Grundfos CIU 300 Скачать руководство пользователя страница 18

18

7.2 Setpoint

This object accepts values ranging from 0 to 100 (0 % to 100 %). 

This is illustrated in fig. 

9

The setpoint value can represent speed, pressure, flow, etc., 

depending on the selected control mode.
A setpoint of 0 does not imply a stop.

Fig. 9

Setpoint

7.2.1 Setpoint examples
Closed loop
If the control mode is set to Constant pressure (closed loop) and 

the pressure sensor is in the range of 0 to 10 bar, a setpoint of 

80 % will result in an effective setpoint of 8 bar.
If the sensor range was 0 to 16 bar, a 50 % setpoint would be 8 bar, 

a 25 % setpoint would be 4 bar, and so on.

Fig. 10 Constant pressure

Open loop
If the control mode is set to Constant speed (open loop), the 

setpoint is interpreted as setpoint for the booster performance.

Fig. 11 Constant speed

7.3 BACnet communication watchdog

A BACnet communication watchdog is implemented in the 

CIM/CIU 300. If no BACnet communication is detected for the time 

period defined by the BACnet watchdog object (AV, 1), and the 

control source of the booster is set to Bus control (BO, 0), the 

CIM 300 will make the booster run with the settings defined in 

local mode.
This functionality can be used to define the booster behaviour in 

case of a BACnet communication breakdown. Before enabling the 

watchdog, the local booster settings should be made with either 

a Grundfos PC Tool or the Grundfos R100 remote control (for 

Multi-E only). This ensures that the booster behaves as expected if 

the BACnet communication breaks down.
When BACnet communication is re-established after a watchdog 

timeout, the booster will run with the remote settings again.
When the Present_Value of the AV, 1 object is set to 0, the 

watchdog is disabled (default). To enable the watchdog, set the 

Present_Value to [5-3600] seconds.

7.4 Fault monitoring and resetting

This example shows how to monitor faults or warnings in the 

booster and how to manually reset a fault.
The Fault code object (AV, 0) and the Warning code object (AV, 1) 

can both hold a Grundfos-specific fault code. See section 

11. Grundfos alarm and warning codes

 for code interpretation.

Warnings are notifications only, and a warning will normally not 

stop the booster system.
If a fault is to be manually reset, use the Reset fault object (BO, 4). 

When the Present_Value of this object is set to 1, a Reset fault 

command is sent to the device.

7.5 Fault simulation example

Fault simulation can be helpful for testing alarm behaviour for 

a Hydro MPC booster system. The system will behave exactly as if 

a real alarm was present.
This example shows how to simulate a "Pressure high" alarm on 

a Hydro MPC that will result in a stop of all pumps, and require 

manual resetting.
• Set "Simulation event code" (AV, 4) to 210 (Pressure high).
• Set "Simulation device type" (AV, 5) to 8 (System).
• Set "Simulation device number" (AV, 6) to 1 (System).
• Set "Simulation event action type" (AV, 7) to 0 (Stop).
• Set "Simulation event reset type" (AV, 8) to 0 (Manual 

resetting).

• Set "Fault simulation" (BO, 5) to 1 (Enabled).
• The CU 351 will now enter into the system mode "Event action", 

and in this case stop all pumps, and the red LED on the CU 351 

will be on. On the CU 351 display, the "Pressure high" alarm is 

indicated.

• Read "Fault simulation status" (BI, 28), and see that it is set to 1 

(Fault simulation enabled).

• Remove the simulated alarm settings by setting "Fault 

simulation" (BO, 5) to 0 (Disabled).

• Reset the alarm via the CU 351 display or via the BACnet object 

"Reset fault" (BO, 4), and the CU 351 will go back to normal 

operation.

Note

The setpoint is a percentage of the maximum setpoint 

or sensor maximum (max. = 100 %).

TM

04 

2373 

2508

TM

04 2

371 

2508

TM

04

 2372

 2508

Sensor 

maximum

Minimum 

setpoint

Effe

ctive se

tpoint

 0 %

100 %

Setpoint [%]

10 bar

8 bar

 0 %

100 %

 80 %

Maximum 

booster 

performance

50 % system 

performance

0 %

100 %

50 %

Содержание CIU 300

Страница 1: ...GRUNDFOS INSTRUCTIONS Grundfos CIU 300 BACnet MS TP for Grundfos Hydro MPC Control MPC and Multi E Functional pro le and user manual...

Страница 2: ...2...

Страница 3: ...in this document 2 Introduction 2 1 About this functional profile This functional profile describes the CIU 300 BACnet Communication Interface Unit 300 for the following Grundfos booster systems Grund...

Страница 4: ...et module It can either be mounted on a DIN rail or on a wall It is used in conjunction with Grundfos Hydro MPC Control MPC and Multi E Fig 1 CIU 300 solution for Hydro MPC and Hydro Multi E Note The...

Страница 5: ...s SW6 and SW7 See section 3 7 Selecting the BACnet MAC address Line termination On or Off Set via DIP switches SW1 and SW2 See section 3 8 Termination resistor Supported transmission speeds bits s 960...

Страница 6: ...egments can be connected by use of repeaters or bridges thus forming networks Multiple networks may be interconnected by BACnet routers to form a BACnet inter network 3 1 1 Line termination resistors...

Страница 7: ...ce Number bits 0 to 21 Fig 5 Bit numbers The Object Type is fixed and determines that it is a Device Object The Instance Number is a numeric code that is used to identify the device It must be unique...

Страница 8: ...elected it will be stored in the device and replace the default naming scheme 3 7 Selecting the BACnet MAC address To set the BACnet MAC address use the two hexadecimal rotary switches SW6 and SW7 The...

Страница 9: ...Communication active Flashing red Fault in the BACnet communication Permanently red Fault in the CIM 300 BACnet configuration Status Description Off The CIM 300 has been switched off or is starting up...

Страница 10: ...a value to be changed over the network X WritePropertyMultiple DS WPM B The CIM CIU 300 allows multiple values to be changed over the network X SubscribeCOV DS COV B The CIM CIU 300 can be a provider...

Страница 11: ...BACnetServicesSupported Indicates which standardised protocol services are supported R Protocol_Object_Types_Supported BACnetObjectTypesSupported Indicates which standardised protocol object types ar...

Страница 12: ...gital input 2 status R 0 Not active 1 Active X X BI 13 Digital input 3 status R 0 Not active 1 Active X X BI 14 Digital output 1 status R 0 Not active 1 Active X X BI 15 Digital output 2 status R 0 No...

Страница 13: ...ESERVED 5 Constant flow 6 Constant temperature 7 Constant level 8 Constant percentage See section 7 1 Control modes for details on the control modes X X MI 1 Actual operating mode R Reads the current...

Страница 14: ...level 8 Constant percentage See section 7 1 Control modes for details on the control modes Note Multi E always runs constant pressure mode X MO 1 Set operating mode W Sets the operating mode if bus co...

Страница 15: ...bient temperature C S AI 34 Forward temperature R Flow pipe temperature C S AI 35 Return temperature R Return pipe temperature C S AI 36 Differential temperature R Differential temperature C S AI 37 O...

Страница 16: ...among others 000 No alarm 003 External fault 010 Pump communication alarm 089 Closed loop feedback sensor signal fault 088 General meas sensor signal fault 203 All pumps in alarm 210 Pressure high 21...

Страница 17: ...he pressure is constant regardless of the flow A pressure sensor is required Constant flow Constant level Constant temperature Constant percentage Closed loop Constant flow constant level constant tem...

Страница 18: ...nitoring and resetting This example shows how to monitor faults or warnings in the booster and how to manually reset a fault The Fault code object AV 0 and the Warning code object AV 1 can both hold a...

Страница 19: ...lue of 1 Now the Hydro MPC should be running at 50 in constant pressure mode with bus control 7 7 Product simulation Product profile simulation booster simulation can be useful for testing and pre com...

Страница 20: ...Number See section 3 5 Selecting the Device Object Instance Number 5 If necessary set line termination See section 3 8 Termination resistor 6 Connect the GENIbus cable from the CIU 300 to the booster...

Страница 21: ...3 8 Termination resistor Fault Possible cause Remedy 1 The CIM CIU 300 does not communicate on the BACnet MS TP network a Configuration or wiring fault Ensure that the cable between the BACnet MS TP...

Страница 22: ...Pad 2 bytes 0x55 0xFF 1 byte 1 byte 1 byte 2 bytes MSB first 1 byte Variable 0 501 bytes 2 bytes LSB first At most 1 byte 0xFF Type Name Description 00 Token Used to pass network mastership to the de...

Страница 23: ...or current protection activated MCP 93 Signal fault sensor 2 17 Performance requirement cannot be met 56 Underload 94 Limit exceeded sensor 1 18 Commanded alarm standby trip 57 Dry running 95 Limit ex...

Страница 24: ...lt 198 Operation with increased power consumption 230 Network alarm 159 CIM fault Communication Interface Module 199 Process out of range monitoring estimation calculation control 231 Ethernet No IP a...

Страница 25: ...7 2 13 0 D 64 4 0 115 7 3 14 0 E 65 4 1 116 7 4 15 0 F 66 4 2 117 7 5 16 1 0 67 4 3 118 7 6 17 1 1 68 4 4 119 7 7 18 1 2 69 4 5 120 7 8 19 1 3 70 4 6 121 7 9 20 1 4 71 4 7 122 7 A 21 1 5 72 4 8 123 7...

Страница 26: ...26...

Страница 27: ...gotanda Shiagawa ku Tokyo 141 0022 Japan Phone 81 35 448 1391 Telefax 81 35 448 9619 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2...

Страница 28: ...nking ahead makes it possible Innovation is the essence The name Grundfos the Grundfos logo and the payoff Be Think Innovate are registrated trademarks owned by Grundfos Management A S or Grundfos A S...

Отзывы: