3.2 CIM 300 BACnet module

Fig. 3

CIM 300 BACnet module

3.3 Connecting to the BACnet network

A screened, twisted-pair cable must be used.

The ANSI/ASHRAE BACnet standard states that the cable screen 

must only be earthed at one end of the segment to prevent earth 

fault currents.

3.4 Setting the BACnet transmission speed

The transmission speed must be set correctly before the CIM 300 is 

ready to communicate on the BACnet MS/TP network. DIP switches 

SW4 and SW5 are used to set the transmission speed. 

The default transmission speed is 9600 bits/s, but higher speeds 

are recommended for better data throughput. All devices on the 

BACnet MS/TP network must communicate at the same 

transmission speed.

Fig. 4

BACnet transmission speed settings

3.4.1 DIP switch settings
Available transmission speeds in bits/s: 9600, 19200, 38400 and 

76800. 
Use DIP switches SW4 and SW5 to select the desired speed.

The default transmission speed is 9600 bit/s, as per the BACnet 

MS/TP standard. The transmission speed will be effective 

immediately after setting the values of the DIP switch.

3.5 Selecting the Device Object Instance Number

The Device Object Identifier value consists of two components:
• a 10-bit Object Type (bits 22 to 31)
• a 22-bit Instance Number (bits 0 to 21).

Fig. 5

Bit numbers

The Object Type is fixed and determines that it is a Device Object. 

The Instance Number is a numeric code that is used to identify the 

device. It must be unique inter-network-wide, i.e. on all 

interconnected networks.
The CIM 300 offers two different approaches to setting the BACnet 

Device Object Instance Number: default and custom, both 

described in the following subsections.

TM

04 1

697 0

908

Pos. Designation

Description

1

Plus

BACnet Plus terminal 

(RS-485 positive data signal)

2

Minus

BACnet Minus terminal 

(RS-485 negative data signal)

3

Ground

BACnet Ground terminal

4

SW1/SW2

On/off switches for termination 

resistor

5

SW3/SW4/SW5

Switches for selecting the BACnet 

transmission speed and the default 

or custom Device Object Instance 

Number

6

LED1

Red/green status LED for 

BACnet communication

7

LED2

Red/green status LED for internal 

communication between the 

CIM 300 and the Grundfos booster

8

SW6

Hexadecimal rotary switch for 

setting the BACnet MAC address 

(four most significant bits)

9

SW7

Hexadecimal rotary switch for 

setting the BACnet MAC address 

(four least significant bits)

1 2 3

4

5

6

7

8

9

BACnet terminal

Recommended colour

Data signal

Plus

Red

Positive

Minus

Green

Negative

Ground

Grey

Ground

TM

04 

1710 

0908

Transmission speed 

[bits/s]

SW4

SW5

9600

OFF

OFF

19200

OFF

ON

38400

ON

OFF

76800

ON

ON

TM

04 

5977

 4509

SW4 SW5

31

22

10 bits

22 bits

21

0

Object type

Instance Number

...

Содержание CIU 300

Страница 1: ...GRUNDFOS INSTRUCTIONS Grundfos CIU 300 BACnet MS TP for Grundfos Hydro MPC Control MPC and Multi E Functional pro le and user manual...

Страница 2: ...2...

Страница 3: ...in this document 2 Introduction 2 1 About this functional profile This functional profile describes the CIU 300 BACnet Communication Interface Unit 300 for the following Grundfos booster systems Grund...

Страница 4: ...et module It can either be mounted on a DIN rail or on a wall It is used in conjunction with Grundfos Hydro MPC Control MPC and Multi E Fig 1 CIU 300 solution for Hydro MPC and Hydro Multi E Note The...

Страница 5: ...s SW6 and SW7 See section 3 7 Selecting the BACnet MAC address Line termination On or Off Set via DIP switches SW1 and SW2 See section 3 8 Termination resistor Supported transmission speeds bits s 960...

Страница 6: ...egments can be connected by use of repeaters or bridges thus forming networks Multiple networks may be interconnected by BACnet routers to form a BACnet inter network 3 1 1 Line termination resistors...

Страница 7: ...ce Number bits 0 to 21 Fig 5 Bit numbers The Object Type is fixed and determines that it is a Device Object The Instance Number is a numeric code that is used to identify the device It must be unique...

Страница 8: ...elected it will be stored in the device and replace the default naming scheme 3 7 Selecting the BACnet MAC address To set the BACnet MAC address use the two hexadecimal rotary switches SW6 and SW7 The...

Страница 9: ...Communication active Flashing red Fault in the BACnet communication Permanently red Fault in the CIM 300 BACnet configuration Status Description Off The CIM 300 has been switched off or is starting up...

Страница 10: ...a value to be changed over the network X WritePropertyMultiple DS WPM B The CIM CIU 300 allows multiple values to be changed over the network X SubscribeCOV DS COV B The CIM CIU 300 can be a provider...

Страница 11: ...BACnetServicesSupported Indicates which standardised protocol services are supported R Protocol_Object_Types_Supported BACnetObjectTypesSupported Indicates which standardised protocol object types ar...

Страница 12: ...gital input 2 status R 0 Not active 1 Active X X BI 13 Digital input 3 status R 0 Not active 1 Active X X BI 14 Digital output 1 status R 0 Not active 1 Active X X BI 15 Digital output 2 status R 0 No...

Страница 13: ...ESERVED 5 Constant flow 6 Constant temperature 7 Constant level 8 Constant percentage See section 7 1 Control modes for details on the control modes X X MI 1 Actual operating mode R Reads the current...

Страница 14: ...level 8 Constant percentage See section 7 1 Control modes for details on the control modes Note Multi E always runs constant pressure mode X MO 1 Set operating mode W Sets the operating mode if bus co...

Страница 15: ...bient temperature C S AI 34 Forward temperature R Flow pipe temperature C S AI 35 Return temperature R Return pipe temperature C S AI 36 Differential temperature R Differential temperature C S AI 37 O...

Страница 16: ...among others 000 No alarm 003 External fault 010 Pump communication alarm 089 Closed loop feedback sensor signal fault 088 General meas sensor signal fault 203 All pumps in alarm 210 Pressure high 21...

Страница 17: ...he pressure is constant regardless of the flow A pressure sensor is required Constant flow Constant level Constant temperature Constant percentage Closed loop Constant flow constant level constant tem...

Страница 18: ...nitoring and resetting This example shows how to monitor faults or warnings in the booster and how to manually reset a fault The Fault code object AV 0 and the Warning code object AV 1 can both hold a...

Страница 19: ...lue of 1 Now the Hydro MPC should be running at 50 in constant pressure mode with bus control 7 7 Product simulation Product profile simulation booster simulation can be useful for testing and pre com...

Страница 20: ...Number See section 3 5 Selecting the Device Object Instance Number 5 If necessary set line termination See section 3 8 Termination resistor 6 Connect the GENIbus cable from the CIU 300 to the booster...

Страница 21: ...3 8 Termination resistor Fault Possible cause Remedy 1 The CIM CIU 300 does not communicate on the BACnet MS TP network a Configuration or wiring fault Ensure that the cable between the BACnet MS TP...

Страница 22: ...Pad 2 bytes 0x55 0xFF 1 byte 1 byte 1 byte 2 bytes MSB first 1 byte Variable 0 501 bytes 2 bytes LSB first At most 1 byte 0xFF Type Name Description 00 Token Used to pass network mastership to the de...

Страница 23: ...or current protection activated MCP 93 Signal fault sensor 2 17 Performance requirement cannot be met 56 Underload 94 Limit exceeded sensor 1 18 Commanded alarm standby trip 57 Dry running 95 Limit ex...

Страница 24: ...lt 198 Operation with increased power consumption 230 Network alarm 159 CIM fault Communication Interface Module 199 Process out of range monitoring estimation calculation control 231 Ethernet No IP a...

Страница 25: ...7 2 13 0 D 64 4 0 115 7 3 14 0 E 65 4 1 116 7 4 15 0 F 66 4 2 117 7 5 16 1 0 67 4 3 118 7 6 17 1 1 68 4 4 119 7 7 18 1 2 69 4 5 120 7 8 19 1 3 70 4 6 121 7 9 20 1 4 71 4 7 122 7 A 21 1 5 72 4 8 123 7...

Страница 26: ...26...

Страница 27: ...gotanda Shiagawa ku Tokyo 141 0022 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2...

Страница 28: ...nking ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S...

Отзывы: