background image

Operation 

GENO

-Multi BS 

 

 
 

-CONFIDENTIAL-  

Order no

. 004 523 950-gb   Edited by: KONS-rjau-mrie G:\BA-523950-GB_KD-F.DOC 

F-8 

2.3 Installer level 

 

Code 290 

 

 

Note:

 The parameters specified below should only be modified by 

trained experts as incorrect values may lead to malfunctions or 
insufficient disinfected drinking water. 

 

Requirement: The control unit shows the basic display of irradi-
ance. 

 1.

 

Press keys       +        at the same time until the display  
changes. 

 

The installer level is active. The required menu must be selected 
first. The numbers (000) flash. 

These should be reset so that they 

display the code for the menu to be edited.

 The code for the level 

required here is 290. 

 2.

 

Press key        to count upwards until C.290 appears in the 
display. 

 

OR

 

 

Press key        to count downwards until C.290 appears in 
the display. 

 

Hold down keys        and        so that the numbers run faster; press 
the keys for fine adjustment. 

 

3.

 

Press key        to accept code 290.

 

Note:

 In contrast to the Info level, it is possible to move backwards 

and forwards between the individual parameters in the installer 
level using keys        and        . 

 

Index Parameter, 

Unit 

Factory 
setting 

Setting 
range 

Note

 

System type 

0  60 

60/120/

 

200/201 

60 = UV60

 

120 = UV120

 

200 = UV200 with SAK

254

 = 2.7

 

201 = UV200 with SAK

254

 = 5.1 

Option temperature flush-
ing system 

1   0 

0 … 1 

0 = deactivated

 

1 = activated 

Service interval [days] 

2   0 

0 … 730 

Restart the service interval by 
reprogramming 

 

 

Содержание GENO-UV 120 S

Страница 1: ...section consists of a lose collection of sheets that should according to the respective chapter and page number refer to header and footer be attached to the corresponding chapters of the standard ope...

Страница 2: ......

Страница 3: ...device For determination of the SAK254 please send a water sample of at least one liter to our internal lab The testing of the UV systems for the disinfection of drinking water is carried out at a des...

Страница 4: ...tested by the DVGW is maintained Table E 1 Indicator points certified by the DVGW System SAK254 10 50 100 max flow min irradiance m 1 m h W m GENO UV 60 S 2 7 94 0 74 1 55 0 3 3 11 5 GENO UV 120 S 8 0...

Страница 5: ...rating panels and display 2 2 Operation programming level 2 3 Installer level code 290 2 4 Error memory code 245 2 5 Displaying the software version code 999 2 6 Customer service level code 302 2 7 Re...

Страница 6: ...level Key Display Unit LED Basic display of irradiance XX XX W m X Operating duration XXXX Days X Switch on processes XXXX X Time until service is due XXXd Days Back to basic display of irradiance or...

Страница 7: ...d parameter while value flashes Return to the next parameter Close the opened parameter without saving the old set value is main tained Jump back to the basic display of irradiance Open the display of...

Страница 8: ...or the menu to be edited The code for the level required here is 290 2 Press key to count upwards until C 290 appears in the display OR Press key to count downwards until C 290 appears in the display...

Страница 9: ...hould be reset so that they display the code for the menu to be edited The code for the level required here is 245 2 Press key to count upwards until C 245 appears in the display OR Press key to count...

Страница 10: ...l code 302 Index Parameter Unit Factory setting Setting range Note 0 Calibration of UV sensor W m Current irradiance 0 45 0 see chapter H 2 1 1 Irradiance limit value W m According to currently set da...

Страница 11: ...ooting This is what you observe This is the cause This is what to do Er 1 and UV lamp light up Irradiance limit value System is dirty inside Service life 730 days or 18 000 h of UV lamp has been excee...

Страница 12: ...20 mA interrupted UV sensor connection plug in serted correctly Optional USB data recording device wired incorrectly Er 6 or Er 7 Wire fracture or short circuit of the temperature sensor only when the...

Страница 13: ...Check seals and replace if necessary Check functioning of the safety device Check functioning of a possibly existing rinsing valve Rinse UV disinfection system if required Clean protective pipes if ne...

Страница 14: ...afety device that might be installed If the system is switched off the safety device must close check the water flow Check the functioning of a temperature flushing system that might be installed Dip...

Страница 15: ...ation log On the GENO Multi BS control unit change to calibration level code 302 and open the parameter 0 XX X with the key P for editing 0 XX X flashes Remove the system sensor insert the reference s...

Страница 16: ...Edited by KONS mhug mrie G BA 523950 GB_KD H DOC H 8 3 Resetting the operating hours and the switch on counter After replacing the lamp the operating duration and switch on counter should be reset Rep...

Отзывы: