6.2 Connection to mains power
The unit can operate with voltage from 100 to 240Vac with frequency of 50 and 60Hz.
1.
Untighten the 4 screws
“A”
and open the units.
2.
Let the main supply cable pass through the cable glands
“G”
located onto the unit body and connect the main cable to
the terminal box
“H”
.
The connection of the cable to the unit must be performed re-
specting the label next to the terminal box.
Size and connection scheme of the main cable are shown in
the following picture.
3.
Close the unit again by tighten the screw
“A”
previously removed.
Warning!
• Before connecting the unit, verify that power supplies features are compatible with the unit features.
• The unit must never be installed if not grounded electrically.
• It is suggested to use a magnetothermic switch along the power supply line, as prescribed by in force rules.
• The unit must not be powered up through a dimmer power device.
• Wiring and connection actions are to be performed by a qualified staff.
G
A
ø9 MIN
ø12 MAX
LED OFF NO DMX SIGNAL
LED ON DMX SIGNAL
LED FLASH AUTOMATIC MODE
L
Ground
N
Neutral
Phase
H
3x1.5mm
²
minimum cable
section
Main cable size
20
English