14
6.5 Multistate outputs
Objects that set an enumeration value in the booster.
ID
Object Name
R/W
Notes
Multi-E
MPC
MO, 0
Set control mode
W
Sets the control mode if bus control is enabled.
1 = Constant speed
2 = Constant pressure
3 = Proportional pressure
4 = RESERVED
5 = Constant flow
6 = Constant temperature
7 = Constant level
8 = Constant percentage.
See section
7.1 Control modes
for details
on the control modes.
Note: Multi-E always runs constant pressure mode.
X
MO, 1
Set operating mode
W
Sets the operating mode if bus control is enabled.
1 = Start (normal)
2 = Stop
3 = Minimum (MPC only)
4 = Maximum.
X
X
MO, 2
Product simulation
W
Enables product simulation (for commissioning and
testing purposes, can only be enabled when no
physical booster is present).
1 = Disabled
5 = Hydro Multi-E
6 = Hydro MPC.
See section
7.7 Product simulation
for details.
X
X