) or AUTO ( ), the alarm indication will be repeated immediately.

AUTO (

)

, bottom position:

• The pump is controlled by the input signals from the electrodes and the pump according to the selected DIP switch 

setting.

• Alarm signals will automatically be reset. Switch 9 of the DIP switch can, however, be set to manual resetting 

which is carried out by means of the reset button, see section 

3.2

.

• The pump will restart automatically when a given fault condition disappears. However, this is dependent on the 

setting of switch 10 of the DIP switch, see section 

3.2

.

• When the pump starts automatically after a fault condition which has disappeared, the indicator light will continue 

to show the fault condition (alarm memory) and the indication can only be removed by resetting the alarm memory, 
see position OFF

 

( ).

1

Содержание LC 110

Страница 1: ...LC 110 LCD 110 GRUNDFOS INSTRUCTIONS Installation and operating instructions LC 110 LCD 110...

Страница 2: ...bereinstimmen Maschinenrichtlinie 2006 42 EG Norm die verwendet wurde EN 60204 1 2006 Niederspannungsrichtlinie 2006 95 EG Norm die verwendet wurde EN 60439 1 2004 EMV Richtlinie 2004 108 EG Normen di...

Страница 3: ...3 LC 110 LCD 110 Installation and operating instructions 4 Montage und Betriebsanleitung 33 Monterings og driftsinstruktion 68...

Страница 4: ...a LCD 110 31 20 Fault finding chart 32 21 Disposal 32 1 General LC 110 The LC 110 controller is designed for the control of pumps in wastewater water supply and drainage systems Type key 1 1 Applicati...

Страница 5: ...lems with the signal values sent back to the controller may arise In such cases it is recommended to use float switches Note Cables of up to 100 metres can be connected between the controller and the...

Страница 6: ...arm resetting switch 9 selection of automatic restarting switch 10 Fig 3 Set the DIP switch as shown in fig 3 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The...

Страница 7: ...pump Restarting will not be carried out until the motor has cooled to normal temperature When the pump connected is used in an explosion hazard area switch 10 must not be in this position At this sett...

Страница 8: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO s...

Страница 9: ...estarting switch 10 Fig 5 Set the DIP switch as shown in fig 5 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP switch must not be set to other switch com...

Страница 10: ...ed out until the motor has cooled to normal tem perature When the pump connected is used in an explosion hazard area switch 10 must not be in this position At this setting the pump must be restarted m...

Страница 11: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO s...

Страница 12: ...automatic restarting switch 10 Fig 7 Set the DIP switch as shown in fig 7 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP switch must not be set to othe...

Страница 13: ...ted is used in an explosion hazard area switch 10 must not be in this position At this setting the pump must be restarted manually after the motor thermal switch has cut out the pump To restart the pu...

Страница 14: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO...

Страница 15: ...ossible chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The above list is not complete...

Страница 16: ...N OFF AUTO selector switch into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control cir cuit fuses see pos 6 in fig 1 d The motor protection relay h...

Страница 17: ...s Section 14 Systems for parallel operation with 4 levels 5 electrodes Section 15 Systems for 100 standby operation with 4 levels 5 electrodes Section 16 Systems for full control operation with 4 leve...

Страница 18: ...instructions of the pump Key to the symbols in fig D1 on page 100 TM02 2349 4101 Pos Description 1 Module CU 214 2 Terminal block for level inputs 11 12 22 32 and 42 3 Terminal block with input for th...

Страница 19: ...itched off for at least 1 minute TM016870 2308 This setting determines the actual application type par allel operation with 3 levels 4 electrodes page 100 At this setting the start up is delayed withi...

Страница 20: ...hing TM02 4643 1402 Pos Description 1 Green indicator light for pump 1 and 2 indicating start ing delay flashing and pump operation permanently on 2 Red indicator light for pump 1 and 2 indicating pum...

Страница 21: ...switch registers overtemperature OFF middle position The pump cannot start when the selector switch has been set to this position The alarm memory is reset by pushing the selector switch into position...

Страница 22: ...etting switch 9 selection of automatic restarting switch 10 Fig 13 Set the DIP switch as shown in fig 13 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP...

Страница 23: ...When the pumps connected are used in explosion hazard areas switch 10 must not be in this position At this setting the pump must be restarted manually after the motor thermal switch has cut out the p...

Страница 24: ...f 1 2 2 1 The reset button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means...

Страница 25: ...re the correct configuration during start up after change of the DIP switch setting The DIP switch setting offers the following possibilities selection of starting delay and automatic test run switch...

Страница 26: ...must be reset manually by means of the reset button the reset button is described in section 15 5 This setting enables automatic restarting after the motor thermal switch has cut out the pump Restarti...

Страница 27: ...electricity supply switched on is off 1 2 2 1 The reset button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the al...

Страница 28: ...larm resetting switch 9 selection of automatic restarting switch 10 Fig 17 Set the DIP switch as shown in fig 17 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note...

Страница 29: ...scribed in section 16 5 This setting enables automatic restarting after the motor thermal switch has cut out the pump Restarting will not be carried out until the motor has cooled to normal temperatur...

Страница 30: ...r switch see position OFF Even if the fault condition still exists the external alarm devices and the built in buzzer will be reset when the reset button is pressed The ON OFF AUTO selector switch for...

Страница 31: ...r to identify possible chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The list above i...

Страница 32: ...or switch into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control cir cuit fuses see pos 6 in fig 9 d The motor protection relays have cut out the...

Страница 33: ...4614 2308 M Ext max 230V max 2A H NC H COM H NO G NC G COM G NO ref 2 LC 110 1 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T1 T2 3 3 L1 L2L3...

Страница 34: ...10 M Ext 1 2 ref 3 max 230V max 2A H NC H COM H NO G NC G COM G NO ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T1...

Страница 35: ...max 230V max 2A H NC H COM H NO G NC G COM G NO LC 110 1 2 ref 3 4 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T...

Страница 36: ...C H COM H NO G NC G COM G NO T12 T22 32 LC 110 1 2 ref 3 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M 1U2 1V2 1W2...

Страница 37: ...C H COM H NO G NC G COM G NO LCD 110 T11 11 12 22 32 42 T21 T12 T22 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Страница 38: ...x 2A ON DIP 1 2 3 4 5 6 7 8 9 10 H NC H COM H NO G NC G COM G NO T11 11 12 22 32 42 T21 T12 T22 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Страница 39: ...DIP 1 2 3 4 5 6 7 8 9 10 LCD 110 H NC H COM H NO G NC G COM G NO T11 11 12 22 32 42 T21 T12 T22 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Страница 40: ...5 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS...

Страница 41: ...d makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark A...

Отзывы: