background image

19

13.2 Setting

Systems for parallel operation with 3 levels (4 electrodes), 
page 100.

The module CU 214 has a 10-pole DIP switch in the bottom right 
corner, see fig. 11.

Note:

 During setting, the controller must be off circuit for at least 

1 minute to ensure the correct configuration during start-up after 
change of the DIP switch setting.

The DIP switch setting offers the following possibilities:

selection of starting delay and automatic test run (switch 4),

setting of stop delay (switches 5, 6 and 7),

selection of automatic alarm resetting (switch 9),

selection of automatic restarting (switch 10).

Fig. 11

Set the DIP switch as shown in fig. 11.

Each individual switch (1 to 10) of the DIP switch can be set to 
position OFF or ON.

Note:

 The DIP switch 

must

 

not

 be set to other switch combina-

tions than those described in this section. 

Set the switches 1 to 10 as follows:

Switches 

1

2

 and 

3

, application type:

When the DIP switch setting is changed, the controller must 
be switched off for at least 1 minute!

Switch 

4

, starting delay and automatic test run 

(only in the case of battery back-up):

When the DIP switch setting is changed, the controller must 
be switched off for at least 1 minute!

Switches 

5

6

 and 

7

, stop delay:

When the DIP switch setting is changed, the controller must 
be switched off for at least 1 minute!

Switch 

8

:

When the DIP switch setting is changed, the controller must 
be switched off for at least 1 minute!

Switch 

9

, automatic alarm resetting:

When the DIP switch setting is changed, the controller must 
be switched off for at least 1 minute!

Switch 

10

, automatic restarting:

When the DIP switch setting is changed, the controller must 
be switched off for at least 1 minute!

TM

01

68

70 23

08

This setting determines the actual application type 

(par-

allel operation with 3 levels (4 electrodes), page 100)

.

At this setting, the start-up is delayed within the range 
from 0 to 255 sec. (random) after the electricity supply 
has been switched on 

when

 the liquid level is suffi-

ciently high.

Automatic test run carried out every 24 hours.

After the electricity has been switched on, the pump will 
start immediately 

when

 the liquid level is sufficiently 

high.

No automatic test run.

The

 stop delay 

is the time from the stop signal is given until the 

pump is stopped. 
It must be ensured that the pump is not running dry.

0 sec.

60 sec.

15 sec.

90 sec.

30 sec.

120 sec.

45 sec.

180 sec.

Switch 8 has no function in connection with the actual 
application 

(parallel operation with 3 levels 

(4 electrodes), page 100)

, but this setting 

must 

be 

maintained!

This setting ensures automatic resetting of alarm 
signals to external alarm devices and the built-in 
buzzer. However, an alarm signal will only be reset if 
the cause of the fault no longer exists. 

At this setting, the alarm signal must be reset manually 
by means of the reset button (the reset button is 
described in section 

13.5

).

This setting enables automatic restarting after the motor 
thermal switch has cut out the pump. Restarting will not 
be carried out until the motor has cooled to normal 
temperature.

When the pumps connected are used in explosion 
hazard areas, switch 10 

must not

 be in this 

position!

At this setting, the pump must be restarted manually after 
the motor thermal switch has cut out the pump. To restart 
the pump, push the ON-OFF-AUTO selector switch into 
position OFF for a short period (the ON-OFF-AUTO 
selector switch is described in section 

13.5

).

When the pumps connected are used in explosion 
hazard areas, switch 10 

must 

be in this position!

Содержание LC 110

Страница 1: ...LC 110 LCD 110 GRUNDFOS INSTRUCTIONS Installation and operating instructions LC 110 LCD 110...

Страница 2: ...bereinstimmen Maschinenrichtlinie 2006 42 EG Norm die verwendet wurde EN 60204 1 2006 Niederspannungsrichtlinie 2006 95 EG Norm die verwendet wurde EN 60439 1 2004 EMV Richtlinie 2004 108 EG Normen di...

Страница 3: ...3 LC 110 LCD 110 Installation and operating instructions 4 Montage und Betriebsanleitung 33 Monterings og driftsinstruktion 68...

Страница 4: ...a LCD 110 31 20 Fault finding chart 32 21 Disposal 32 1 General LC 110 The LC 110 controller is designed for the control of pumps in wastewater water supply and drainage systems Type key 1 1 Applicati...

Страница 5: ...lems with the signal values sent back to the controller may arise In such cases it is recommended to use float switches Note Cables of up to 100 metres can be connected between the controller and the...

Страница 6: ...arm resetting switch 9 selection of automatic restarting switch 10 Fig 3 Set the DIP switch as shown in fig 3 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The...

Страница 7: ...pump Restarting will not be carried out until the motor has cooled to normal temperature When the pump connected is used in an explosion hazard area switch 10 must not be in this position At this sett...

Страница 8: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO s...

Страница 9: ...estarting switch 10 Fig 5 Set the DIP switch as shown in fig 5 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP switch must not be set to other switch com...

Страница 10: ...ed out until the motor has cooled to normal tem perature When the pump connected is used in an explosion hazard area switch 10 must not be in this position At this setting the pump must be restarted m...

Страница 11: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO s...

Страница 12: ...automatic restarting switch 10 Fig 7 Set the DIP switch as shown in fig 7 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP switch must not be set to othe...

Страница 13: ...ted is used in an explosion hazard area switch 10 must not be in this position At this setting the pump must be restarted manually after the motor thermal switch has cut out the pump To restart the pu...

Страница 14: ...button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means of the ON OFF AUTO...

Страница 15: ...ossible chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The above list is not complete...

Страница 16: ...N OFF AUTO selector switch into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control cir cuit fuses see pos 6 in fig 1 d The motor protection relay h...

Страница 17: ...s Section 14 Systems for parallel operation with 4 levels 5 electrodes Section 15 Systems for 100 standby operation with 4 levels 5 electrodes Section 16 Systems for full control operation with 4 leve...

Страница 18: ...instructions of the pump Key to the symbols in fig D1 on page 100 TM02 2349 4101 Pos Description 1 Module CU 214 2 Terminal block for level inputs 11 12 22 32 and 42 3 Terminal block with input for th...

Страница 19: ...itched off for at least 1 minute TM016870 2308 This setting determines the actual application type par allel operation with 3 levels 4 electrodes page 100 At this setting the start up is delayed withi...

Страница 20: ...hing TM02 4643 1402 Pos Description 1 Green indicator light for pump 1 and 2 indicating start ing delay flashing and pump operation permanently on 2 Red indicator light for pump 1 and 2 indicating pum...

Страница 21: ...switch registers overtemperature OFF middle position The pump cannot start when the selector switch has been set to this position The alarm memory is reset by pushing the selector switch into position...

Страница 22: ...etting switch 9 selection of automatic restarting switch 10 Fig 13 Set the DIP switch as shown in fig 13 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note The DIP...

Страница 23: ...When the pumps connected are used in explosion hazard areas switch 10 must not be in this position At this setting the pump must be restarted manually after the motor thermal switch has cut out the p...

Страница 24: ...f 1 2 2 1 The reset button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the alarm memory as this is reset by means...

Страница 25: ...re the correct configuration during start up after change of the DIP switch setting The DIP switch setting offers the following possibilities selection of starting delay and automatic test run switch...

Страница 26: ...must be reset manually by means of the reset button the reset button is described in section 15 5 This setting enables automatic restarting after the motor thermal switch has cut out the pump Restarti...

Страница 27: ...electricity supply switched on is off 1 2 2 1 The reset button is a push button for manual resetting of alarm signals to external alarm devices and the built in buzzer i e not for resetting of the al...

Страница 28: ...larm resetting switch 9 selection of automatic restarting switch 10 Fig 17 Set the DIP switch as shown in fig 17 Each individual switch 1 to 10 of the DIP switch can be set to position OFF or ON Note...

Страница 29: ...scribed in section 16 5 This setting enables automatic restarting after the motor thermal switch has cut out the pump Restarting will not be carried out until the motor has cooled to normal temperatur...

Страница 30: ...r switch see position OFF Even if the fault condition still exists the external alarm devices and the built in buzzer will be reset when the reset button is pressed The ON OFF AUTO selector switch for...

Страница 31: ...r to identify possible chemical attack resulting in corrosion In typical installations the motor protection contacts will work for several years and do not require any inspection Note The list above i...

Страница 32: ...or switch into position ON or AUTO c Control circuit fuses are blown Check and eliminate the cause Replace the control cir cuit fuses see pos 6 in fig 9 d The motor protection relays have cut out the...

Страница 33: ...4614 2308 M Ext max 230V max 2A H NC H COM H NO G NC G COM G NO ref 2 LC 110 1 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T1 T2 3 3 L1 L2L3...

Страница 34: ...10 M Ext 1 2 ref 3 max 230V max 2A H NC H COM H NO G NC G COM G NO ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T1...

Страница 35: ...max 230V max 2A H NC H COM H NO G NC G COM G NO LC 110 1 2 ref 3 4 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4615 2308 M N v w LC 110 T3 T2 1 1 L L N PE T21 T11 PE TM02 4616 2308 PE L1 N L2L3 N M u v w T3 T...

Страница 36: ...C H COM H NO G NC G COM G NO T12 T22 32 LC 110 1 2 ref 3 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M 1U2 1V2 1W2...

Страница 37: ...C H COM H NO G NC G COM G NO LCD 110 T11 11 12 22 32 42 T21 T12 T22 ON DIP 1 2 3 4 5 6 7 8 9 10 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Страница 38: ...x 2A ON DIP 1 2 3 4 5 6 7 8 9 10 H NC H COM H NO G NC G COM G NO T11 11 12 22 32 42 T21 T12 T22 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Страница 39: ...DIP 1 2 3 4 5 6 7 8 9 10 LCD 110 H NC H COM H NO G NC G COM G NO T11 11 12 22 32 42 T21 T12 T22 R TM02 4662 2308 PE M 1N2 1 T21 T11 2U2 2N2 T12 T22 1 2 M 1 N1 1 U1 L N PE 1U2 TM02 4663 2308 PE U1 N M...

Страница 40: ...5 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS...

Страница 41: ...d makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S Denmark A...

Отзывы: