56

12 Manufacturer Warranty   

     

  Please refer to the warranty card. 

13 Decommissioning 

13.1 Dismantling the Inverter 

1

 

  Disconnect the inverter as described in section 8      . 

2

 

  Remove all connection cables from the inverter. 

 

CAUTION

 

Danger of burn injuries due to hot enclosure parts! 

Wait 20 minutes before disassembling until the housing has cooled down. 

3

 

 

Screw off all projecting cable glands. 

4

 

  Lift the inverter off the bracket and unscrew the bracket screws. 

13.2 Packing the Inverter 

If possible, always pack the inverter in its original carton and secure it with tension 
belts. If it is no longer available, you can also use an equivalent carton. The box must 
be capable of being closed completely and made to support both the weight and the 
size of the inverter. 

 

13.3 Storing the Inverter 

Store the inverter in a dry place where ambient temperatures are always between 
-25°C and +60°C. 

13.4 Disposing of the Inverter 

 

Do not dispose of faulty inverters or accessories together with household 

waste. Please accordance with the disposal regulations for electronic waste 

which apply at the installation site at that time. Ensure that the old unit and, 

where applicable, any accessories are disposed of in a proper manner   

 

Содержание MIC 1000 TL-X

Страница 1: ...1 MIC 600TL X MIC 750TL X MIC 1000 TL X MIC 1500 TL X MIC 2000 TL X MIC 2500 TL X MIC 3000 TL X MIC 3300 TL X Installation Operation Manual...

Страница 2: ...com au T 61 2 8065 1298 H 1800 476 928 E australia ginverter com Please note Growatt reserve the ultimate explanation right on this warranty card Supplier is required to send the warranty claim form...

Страница 3: ...t device In this case you do not receive a new certificate since your entitlement is documented at Growatt Failure to observe the user manual the installation guide and the maintenance regulations Una...

Страница 4: ...he unit 16 4 Unpacking and inspection 16 5 Installation 17 5 1 Safety instructions 18 5 2 Selecting the installation location 19 5 3 Mounting the Inverter 22 5 3 1 Mounting the Inverter with bracket 2...

Страница 5: ...r Quality Response Modes PQRM 45 7 3 2 Generation Export limitation control and Power Sensor setting 46 7 3 3 Reset factory 48 7 3 4 Adjust the setpoints from the regional default values 48 7 4 Commun...

Страница 6: ...4 14 Technical Data 57 14 1 Specification 57 14 2 DC AC connector info 60 14 3 Torque 60 14 4 Accessories 61 15 Compliance Certificates 61 16 Contact 61...

Страница 7: ...market 1 2 Target Group This manual is for qualified personnel Qualified personnel have received training and have demonstrated skills and knowledge in the construction and operation of this device Q...

Страница 8: ...description DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result...

Страница 9: ...s Point of connection for grounding protection Direct Current DC Isolation Switch Alternating Current AC Read the manual CE mark The inverter complies with the requirements of the applicable CE guidel...

Страница 10: ...t power feeding into the power distribution grid and the maximum power of the inverter that can feed into the power distribution grid Power Factor Power factor is the ratio of true power or watts to a...

Страница 11: ...intended use The manufacturer supplier is not liable for damage caused by such unintended use Damage caused by such unintended use is at the sole risk of the operator PV modules Capacitive Discharge C...

Страница 12: ...the instructions in this manual Use care when choosing installation location and adhere to specified cooling requirements Unauthorized removal of necessary protections improper use incorrect installat...

Страница 13: ...vailing safety regulations to minimize risk of accidents Systems with inverters typically require additional control e g switches disconnects or protective devices e g fusing circuit breakers dependin...

Страница 14: ...in this manual In special cases there may still be interference for the specified application area despite maintaining standardized emission limit values e g when sensitive equipment is located at the...

Страница 15: ...ol Touch button We can switch the OLED display and set parameter by touching Inverter status symbol Indicates inverter operation status Red Fault Green Nomal Red leaf flash Warning or DSP Programming...

Страница 16: ...range 50V 500V AC nominal voltage 230V AC grid frequency 50 60 Hz Max apparent power 600VA 750VA 1000VA 1500VA AC normal output current 2 6A 3 3A 4 3A 6 5A Power factor 0 8leading 0 8lagging Environm...

Страница 17: ...ate location to store the inverter The unit must be stored in original package and desiccant must be left in the package Max input DC current 13A Start voltage 80V MPP voltage range 65V 550V AC nomina...

Страница 18: ...s leave our factory in proper electrical and mechanical condition Special packaging ensures safe and careful transportation However transport damage may still occur The shipping company is responsible...

Страница 19: ...unting bracket 1 C Quick Guide 1 D Monitor Optional 1 E Signal connector 1 F DRED connector 1 G Self tapping screws 3 H Safety lock screw 2 I Plastic expansion pipe 3 J PV PV terminal 1 1 K PV PV meta...

Страница 20: ...pliance to EMC regulations for the complete system All electrical installations shall be done in accordance with the local and national electrical codes Do not remove the casing Inverter contains no u...

Страница 21: ...id potential damages to device and operators The installation location must be suitable for the inverter s weight and dimensions for a long period time Select the installation location so that the sta...

Страница 22: ...Inverter requires adequate cooling space Providing better ventilation for the inverter to ensure the heat escape adequately The ambient temperature should be below 40 C to ensure optimum operation Do...

Страница 23: ...ary increase the clearance spaces and make sure there is enough fresh air supply to ensure sufficient cooling of the inverters The inverter can t install to solarization drench firn location We sugges...

Страница 24: ...racket DANGER In order to avoid electrical shock or other injury inspect existing electronic or plumbing installations before drilling holes Fix the mounting bracket as the figure shows Do not make th...

Страница 25: ...mounting frame is really firmly mounted on the wall after carefully checking Rise up the inverter a little higher than the bracket Considered the weight of them During the process please maintain the...

Страница 26: ...S485 A 6 1 Safety Danger to life due to lethal voltages High voltages which may cause electric shocks are present in the conductive parts of the inverter Prior to performing any work on the inverter d...

Страница 27: ...you must choose a Type B RCD breaker with the rating residual current not less than 300mA You must install a separate single phase circuit breaker or other load disconnection unit for each inverter i...

Страница 28: ...through pressure screw seal ring threaded sleeve in sequence insert cables into connection terminal according to polarities indicates on it and tighten the screws firmly Please try to pull out the wi...

Страница 29: ...27 3 Push the threaded sleeve into the socket Tighten up the cap on the terminal 4 Finally Push or screw the threaded sleeve to connection terminal until both are locked tightly on the inverter...

Страница 30: ...28 5 To remove the AC output terminal press the bayonet out of the slot with a small screwdriver and pull it out or unscrew the threaded sleeve then pull it out...

Страница 31: ...29 Wire suggestion length Conductor cross section Max cable length MIC 600 750 TL X MIC 1000 TL X MIC 1500 TL X 2 0mm 14AWG 72m 54m 37m 3 3 mm 12AWG 120m 90m 61m...

Страница 32: ...ith a conductor cross section of at least 10 mm Cu Or Install a second protective conductor on the earth terminal with the same cross section as the original protective conductor on the AC terminal Th...

Страница 33: ...VER connect or disconnect the DC connectors under load Make sure the maximum open circuit voltage Voc of each PV string is less than the maximum input voltage of the inverter Check the design of the P...

Страница 34: ...threaded sleeve in sequence insert cables into connection terminal according to number indicates on it and tighten the screws firmly Please try to pull out the wire to make sure the it s well connect...

Страница 35: ...to the socket Tighten up the cap on the terminal Step 3 Push the threaded sleeve to connection terminal until both are locked tightly on the inverter Uninstall signal connector Step 1 Press the fasten...

Страница 36: ...unding the inverter The inverter must be connected to the AC grounding conductor of the power distribution grid via the ground terminal PE WARNING Because of the transformerless design the DC positive...

Страница 37: ...r multiple inverter combination The export limit control function for an inverter is used to control the generation from an inverter or multiple inverter combination to manage the export power level f...

Страница 38: ...time 3s Installation category CAT II Mechanical Environment M1 Electromagnetic environment E2 Degree of pollution 2 Mechanics Din rail dimensions 18x118x64 WxHxD DIN 43880 Mounting DIN rail 35mm Ingre...

Страница 39: ...netration All the warranty claim will be invalid WARNING Excessive voltage can damage the inverter External voltage of DRM PORT don t over 5V 6 8 1 RJ45 pin assignment Pin Assignment for inverters cap...

Страница 40: ...t 3 Relay contact 3 input K3 Relay 3 output 4 Relay contact 4 input K4 Relay 4 output 5 GND Relays common node 6 Not connected Not connected 7 Not connected Not connected 8 Not connected Not connected...

Страница 41: ...Electrical Code R Section 690 11 stipulates that newly installed PV systems attached to a building must be fitted with a means of detecting and disconnecting serial electric arcs AFCI on the PV side 6...

Страница 42: ...lready set up When the Earth fault occurs the Red LED will light up The buzzer in the inverter will keep ringing unless the fault condition is cleared This function is o nly avilable for Australia and...

Страница 43: ...defaut value 7 1 2 Country Area and Region setting Information Country Area and Region setting When the inverter start up the installer need to select the right country if the installer don t select a...

Страница 44: ...grid protection settings 7 1 3 Enabling Disabling Power Quality Response Modes PQRM Information PQRM setting When the Region setting is completed the inverter will operate under default mode different...

Страница 45: ...Single touch to switch different language Double touch to confirm you setting Set the language as described below 7 2 2 Set inverter COM address The default COM address is 1 We can change COM address...

Страница 46: ...44 Double touch to confirm you setting 7 2 3 Set inverter date time Single touch make the number 1 Double touch to confirm you setting Hold 5s recover defaut value...

Страница 47: ...Region and Power Quality Response Modes PQRM Single touch to switch display or make the number 1 Double touch to confirm you setting Input right password you can change Country Area Region and PQRM se...

Страница 48: ...to switch display or make the number 1 Double touch to confirm you setting Control type SW stands for enabling software limit control function HW stands for enabling hardware limit control function Bo...

Страница 49: ...ergy provider the ratio of your system output power divide d by the rated power of the inverter is called Limit Rate For instance if the energy provider only ac cepts 1kVA kW from your 2kW system then...

Страница 50: ...ameters will be restored to their factory defaults Single touch to switch display or make the number 1 Double touch to confirm you setting Input right password you can reset factory default setting 7...

Страница 51: ...SB connection we can connect external optional monitor for example Shine WIFI X Shine 4G X Shine LAN X ect And also you can quickly update the software by U disk We can monitor as below Make sure the...

Страница 52: ...4 Waiting until LED OLED have go out the inverter is shut down 9 Maintenance Repair and Cleaning WARNING Prior to removal of any cover for maintenance or repair turn off the switch on the AC and DC s...

Страница 53: ...nzhen Growatt New Energy Technology Co Ltd confirms that the Growatt inverters and accessories described in this document are in compliance with the above mentioned EU directives The entire EU Declara...

Страница 54: ...ggestion Residual I High Error 201 Leakage current too high 1 Restart the invert 2 If error message still exists contact Growatt PV Voltage High Error 202 The DC input voltage is exceeding the maximum...

Страница 55: ...utral and PE 2 Check AC wiring 3 Restart inverter if error message still exisits contact Manufacturer AC F Outrange Error 304 Utility grid frequency out of permissible range Please switch off DC switc...

Страница 56: ...er service to replace the power board Warning207 USB over current 1 Unplug the U disk or monitor 2 Re access U disk or monitor after shutdown 3 If the error message still exists contact manufacturer W...

Страница 57: ...ist Contact Growatt Error 411 DSP communicates with M3 abnormal Restart inverter if problem still exist update the DSP M3 firmware Change DSP board or M3 board if problem still exist contact Growatt E...

Страница 58: ...the inverter in its original carton and secure it with tension belts If it is no longer available you can also use an equivalent carton The box must be capable of being closed completely and made to s...

Страница 59: ...MPP trackers 16A Output data AC Rated output power 600W 750W 1000W 1500W Rated apparent power 600VA 750VA 1000VA 1500VA Max AC apparent power 600VA 750VA 1000VA 1500VA Nominal AC voltage range 230 18...

Страница 60: ...y Drift Residual current monitoring unit Integrated General data Dimensions W H D in mm 274 254 138 Weight 6 0 kg Operating temperature range 25 C 60 C Noise emission typical 25 dB A Altitude 4000m In...

Страница 61: ...y range 50 60Hz 44 55Hz 54 65Hz Rated output current 8 7A 10 9A 13A 14 3A Max output current 9 5A 11 9A 14 3A 14 3A Initial short circuit AC current 8 7A 10 9A 13A 14 3A Inrush current 10A Max output...

Страница 62: ...ht 0 5W Topology Non isolated Cooling Natural convection Protection degree IP65 Relative humidity 0 100 DC connection VP D4 H4 opt AC connection AC connector Interfaces Display OLED LED RS485 USB Inte...

Страница 63: ...so be expressly exclude as are all other related logistical and process costs incurred by all parties in relation to this warranty claim 15 Compliance Certificates Certificates With the appropriate se...

Страница 64: ...62 www ginverter com Serviceline Tel 86 755 2747 1942 Email service ginverter com...

Отзывы: