An identi
fi
cation plate containing information about the tank is attached to the base of the
tank in line with the thermometer and on the jacket.
Please take note of these details before
contacting After-Sales Service.
3. INSTALLING THE EQUIPMENT
• Place the tank and its safety unit (and/or safety valve)
in a frost-free place.
• Position it as near as possible to the most-used taps.
• If it is placed outside occupied areas, insulate the pipework. If the device needs
to be installed in a location where the ambient temperature is always above 35°C,
ensure the space is ventilated.
• Ensure that the supporting structure is strong enough to take the weight of the tank
when it is fi lled with water.
• Allow a minimum of 1 metre in front of the fl ange for regular maintenance of the
tank.
• Fit a retention tank with a drain beneath the tank if it is located in a loft or above premises
in use.
• The safety unit and/or safety valve must be accessible.
• A drain connection must be provided equipped with a funnel.
• The lower tapping allows the tank to be drained fully.
• The tank only operates in the vertical position.
• Any unused couplings must be suitably sealed.
The water tightness of the complete system must be checked under normal operating
conditions and during maintenance operations, and the
fl
ange couplings must be tightened,
if necessary.
The hot water tank must be included in the potential equalisation.
For safety reasons, water may
fl
ow out of the evacuation duct when the tank is heating
up. Do not close or obstruct the evacuation duct.
!