16
6.7 Analog outputs
Object for setting a new setpoint in the booster.
6.8 Analog values
Objects for configuration of the CIM/CIU 300 and/or the booster.
ID
Object Name
R/W Notes
Unit
Multi-E
MPC
AO, 0 Set setpoint
W
Sets the booster setpoint if bus control is enabled.
A value of 0 does not imply a stop.
See section
7.2 Setpoint
..
%
X
X
ID
Object Name
R/W Notes
Multi-E
MPC
AV, 0
Custom device object instance number
R/W
Value for Custom Device Object Instance Number.
Used in conjunction with DIP switch SW3.
See section
3.5 Selecting the Device Object Instance
Number
.
Present_Value range: 0-0x3FFFFE.
Default Present_Value: 0xE7.
X
X
AV, 1
BACnet watchdog
R/W
Time in seconds before BACnet communication
watchdog times out, and sets the booster to use its local
settings.
See section
7.3 BACnet communication watchdog
.
0 = Disabled (default)
Set to a value between 5 and 3600 to enable.
X
X
AV, 4
Simulation event code
R/W
Event code to simulate.
The following event code values are available for
simulation (among others):
000 = No alarm
003 = External fault
010 = Pump communication alarm
089 = Closed-loop feedback sensor signal fault
088 = General (meas.) sensor signal fault
203 = All pumps in alarm
210 = Pressure high
211 = Pressure low
214 = Water shortage
231 = No Ethernet address from DHCP server.
X
AV, 5
Simulation device type
R/W
Device type of simulated event.
0 = Controller
2 = Pump
3 = IO 351
4 = Primary sensor
7 = IO 351
8 = System
9 = Analog input
10 = Pilot pump
11 = Limit-exceeded function.
X
AV, 6
Simulation device number
R/W
Device number of simulated event.
If the device type is "Pump", the device number
indicates the pump number [1-6].
If the device type is "Analog input", the device number
indicates the sensor that generated the event [1-7].
X
AV, 7
Simulation event action type
R/W
The associated action to the event.
0 = Go to operating mode "Stop".
1 = Go to operating mode "Stop" (delay).
2 = Go to operating mode "Minimum".
3 = Go to operating mode "User-defined".
4 = Go to operating mode "Maximum".
5 = Set pumps in source mode to "Local control".
6 = No action (warning only).
7 = Go to operating mode "Emergency run".
X
AV, 8
Simulation event reset type
R/W
Resetting type for simulated event. Manual or automatic.
0 = Manual resetting
1 = Automatic resetting.
X