10. Index
The index contains all objects in the BACnet profile for MIXIT. The
objects are divided by function, for example "System alarm/warning
status and reset".
10.1 BACnet device object
The following properties are supported in the device object.
Property identifier
Data type
Description
Access
Object_identifier
BACnetObjectIdentifier
Device Object Instance Number
R
Object_name
Character string
Device Object Name
R/W
Object_Type
BACnetObjectType
Device
R
System_Status
BACnetDeviceStatus
Operational
R
Vendor_Name
Character string
Grundfos
R
Vendor_Identifier
Unsigned16
227
R
Model_Name_Family
Character string
Grundfos product family. This will
show the Grundfos pump model
to which the MIXIT unit is
connected to.
R
Model_Name_type
GrundfosUnitType
Grundfos product type number.
R
Model_Name_version
GrundfosUnitVersion
Grundfos product version number.
R
Firmware_Revision
Character string
Revision number of the BACnet
firmware in the MIXIT unit.
R
Application_Software_Version
Character string
Software build date, DD-MM-
YYYY.
R
Location
Character string
The user can enter a location
here (maximum 200 characters).
R/W
Description
Character string
The user can enter a description
here (maximum 200 characters).
R/W
Protocol_Version
Unsigned
Actual revision of the BACnet
protocol.
R
Protocol_Revision
Unsigned
Actual revision of the BACnet
protocol.
R
Protocol_Services_Supported
BACnetServicesSupported
This indicates which standardised
protocol services are supported.
R
Protocol_Object_Types_Supporte
d
ProtocolObjectTypesSupported
This indicates which standardised
protocol object types are
supported.
R
Object_List
BACnetARRAY[N]ofBACnetObjec
tIdentifier
An array of objects available.
R
Max_APDU_length_Accepted
Unsigned
The maximum number of bytes
that may be contained in a single
APDU.
R
Segmentation_Supported
BACnetSegmentation
This indicates if segmentation of
messages is possible. It will
always read
NO_SEGMENTATION to indicate
that segmentation is not possible.
R
APDU_Timeout
Unsigned
This indicates the amount of time
in ms before timeout.
R
Number_Of_APDU_Retries
Unsigned
This indicates the maximum
number of times an APDU is to be
retransmitted.
R
24