TM053496
•
Open the drain holes in the product.
•
Connect the product permanently to the mains supply and activate the built-in standstill heating function.
4.1.5 Installation altitude
The installation altitude is the height above sea level of the installation site.
Products installed up to 1000 m above sea level can be loaded 100 %.
The motors can be installed up to 3500 m above sea level.
Products installed more than 1000 m above sea level must not be fully loaded due to the low density and consequent low cooling
effect of the air.
The motor output power (P2) in relation to the altitude above sea level is shown in the graph.
60
80
90
70
100
500
1500
2500
3500
X
Y
TM069816
Pos.
Description
Y
P2 [%]
X
Altitude [m]
To maintain the galvanic isolation and ensure correct clearance according to EN60664-1:2007, adapt the supply voltage to the altitude.
The supply voltage for a single-phase motor in relation to the altitude is shown in the graph.
500
1500
2500
3500
200
210
220
230
240
250
Y
X
TM069867
Pos.
Description
Y
Supply voltage
X
Altitude [m]
The supply voltage for a three-phase motor in relation to the altitude is shown in the graph.
500
480
460
440
420
380
400
500
2500
3500
1500
Y
X
TM069866
9
English (GB)