background image

Operating the Pump

Page 10

Page 9

Installation Procedures

Installation depths

Maximum installation depth: below the static water level: 500 feet,
Minimum installation depths: 1.75' below the dynamic water level:

Vertical installation:

During start-up and operation, the pump must always be
completely submerged in water.

Horizontal installation:

The pump must be installed at least 1.75 ft. below the
dynamic water level. If there is a risk that the pump might be
covered by mud, the pump must always be placed in a flow
sleeve.

17. Generator Operation

•  It is OK to operate the Redi-Flo3 with a generator.

The generator must be sized 10% above the pumps P1
(Input Power) values.
Use the table to select the correct size generator for the
motor HP.

16. Installing the Pump(cont.)

4.

Lower the pump into the well. Make sure the motor cable is not
damaged when the pump is lifted or lowered into the well —
especially in 3" wells.

NOTE:  Do not lower or lift the pump

using the  motor cable.

5.

When the pump has been installed to the required depth, the
installation should be finished by means of a well seal. Note that
the dynamic water level should always be above the pump.

6.

Loosen the safety wire so that it becomes unloaded and lock it to
the well seal using a cable clamp.

7.

Attach the supplemental information label at the electrical
installation site.

8.

Complete the electrical connections. Remember that  a
capacitor or a control box should NEVER be connected to a
Redi-Flo3 submersible pump.

18. Starting the Pump for the First Time

When the pump has been connected correctly, the pump should be
started with the discharge valve closed approximately one-third.  Due
to the soft start feature, the pump takes approximately 2 seconds to
develop full pressure.

Motor Cooling and Other Considerations

      •

Make sure the well is capable of yielding a minimum quantity
of water corresponding to the pump capacity.

Do not start the pump until it is completely submerged in the
liquid.

As the valve is being opened, the drawdown should be checked to
ensure that the pump always remains submerged.

To ensure the necessary cooling of the motor, the pump should
never be set so low that it gives no water.  If the flow rate
suddenly falls, the reason might be that the pump is pumping
more water than the well can yield.

Water Impurities

If there are impurities in the water, the valve should be opened
gradually as the water becomes clearer. The pump should not be
stopped until the water is clean, otherwise the pump parts and the
check valve may become clogged.

When the water is clean the valve should be fully opened.

Minimum flow rate

To ensure the necessary cooling of the motor, the pump flow rate
should never be set to a value lower than .2 gpm. If the flow rate
suddenly falls, the reason might be that the pump is pumping
more water than the well can yield.

Note:

The pump's dry-running protection is effective only within
the recommended duty range of the pump.

Note:

Do not let the pump run against a closed discharge valve for
more than 5 minutes. When the discharge valve is closed,
there is no cooling flow and there is a risk of overheating in
motor and pump.

Motor HP

Min.  Generator Size (Watts)

1/3 - 1/2 A

1000

1/2 - 3/4 B

1700

1- 1

1

/

2

 C

2000

Содержание 10SQE03A-100-NE

Страница 1: ...t Permanent Magnet Motor High Starting Torque Soft Start 2 seconds to reach maximum rpm and maximum pressure Built in Smart Motor Protection with automatic restart Communication Through the Redi Flo3...

Страница 2: ...ORANYINCIDENTALORCONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHERCAUSES THEREARENOEXPRESSORIMPLIEDWARRANTIES INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PU...

Страница 3: ...p life and optimal performance can best be obtained through proper well development and in the case of higher fluid temperatures use a cooling shroud A check should be made to ensure that the installa...

Страница 4: ...uid It is recommended to check and if needed refill the motor with GRUNDFOS motor fluid SML 2 If the pump is to be installed horizontally e g in a tank and there is a risk that the pump might be cover...

Страница 5: ...l position with an inclination of approx 10 3 Remove the filling plug using a screwdriver or a similar tool 4 Inject motor liquid into the motor with a filling syringe or similar tool see fig 3 5 To a...

Страница 6: ...the pump is connected to an installation where a Ground Fault circuit breaker GFI is used as additional protection this circuit breaker must trip out when ground fault currents with DC content pulsat...

Страница 7: ...trol box should NEVER be connected to a Redi Flo3 submersible pump WARNING To reduce the risk of electric shock during operation of this pump requires the provision of acceptable grounding If the mean...

Страница 8: ...50 1020 1610 2510 3880 5880 3 4 300 480 760 1200 1870 2890 4370 6470 1 250 400 630 990 1540 2380 3610 5360 6520 1 1 2 190 310 480 770 1200 1870 2850 4280 5240 10 Cable Sizing 11 Motor Cable Redi Flo3...

Страница 9: ...Check that the motor socket is clean and dry 4 Press the cable plug into the motor socket The plug will only fit one way see fig 6 5 Install and tighten the four nuts see fig 6 When the plug has been...

Страница 10: ...l cut and fit together tightly to ensure that they do not work loose 15 Installing the Pump Installation Depth The dynamic water level should always be above the pump see fig 11 A Dynamic water level...

Страница 11: ...e correct size generator for the motor HP 16 Installing the Pump cont 4 Lower the pump into the well Make sure the motor cable is not damaged when the pump is lifted or lowered into the well especiall...

Страница 12: ...denly falls the reason might be that the pump is pumping more water than the well can yield Water Impurities If there are impurities in the water the valve should be opened gradually as the water beco...

Страница 13: ...overload overtemperature MSE 3NE Motors Note To set Dry Run limit in the MSE NE pumps you need to connect the pump to a Redi Flo3 status box Refer to Redi Flo3 status box I O for proper connections To...

Страница 14: ...shaft end with a vegetable based grease 3 Screw the pump end on the motor A spanner may be used on the clamping faces of the pump part see fig 12 4 Install cable guard as described on page 7 When pump...

Страница 15: ...is larger than anticipated capacity b The valve s in the discharge pipe are partly closed blocked c The discharge pipe is partly chocked by impurities Iron bacteria d The non return valve of the pump...

Страница 16: ...e the valve oked Pull out the pump Check and clean or replace the pump if necessary Clean the pipes Repair replace the pump Check and repair the piping Replace Check the electricity supply Increase th...

Страница 17: ...sed in the product please deliver the product or any hazardous materials from it to your nearest GRUNDFOS company or service center Insulation Test Resistance Test High voltage Test Measure the voltag...

Страница 18: ...15SQE NE 1 1 4 NPT 22 30SQE NE 1 1 2 NPT STORAGE CONDITIONS Minimum Ambient Temperature 4 F Maximum Ambient Temperature 140 F Freeze Protection If the pump has to be stored after use it must be store...

Страница 19: ...7 6 10SQE10C 260 NE 1 C 230V 7 6 10SQE10C 300 NE 1 C 230V 7 6 10SQE15C 340 NE 1 1 2 C 230V 11 1 15SQE03A 70 NE 1 3 A 230V 115V 3 9 7 8 15SQE05A 110 NE 1 2 A 230V 115V 4 9 9 8 15SQE05B 130 NE 1 2 B 23...

Страница 20: ...s SPP1 Potentiometer 625468 RediFlo3 Motor Leads available in 5ft increments See price list 25ft 96037428 50ft 96037429 75ft 96037430 100ft 96037431 125ft 96037432 150ft 96037433 175ft 96037434 200ft...

Отзывы: