background image

[6] SAMPLING TUBE INSTALLATION

[6.1] SAMPLING TUBE SELECTION

The sampling tube must be purchased separately. Order the correct length, as 
specified in 

Table 1

, for width of the duct where it will be installed. It is recom-

mended that the sampling tube length extend at least 

2

/

3

 across the duct width 

for optimal performance.

TABLE 1. SAMPLING TUBES RECOMMENDED FOR DIFFERENT 

DUCT WIDTHS:

Outside Duct Width

Sampling Tube Recommended*

Up to 1 ft.

DST1

1 to 2 ft.

DST1.5

2 to 4 ft.

DST3

4 to 8 ft.

DST5

8 to 12 ft.

DST10 (2-piece)

*Must extend a minimum of 

2

/

3

 the duct width. 

The sampling tube is always installed with the air inlet holes facing into the 
air flow. To assist proper installation, the tube’s connector is marked with an 
arrow. Make sure the sampling tube is mounted so that the arrow points into 
the airflow as shown in 

Figure 3

. Mounting the detector housing in a vertical 

orientation is acceptable provided that the air flows directly into the sampling 
tube holes as indicated in 

Figure 3

. The sampling tube and exhaust tube can be 

mounted in either housing connection as long as the exhaust tube is mounted 
downstream from the sampling tube.

FIGURE 3. AIR DUCT DETECTOR SAMPLING TUBE:

SAMPLING TUBE ENDCAP

ARROW MUST FACE 

INTO AIR FLOW

AIR FLOW 

DIRECTION

H0551-00

CAUTION:

 The sampling tube end cap, included with the detector, is critical to 

proper operation of the duct smoke detector. The end cap is needed to create 
the proper air flow to the sensor of the duct smoke detector. Once any sampling 
tube length adjustments are made, plug the end of the sampling tube with the 
provided end cap.

A plastic exhaust tube is included with the unit to be installed if needed. Install 
into the housing connection that is downstream from the sampling tube connec-
tion. The exhaust tube can be installed from the front or back of the detector. 
A longer 1 foot exhaust tube, model ETX, is available as an accessory in cases 
where the molded exhaust tube does not extend at least 2 inches into the duct.

[6.2] SAMPLING TUBE INSTALLATION

1.   For tubes shorter than the width of the duct, slide the sampling tube, 

with installed end cap, into the housing connection that meets the airflow 
first. Position the tube so the arrow points into the airflow as shown in 

Figure 3

. Per NFPA sampling tubes over 3 feet long should be supported at 

the end opposite the duct detector. In ducts wider than 8 feet, work must 
be performed inside the duct to couple the other section of the sampling 
tube to the section already installed using the 

1

/

2

 inch conduit fitting. Make 

sure that the holes on both sections of the air inlet sampling tube are lined 
up and facing into the airflow.

2.   For tubes longer than the width of the duct, the tube should extend out 

of the opposite side of the duct. Drill a 

3

/

4

 inch hole in the duct opposite 

the hole already cut for the sampling tube. Ensure that the sampling tube 
is angled downward from the duct smoke detector to allow for moisture 
drainage away from the detector. The sampling tube should be angled 
at least 1/4” downward for every 12” of duct width per 

Figure 4

. There 

should be 10 to 12 holes spaced as evenly as possible across the width of 
the duct. If there are more than 2 holes in the section of the tube extending 
out of the duct, select a shorter tube using 

Table 1

. Otherwise, trim the 

tube to leave approximately 1 to 2 inches extending outside the duct. Plug 
the end with the end cap and tape closed any holes in the protruding sec-
tion of tube. Be sure to seal the duct where the tube protrudes.

FIGURE 4. 

DETECTOR

3

/

4

˝

HOLE

12˝

1

/

4

˝

 H0215-00

NOTE:

 Air currents inside the duct may cause excessive vibration, especially 

when the longer sampling tubes are used. In these cases, a 3 inch floor flange 
(available at most plumbing supply stores) may be used to fasten the sampling 
tube to the other side of the duct. When using the flange/connector mounting 
technique, drill a 1 to 1

1

/

4

 inch hole where the flange will be used.

[6.3] MODIFICATIONS OF SAMPLING TUBES

There may be applications where duct widths are not what is specified for the 
installation. In such cases, it is permissible to modify a sampling tube that is 
longer than necessary to span the duct width.

Use a 0.193 inch diameter (#10) drill and add the appropriate number of holes 
so that the total number of holes exposed to the air flow in the duct is 10 to 12. 
Space the additional holes as evenly as possible over the length of the tube.

NOTE:

 This procedure should only be used as a temporary fix and is not in-

tended as a substitute for ordering the correct length tubes.

[6.4] REMOTE SAMPLING TUBE INSTALLATION

The detector arrangement can also incorporate remote mounting of the sam-
pling tube and/or exhaust tube. In this case both the detector, sampling tube 
and exhaust tube (if included) should be rigidly mounted to withstand the pres-
sure and vibrations caused by the air velocity. The location of the detector’s 
sampling tube should be such that there is uniform airflow in the cross section 
area. 

The pressure differential across the sampling and exhaust ports in the detector 
housing shall be verified to be between 0.01 and 1.11 inches of water. Do so 
by measuring the pressure difference between the inlet and outlet ports on the 
detector housing using a manometer as described in 

Section 7.1

.

[7] MEASUREMENT TESTS

[7.1] AIR FLOW

The DSD120 is designed to operate over an extended air speed range of 100 
to 4000 FPM. To verify sufficient sampling of ducted air, turn the air handler 
on and use a manometer to measure the differential pressure between the two 
sampling tubes. The differential pressure should measure at least 0.01 inches of 
water and no more than 1.11 inches of water. Because most commercially avail-
able manometers cannot accurately measure very low pressure differentials, ap-
plications with less than 500 FPM of air speed may require one of the following: 
1) the use of a current-sourcing pressure transmitter (Dwyer Series 607) per 
Section 7.2, or 2) the use of aerosol smoke per section 11.4.2.

[7.2] LOW FLOW AIR FLOW TEST USING DWYER SERIES 607 

DIFFERENTIAL PRESSURE TRANSMITTER

Verify the air speed of the duct using an anemometer. Air speed must be at least 
100 FPM. Wire the Dwyer transmitter as shown in 

Figure 5

. Connect the leads 

of the meter to either side of the 1000

Ω

 resistor. Allow unit to warm up for 15 

seconds. With both HIGH and LOW pressure ports open to ambient air, measure 
and record the voltage drop across the 1000

Ω

 resistor (measurement 1), 4.00 

volts is typical. Using flexible tubing and rubber stoppers, connect the HIGH 
side of the transmitter to the sampling tube of the duct smoke detector hous-
ing, and the LOW side of the transmitter to the exhaust tube of the duct smoke 
detector housing. Measure and record the voltage drop across the 1000

Ω

 resistor 

(measurement 2). Subtract the voltage recorded in measurement 1 from the 
voltage recorded in measurement 2. If the difference is greater than 0.15 volts, 
there is enough air flow through the duct smoke detector for proper operation.

IN-GE-DSD120-01-01 3 

I56-9201-000 

 

 5/6/2019

Содержание DSD120

Страница 1: ...Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC resistive 10A 250 VAC resistive 1 2 HP 240 VAC 1 4 HP 120 VAC NOTE Alarm auxiliary contacts shall not be connect...

Страница 2: ...e parameters If necessary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop heating...

Страница 3: ...y holes in the protruding sec tion of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct...

Страница 4: ...DEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FLUKE MODEL 87 OR EQUIVALENT FIGURE 5 PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM H0163 00GS FIGURE 6 SYSTEM WIRING DIAGRAM FOR 4 WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHU...

Страница 5: ...very 5 seconds as depicted in Table 3 on page 7 The maintenance condition indicates that the sensor is operating outside its original factory preset sensitivity and shall be cleaned or replaced Replacement 2D51A sensors are available as a separate item See Sec tion 9 for reference This is a valid UL test 11 4 DETECTOR TESTING AND MAINTENANCE PROCEDURES Notify the proper authorities that the smoke ...

Страница 6: ...and then gently pushing it until it locks into place 8 Reinstall the detector FIGURE 9 DETECTOR SENSOR EXPLODED VIEW SENSOR COVER SENSING CHAMBER COVER AND SCREEN SENSOR CHAMBER COVER REMOVAL TABS C1009 00 12 2 REINSTALLATION 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check Section 11 2 4 Notify the proper authorities testing has been completed and the smoke ...

Страница 7: ...ern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 ar...

Страница 8: ...send defective units post age prepaid to 150 English Drive Moncton N B Canada E1E 4G7 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreason able use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for an...

Отзывы: