1 | Operation of UV systems 

 

1.1 General 

 

information  

The SAK

254

 value (specific absorption coefficient at a wave length 

of the light of 254 nm) is the parameter relevant for the UV disin-
fection which is used in order to describe the properties of the 
water.  The value is determined according to DIN 38404, part 3, 
without prior filtration of the water. The measuring is made by 
means of a spectral photometer in quartz cuvettes of a layer 
thickness of at least 40 mm. The SAK

254

 not only registers the 

impact of the substances dissolved in the water (such as iron, 
copper, manganese,...) but also of the suspended solids (turbidity 
substances) in the water. The following applies: the higher the 
SAK

254

 value, the more light is lost in the water. 

 

Note:

 The SAK

254

 can only be determined by means of a labora-

tory measuring device. For determination of the SAK

254

, please 

send a water sample of at least one liter to our internal lab. 

 

The testing of the UV systems for the disinfection of drinking 
water is carried out at a design SAK

254

 of 2.7 m

-1

. This means 

that the UV systems GENO-UV 60 S, 120 S and 200 S are suita-
ble for water with a SAK

254

 of up to 2.7 m

-1

. Water that has a 

higher SAK

254

 needs a different, equally suitable UV disinfection 

system for the disinfection or the water has to be treated (e.g. 
by filtration, deferrization, ..) to an extent that the SAK

254

 does 

not exceed the above mentioned value. In order to guarantee 
the disinfection efficiency, the flow indicated in table E-1 for the 
respective UV system must not be exceeded and the corre-
sponding minimum irradiance must not be undershot. 

As in many water analyses the water transmission is also speci-
fied, the transmissions corresponding to a SAK

254

 

of 2.7 m

-1

 at a 

cuvette thickness of 10 mm, 50 mm and 100 mm are indicated 
in table E-1 as well. With transmission, the values must not be 
fallen below. 

The control unit of the systems is pre-set to the minimum irradi-
ance as indicated in table E-1. This setting must not be modi-
fied. The same applies for the pre-alarm of irradiance which, as 
required by worksheet W 294-1, is set to a value of 110 % of 
minimum irradiance (e.g. min. irradiance 11.0 W/m², pre-alarm 
12.1 W/m²). 

Содержание GENO-UV 120 S

Страница 1: ...section consists of a lose collection of sheets that should according to the respective chapter and page number refer to header and footer be attached to the corresponding chapters of the standard ope...

Страница 2: ......

Страница 3: ...device For determination of the SAK254 please send a water sample of at least one liter to our internal lab The testing of the UV systems for the disinfection of drinking water is carried out at a des...

Страница 4: ...tested by the DVGW is maintained Table E 1 Indicator points certified by the DVGW System SAK254 10 50 100 max flow min irradiance m 1 m h W m GENO UV 60 S 2 7 94 0 74 1 55 0 3 3 11 5 GENO UV 120 S 8 0...

Страница 5: ...rating panels and display 2 2 Operation programming level 2 3 Installer level code 290 2 4 Error memory code 245 2 5 Displaying the software version code 999 2 6 Customer service level code 302 2 7 Re...

Страница 6: ...level Key Display Unit LED Basic display of irradiance XX XX W m X Operating duration XXXX Days X Switch on processes XXXX X Time until service is due XXXd Days Back to basic display of irradiance or...

Страница 7: ...d parameter while value flashes Return to the next parameter Close the opened parameter without saving the old set value is main tained Jump back to the basic display of irradiance Open the display of...

Страница 8: ...or the menu to be edited The code for the level required here is 290 2 Press key to count upwards until C 290 appears in the display OR Press key to count downwards until C 290 appears in the display...

Страница 9: ...hould be reset so that they display the code for the menu to be edited The code for the level required here is 245 2 Press key to count upwards until C 245 appears in the display OR Press key to count...

Страница 10: ...l code 302 Index Parameter Unit Factory setting Setting range Note 0 Calibration of UV sensor W m Current irradiance 0 45 0 see chapter H 2 1 1 Irradiance limit value W m According to currently set da...

Страница 11: ...ooting This is what you observe This is the cause This is what to do Er 1 and UV lamp light up Irradiance limit value System is dirty inside Service life 730 days or 18 000 h of UV lamp has been excee...

Страница 12: ...20 mA interrupted UV sensor connection plug in serted correctly Optional USB data recording device wired incorrectly Er 6 or Er 7 Wire fracture or short circuit of the temperature sensor only when the...

Страница 13: ...Check seals and replace if necessary Check functioning of the safety device Check functioning of a possibly existing rinsing valve Rinse UV disinfection system if required Clean protective pipes if ne...

Страница 14: ...afety device that might be installed If the system is switched off the safety device must close check the water flow Check the functioning of a temperature flushing system that might be installed Dip...

Страница 15: ...ation log On the GENO Multi BS control unit change to calibration level code 302 and open the parameter 0 XX X with the key P for editing 0 XX X flashes Remove the system sensor insert the reference s...

Страница 16: ...Edited by KONS mhug mrie G BA 523950 GB_KD H DOC H 8 3 Resetting the operating hours and the switch on counter After replacing the lamp the operating duration and switch on counter should be reset Rep...