INTRODUCTION

The single point strap-on temperature sensor utilizes a precision 

sensor that is attached to a 38 mm x 38 mm (1.5”x 1.5”) aluminum plate 

and adhered to a 38 mm x 25.4 mm (1.5 x 1“) compressible foam. A 254 

mm (10”) S/S Pipe clamp is provided to secure the assembly to various 

sizes of pipe. All probes are constructed to provide excellent heat 

transfer, fast response, and are potted to resist moisture penetration. A 

compact ABS enclosure with a hinged and gasketed cover is provided 

for ease of installation.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning 

the temperature sensor. Failure to follow these instructions may 

result in product damage. Do not use in an explosive or hazardous 

environment, with combustible or flammable gases, as a safety or 

emergency stop device or in any other application where failure 

of the product could result in personal injury. 

Do not exceed the 

device ratings

.

MOUNTING

The strap-on sensor installs directly onto any pipe where space between immersion and sensor with thermowell can’t be installed.

Once a suitable spot is selected, remove a small block of insulation, if present. It is recommended that thermal compound be used to improve 

heat transfer. Spread a liberal amount on the pipe. Open the worm gear clamp by swiveling the worm gear away from the clamp and pull the 

clamp apart, as shown in Figure 1.

Place the sensor plate on the selected mounting area and wrap clamp around the 

pipe. Re-insert clamp under the worm gear and pull until snug. Lock in place by 

swiveling the worm gear towards the clamp. Tighten worm gear clamp by using a 

standard screw driver or hex nut driver as shown in Figure 2.

The enclosure has a hinged cover with a latch.  Open the cover by pulling slightly on 

the latch on the right side of the enclosure. At the same time pulling on the cover, as 

illustrated in Figure 3.

A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. 

Screw the EMT connector or cable gland connector in until tight. See Figure 4. It is 

recommended that weatherproof conduit or cable gland fittings be used. E style 

enclosure includes 1/2" NPT to M16 thread adapter and cable gland fitting.

Make wiring connections as per the “Wiring” illustrations on Page 2.

Swing door closed until securely latched.  For added security, 2 screws are provided 

that may be installed in the integrated screw tabs.  See Figure 5.

EMT Connector

Thread adapter and 

cable gland fitting

Figure 1

Figure 3

Figure 4

Figure 5

Figure 2

IN-GE-TSSOXXX-02

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Strap-on 

Temperature Sensor

TSSO Series - Installation Instructions