3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
TM053510
Terminal Type
Function
NC
Normally closed contact
Signal relay 1. LIVE or PELV.
C1
Common
NO
Normally open contact
NC
Normally closed contact
Signal relay 2. PELV only.
C2
Common
NO
Normally open contact
10
DI3/OC1
Digital input/output, configurable.
Open collector: Maximum 24 V resistive or inductive.
4
AI1
External sensor.
Pressure sensor: Pressure signal, 0.5 to 3.5 V. Connect the white wire to this terminal.
2
DI1
Digital input, configurable.
Digital input 1 is factory-set to be start or stop input where an open circuit results in stop. A
jumper has been factory-fitted between terminals 2 and 6. Remove the jumper if digital input 1
is to be used as external start or stop or any other external function.
5
+5 V
Power supply to a potentiometer or sensor.
6
GND
Protective earth.
A
GENIbus, A
GENIbus, A (+).
Y
GENIbus, Y
GENIbus, Y (GND).
B
GENIbus, B
GENIbus, B (-).
3
GND
Protective earth.
15
+24 V
Power supply.
8
+24 V
Power supply.
26
+5 V
Power supply to a potentiometer or sensor.
Pressure sensor: Voltage supply, +5 VDC, PELV. Connect the brown wire to this terminal.
14
English (GB)
Содержание CMBE TWIN
Страница 1: ...CMBE TWIN Installation and operating instructions GRUNDFOS INSTRUCTIONS ...
Страница 2: ......