Menu structure
Menu level
Menu items
Values/settings
Status level
Acknowledgement of
malfunctions
Press one of the three buttons.
Manual backwash
Press the
button for more than 5 s
Select the menu
level
Refer to chapter 5.3.2
Information
1
Current configuration of the backwash.
2
Active backwash interval, [hh:mm]
3
Status of backwash lock
4
Start time of backwash lock, when active,
[hh:mm]
5
Current configuration of microswitch
6
Return to basic display
User
Set the time
Hours and minutes separately, [hh:mm]
Programming /
Code-protected
levels
For settings and displays (refer to chapter 5.5).
5.5
Programming levels
5.5.1
User programming level via Code 113
Status level>Code-protected level 113
Parameters
Meaning
Factory
settings
Setting range
0
Evaluation of the
differential
pressure signal
The GENO-RS-tronic utilises the differential
pressure switch to detect independently
when a backwash is required
1
0 = Differential pressure signal is not
evaluated
1 = Differential pressure signal is
evaluated
1
Backwash
interval
Time after which a backwash takes place
automatically
30 d
1
– 23 h (hours), here, a backwash
always takes place at the full hour
1
– 99 d (days), here, the time can be
programmed in the parameters that
follow as well
2
Start time of the
interval-
controlled
backwash
(hours)
When the backwash interval, parameter
“1”,
is set in range 1 - 99 d
01:
00: - 23:
3
Start time of the
interval-
controlled
backwash
(minutes)
When the backwash interval, parameter
“1”,
is set in range 1 - 99 d
:00
:00 -:59
4
Activation of a
timed backwash
lock
The timed backwash lock can be used to
suppress any backwash for a programmable
period of time
0
0 = Timed backwash lock deactivated
1 = Timed backwash lock active