background image

Air Condition Examples

Internal Sensor Signal

0-5 Volt Linear Output Signal

Clean fresh air

1. 50 volts

1.0 volts = 10 % pollution

Early morning in an un-occupied office

1.75 volts

1.0 volts = 15 % pollution

Smoke from one cigarette in a 300 ft

2

 room

2.00 volts

1.6 volts = 40 % pollution

Coffee break, eight persons in a 300 ft

2

 lunchroom

2.25 volts

2.2 volts = 65 % pollution

Occupied classroom with 30 persons

2.40 volts

2.6 volts = 68 % pollution

Workshop with solvents in use

3.00 volts

4.1 volts = 80 % pollution

Exhaled smoke towards the sensor from 3 ft distance

3.35 volts

5.0 volts = 90 % pollution

Strong chemicals near sensor (ethyl alcohol, nail polish, etc)

4.00 volts

5.0 volts = 100 % pollution

Manual Mode

The manual mode is selected by using the on board keypad and is explained further in the menu section. In this mode the Air Quality
Monitor will operate in the Manual base/Fixed scale mode. In this mode the scale factor (sensitivity) is factory set to 0.2 volts (wrt-
sensor) and cannot be changed by the user. However, the user can set the base level on the keypad. The base level can be set in the range
of 1.0 to 3.5 volts (wrt-sensor) and is displayed on the LEDs as the 5  least significant bits of a 6 bit binary number (63 steps) with the
OK LED being the LSB. During the set-up step, this voltage level can be measured on the ASO terminal with a DC voltmeter.

The processor measures the sensor output 1.50 – 4.00 volt signal and compares it to the base level as set above. If the sensor reads a
value lower than the base level + 0.2 volts the OK LED will be lit, if the sensor reads a value between the base level + 0.2 volts and
the base level + 0.4 volts then the LOW LED will be lit, etc.

The default base level is set to 20 of 63 or about 1.8 volts so the following settings apply: OK

Sensor < 2.0 V

LOW

2.0 V < Sensor < 2.2 V

MID

2.2 V < Sensor < 2.4 V

HIGH

Sensor > 2.4 V

This mode of operation is useful if the user wants to pre-set a level of air quality which must be maintained. The scale factor has been
optimized for contaminants such as solvents or cigarette smoke. Note that in the manual mode of operation the base level remains fixed
and sensor contamination, temperature or humidity extremes, etc. may cause dampers to stay open for long periods of time.

Auto Mode

The auto mode (factory default) is selected by using the keypad and the Air Quality Monitor will operate in the Auto base/Manual scale
mode. In this mode the base level is automatically adjusted by the program to ensure optimum air quality based on the surrounding
environment and the air handling system. The user can adjust the sensitivity of the device by changing the scale factor via the keypad.

The scale factor has a range of 0.05 to 0.36 V (wrt-sensor) and is displayed on the LEDs as the 5  least significant bits of a 6 bit binary
number (63 steps) with the OK LED being the LSB. See the following example of an LED sequence. The binary range of the scale
factor is (0)00000 to (1)11111 and each count represents about 4.9 mV. This value can be measured on the ASO output terminal.

LED

Extra Bit

Auto

High

Mid

Low

OK

Status

Assumed

Off

On

On

On

On

Binary

0

0

1

1

1

1

Scale Factor

15 x 4.9 mV + 0.05 V = 0.12 V,     001111 = 15

The scale factor represents the sensitivity of the device, a smaller scale factor means more sensitive operation and it will take a smaller
change in the pollution level to give a change in output state. On power up, the base level is initially set to the current air reading. During
operation the device constantly monitors the air quality and compares the contamination level to the base level. If the sensor level falls
below the base level, the base level is adjusted after one minute to equal the air level. This one minute interval of checking is indicated
by a flashing OK LED.

 

This feature always keeps the base level current to the present cleanliness of the air.

If the sensor level increases above the base level, the degree of pollution is determined by comparing the sensor level to the base level
plus multiples of the scale factor. When the pollution level is determined the corresponding LED is lit and the ASO output is updated.
This is the same as the example shown for manual mode except the scale factor can be changed by the user on the key pad.
After pollution has been detected the level must drop below the current level for a period of one minute before the output pollution level
is updated to help ensure against false indication. If the pollution level does not decrease within one hour, then the air is deemed to be

Содержание AIR-300

Страница 1: ...AIR 300 Air Quality Controller Installation and Operating Instructions Febuary 15 2005 ...

Страница 2: ...nants automatically control exhaust air on an assembly line where epoxies are used or a multitude of other applications Some common detectable pollutants in decreasing order of sensitivity most are easily detectable in quantities of 20 ppm or less Chemical Symbol Common Source Methyl Ethyl Ketone C4H8O Solvents and cleaning products Acetone C3H6O Solvents and organic synthesis Ethyl Alcohol C2H6O ...

Страница 3: ...m a ventilation fan or may be connected to a digital input of the B A S for status monitoring Start up Verify that the Air Quality Monitor is properly wired and all connections are tight Apply power to the device and note the status LEDs Initially the OK LED will be on and the AUTO LED will flash to indicate a four minute warm up cycle to allow the sensor to reach normal operating temperature The ...

Страница 4: ...re or humidity extremes etc may cause dampers to stay open for long periods of time Auto Mode The auto mode factory default is selected by using the keypad and the Air Quality Monitor will operate in the Auto base Manual scale mode In this mode the base level is automatically adjusted by the program to ensure optimum air quality based on the surrounding environment and the air handling system The ...

Страница 5: ... Once all connections are made and the warm up period has elapsed press the MODE switch once The OK LED will flash to indicate the mode and the ASO terminal will output an analog voltage corresponding to the OK pollution level This signal defaults to about 2 V and will drive the damper to open slightly to allow a minimum amount of fresh air into the area To modify this value simply press the UP or...

Страница 6: ...nu so the relay will turn on when the linear output is Relay Level Relay Hysteresis and turn off at Relay Level Hysteresis Configuration Menu The Configuration Menu is used to set the operation mode relay modes and for calibration This menu is accessed during normal operation by pressing and holding the DOWN key and then pressing the UP key then release the keys This menu is explained below DOWN h...

Страница 7: ...4 Vdc 200 mA 24 Vac 5 VA Max Input Voltage Effect Negligible over specified operating range Protection Circuitry Reverse voltage protected and output limited Operating Conditions 0 40 C 32 104 F 0 95 RH non condensing Standard Output Signal Analog Stepped Output ASO in four steps representing Ok Low Mid and High pollution levels each step is independently adjustable from 0 10 Vdc Optional Output S...

Страница 8: ...Wiring Diagram Relay Connection Optional 20 30Vac dc Power Supply Output Common Analog Stepped Output to damper actuator Linear Output current or voltage to B A S Optional ...

Отзывы: