background image

FAULT FINDING

PRESSURE HIGH

The system pressure has exceeded the Pressure-High Alarm. The
pumps will STOP until the pressure drops below the Pressure-High Alarm
OFF Level.
Check that the Pressure-High Alarm setting has not been set too low.
Check that the capacity of the expansion tanks is adequate for the
system.
Check that the pre-charge pressure has been set correctly.

PRESSURE LOW

The system pressure has dropped below the Pressure-Low Alarm setting.
This will NOT stop the pumps from running unless the Water Leak alarm
has

 

cut

 

in.

PUMP A FAULT
PUMP B FAULT

Indicates that either the pump-Overload has tripped (ADVANCED model)
or the respective Pump FUSE has blown.

PUMP TEST FAILURE
PUMP A FAULT
PUMP B FAULT

Displayed along with a respective indication of which pump has failed the
pump test.
Check whether the pump shaft is free to turn.
Check that the pumps are vented.

SENSOR ERROR

Pressure sensor fault.
Check the cables to the pressure sensor.

SERVICE

 

DUE

 

The

 

unit

 

has

 

reached

 

the

 

SERVICE

 

DUE

 

interval.

 

It

 

is

 

important

 

that

 

an

engineer

 

attends

 

site

 

to

 

ins

 

pect

 

the

 

unit, as soon as possible.

SYSTEM

 

FAILURE

 

Can

 

be

 

displayed

 

along

 

with

 

SENSOR

 

ERROR

 

-

 

in

 

this

 

case

 

check

 

the

Sensor

 

or

 

it's

 

Cabling

 

FIRST.

 

If

 

displayed

 

just

 

on

 

its

 

own,

 

then

 

the

controller could be faulty. Replace as a module.

SYSTEM LOCK

Indicates the System has been Locked from operating.

WATER LEAK

The pumps have exceeded the maximum time they are allowed to run in
any

 

given

 

hour.

 

Reset

 

this

 

alarm

 

by

 

Powering-OFF

 

and

 

back

 

again.

WATER LOW

Sensor (Float Switch), low water level in break tank.
Check water level. Check ball valve, if level is low.
Check wiring to float switch if level is OK.

WATER LOW
WATER REFILLING

This not a fault condition, but is for information, and indicating that the
water

 

has

 

now

 

satisfied

 

the

 

Sensor/Float

 

but

 

the

 

controller

 

is

 

allowing

the tank to refill before operating the pump again. See the Water Low
Reset user Set-Up option, for the reset time.

GRUNDFOS PUMPS LTD

Commercial Building Services

Southern & Northern Region: Tel: 08707 503888, Fax: 01942 605970

Scottish & N. Ireland Region: Tel: 01506 461666, Fax: 01506 461555

Domestic Building Services

Tel: 01525 775402, Fax: 01525 775236

Spares

Tel:

 

01942

 

263490,

 

Fax:

 

01942

 

603462

Email:

[email protected]

Service

Mobile Service : Tel: 08450 508100, Fax: 01942 602830

Service Workshop (Leigh): Tel: 01942 263627, Fax: 01942 603462

Office Addresses

Southern

 

(Head)

 

Office:

 

Grovebury

 

Road,

 

Leighton

 

Buzzard,

 

Beds.

 

LU7

 

4TL. Tel: 01525 850000  Fax: 01525 850011

Northern Office:

Orford Court, Greenfold Way, Leigh, Lancs. WN7 3XJ

Scotland & N. Ireland Office:

Flemming Road, Kirton Campus, Livingston,

West Lothian, Scotland EH54 7BN.

General Sales Enquiries:

[email protected]

Grundfos Group Website:

www.grundfos.com

It

 

is

 

the

 

continuing

 

policy

 

of

 

Grundfos

 

to

 

develop

 

and

 

improve

 

our

 

products,

 

and

 

we

reserve the right to amend prices and specification without prior notice.

REF: GB/IMPRESS I&O/CBS/1007

Содержание IMpress

Страница 1: ...IMpress Pressurisation Sets comprising of Basic Advanced Glycol and H C Installation Operation and Maintenance Manual...

Страница 2: ...components functions not fitted to all units DELIVERY AND HANDLING On arrival inspect the unit s for signs of damage before signing the delivery note and report any damage to the supplier within 7 da...

Страница 3: ...ion of sealed chilled water systems MAXIMUM OPERATING CONDITIONS The Grundfos range of IMpress units have been designed to Liquid temperature range 3 to 90 C Ambient temperature up to 40 C Relative Hu...

Страница 4: ...not be subjected to extremes of temperature 2 The environment should be non aggressive and the atmosphere non explosive 3 Ensure that there is sufficient clearance around the unit to allow maintenance...

Страница 5: ...e the front panel by lifting it off the locating pins in the base PIPEWORK CONNECTIONS The service connections to the pressurisation unit should be made as follows 1 Connect the mains cold water suppl...

Страница 6: ...essurised water out 15mm NRV Pumps Mains supply in 5m of cable Elecrical connection Water connection Transducer Pump B Pump A Low Water DIMENSIONS WEIGHTS AND CONNECTION DETAILS PIPEWORK CONNECTIONS W...

Страница 7: ...n Tank overflow 5 Bar Transducer Controller Feeder Water Tank Transducer Pump Pump Low Water Dosing pump Pulsing Water Meter Isolation Valve MIpress Glycol Duo system shown DIMENSIONS WEIGHTS AND CONN...

Страница 8: ...s water in Pressurised water out 22mm NRV 2 off Pumps 2 off Mains supply 230 240v 45 60 Hz 5m of cable Module enclosure Pressurised water out 22mm Transducer 1 pump per circuit shown DIMENSIONS WEIGHT...

Страница 9: ...ld be connected to a 240 volt single phase 13 amp supply only All cables must be of an adequate size to prevent excessive voltage drop in the supply to the unit The electrical installation should be i...

Страница 10: ...Volt Free Contact Low Water Pump B Pump A 240V 1Ph 13A Mains Supply Microprocessor Controller PCB Pressure Transducer...

Страница 11: ...Pump A Pump B 240V 1Ph 13A Mains Supply...

Страница 12: ......

Страница 13: ...r do not pull on the cable Do not attempt to detached from the display board on the front cover The VFC changeover terminals are marked STOP No other connections are required or should be made into th...

Страница 14: ...ty and the pumps to run dry as this could invalidate the pump warranty This is especially important after initial installation and during the fill cycle OPERATION Do not attempt to supply electricity...

Страница 15: ...Up Menu Button When in Normal Operational Mode pressing this button will cause the controller to jump into the Set Up Menu Mode When in Set Up Mode this button will cause any displayed value to be sav...

Страница 16: ...e The pump will switch off when the Set Pressure is reached Setting range 0 to 16 bars default setting 0 3 bars Note the setting for Differential B can be ignored Pump Test This feature prevents pumps...

Страница 17: ...As e t t i n go f a l l s p a c e s b l a n k s d i s a b l e s t h eP IN Whilst it is recommended that a PIN be always programmed to prevent unauthorised tampering the User Set Up Menu is factory sh...

Страница 18: ......

Страница 19: ...le Entry have been much expanded to keep abreast of additional Alarm BMS Telemetry and Communications features The Bottom of the Control Box is provided with two additional grey M16 Cable Glands and F...

Страница 20: ...OL Version PUMP A RUN J110 PUMP B RUN J111 PRESS LOW J101 PRESS HIGH J102 WATER LOW J103 WATER LEAK J104 PUMP A FAULT J105 PUMP B FAULT J106 SERVCE DUE J107 SYSTEM FAULT J108 TELEMETRY VOLT FREE CONTA...

Страница 21: ...le Entry Facilities for Cable Entry have been much expanded to keep abreast of the additional Alarm BMS Telemetry and Communications features of the Impress Advanced Mk 2 The Bottom of the Control Box...

Страница 22: ...yed out terminals may not be installed in this version PUMP A RUN J110 PUMP B RUN J111 PRESS LOW J101 PRESS HIGH J102 WATER LOW J103 WATER LEAK J104 PUMP A FAULT J105 PUMP B FAULT J106 SERVCE DUE J107...

Страница 23: ...OLD Set UP there are a number of Set Ups that refer to the HOT only which have been separated out for clarity into a separate sub section This sub section for the HOT Is accessed through the HOT SET U...

Страница 24: ...T and COLD are displayed in the form C 2 1B H 1 9B Where C indicates the COLD circuit in the range to a maximum of 10 0 Bar and H indicates the HOT circuit similarly to 10 0 Bar All other options and...

Страница 25: ...ng WATER LEAK The pumps have exceeded the maximum time they are allowed to run in any given hour Reset this alarm by Powering OFF and back again WATER LOW Sensor Float Switch low water level in break...

Отзывы: