9.8 Reading and resetting warnings and alarms
•
Read out system warnings via AI,35.
•
Read out system alarms via AI,37.
•
Pump warnings codes are read via AI,5.
•
Pump alarm codes are read via AI,6.
•
Reset alarms and warnings via BO,2.
ID
Object name R/W
Description
AI,35
Status
System
Warning
Code [Enum]
R
97: Missing analog input
125: Outdoor sensor fault
126: Remote air temperature sensor
fault
127: System pressure sensor fault
157: Real time clock battery fault
169: Flow sensor fault
175: Supply (forward) temp. sensor
fault
176: Return temperature sensor
fault
211: System pressure low.
AI,37
Status
System
Alarm Code
[Enum]
R
10: Pump communication fault
39: Valve fault
91: Flow temperature sensor fault
236: Pump faulty.
AI,5
Status Pump
Warning
Code [Enum]
R
Actual pump warning code.
AI,6
Status Pump
Alarm Code
[Enum]
R
Actual pump alarm code.
BO,2 Reset fault
W
Resets pending alarms and
warnings. The data point is rising
edge triggered.