TABLE 3. DETECTOR STATUS INDICATION

NOTE: Power Board LED is not visible unless the power board cover is removed. If any other visual indication is noted contact technical support at 1-506-853-3057.

DETECTOR 
STATE

SENSOR LED

POWER BOARD LED

COMMENTS

RELAY STATES

Power Up

Red Blink every 5 
seconds

Alternating Green/ 
Amber Blink every 1 
second 

Initialization completes in 
approximately 30 sec

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Standby

Green Blink every 5 
seconds

Green Blink every 5 
seconds

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Maintenance

Red Blink every 5 
seconds

Amber Blink every 5 
seconds

The 2D51A sensor is outside its 
UL approved sensitvity limits and 
needs to be cleaned or replaced.

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Speed-Up

Alternating Red/
Green Blink every 0.5 
seconds

Green Blink every 0.5 
seconds

Alternating red/green blink 
pattern exists until unit either 
enters Alarm or reverts to 
Standby (within approximately 60 
seconds).

Supervisory relay: Terminals 3 and 14 are closed. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states: Terminals 6 and 16 
are closed; Terminals 8 and 18 are closed

Trouble

Red Blink every 5 
seconds

Amber Solid 

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states 

Cover Tamper 
Violation

Red Blink every 5 
seconds

Amber Solid

When in “Standby” mode, 
the product goes into “Cover 
Tamper Violation” if the cover 
has been removed or improperly 
replaced and remains so for at 
least 7 minutes. As soon as the 
cover is properly reseated, the 
product reverts to “Standby” 
automatically.

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open. 

Aux Relay does not switch states 

Communication 
Error

Off

Amber Solid

Sensor LED state cannot be 
guaranteed since there is a 
communication error.

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states

Alarm

Red Solid

Red Solid

Supervisory relay: Terminals 3 and 14 are closed 

Alarm Relay: Terminals 4 and 5 are closed

Aux Relay switches states: Terminals 6 and 16 are 
open; Terminals 8 and 18 are open

Unit Loses 
Power

Off

Off

Supervisory relay: Terminals 3 and 14 are open. 

Alarm Relay: Terminals 4 and 5 are open

Aux Relay does not switch states

IN-GE-DSD120-01-01 7 

I56-9201-000 

 

 5/6/2019

Содержание DSD120

Страница 1: ...Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 20 mA RMS 120 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 35 mA RMS 120 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm auxiliary contacts DPDT 10A 30 VDC resistive 10A 250 VAC resistive 1 2 HP 240 VAC 1 4 HP 120 VAC NOTE Alarm auxiliary contacts shall not be connect...

Страница 2: ...e parameters If necessary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop heating...

Страница 3: ...y holes in the protruding sec tion of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct...

Страница 4: ...DEL 607 01 15 TO 36 VDC SUPPLY 1000 OHM 5 1 WATT RESISTOR VOLT METER FLUKE MODEL 87 OR EQUIVALENT FIGURE 5 PROCEDURE FOR VERIFYING AIR FLOW LESS THAN 500 FPM H0163 00GS FIGURE 6 SYSTEM WIRING DIAGRAM FOR 4 WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHU...

Страница 5: ...very 5 seconds as depicted in Table 3 on page 7 The maintenance condition indicates that the sensor is operating outside its original factory preset sensitivity and shall be cleaned or replaced Replacement 2D51A sensors are available as a separate item See Sec tion 9 for reference This is a valid UL test 11 4 DETECTOR TESTING AND MAINTENANCE PROCEDURES Notify the proper authorities that the smoke ...

Страница 6: ...and then gently pushing it until it locks into place 8 Reinstall the detector FIGURE 9 DETECTOR SENSOR EXPLODED VIEW SENSOR COVER SENSING CHAMBER COVER AND SCREEN SENSOR CHAMBER COVER REMOVAL TABS C1009 00 12 2 REINSTALLATION 1 Reinstall the detector in its housing 2 Restore system power 3 Perform Detector Check Section 11 2 4 Notify the proper authorities testing has been completed and the smoke ...

Страница 7: ...ern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 ar...

Страница 8: ...send defective units post age prepaid to 150 English Drive Moncton N B Canada E1E 4G7 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreason able use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for an...

Отзывы: