Page 2
WIRING
•
Use 18 - 24 AWG shielded wiring for all connections. Do not locate the device wires in the same conduit with wiring used to supply inductive
loads such as motors. Make all connections in accordance with national and local codes.
•
Pull at least six inches of wire into the enclosure, then complete the wiring connection according to wiring diagrams below.
•
All thermistors and most RTD's are a two wire hook up and are not polarity sensitive. See Figure 6.
•
For RTD's that are three wire see Figure 7.
SPECIFICATIONS
:
Sensor Type: ...................................Various thermistors or RTD
Sensor Accuracy: .........................
Thermistors:
±0.2°C (±0.36°F) @ 25°C (77°F)
Platinum RTD's:
±0.3°C (±0.54°F) @ 0°C (32°F)
Nickel RTD's:
±0.4°C (±0.54°F) @ 0°C (32°F)
Probe Material: .............................Machined aluminum heat sink
Probe Dimensions: .....................38.1mm x 12.7mm (1.5” x 0.5”)
Probe Sensing Range: ...............-40 to 100°C (-40 to 212°F)
Ambient Operating Range: ....-40 to 50°C (-40 to 122°F)
Probe Size: ......................................38 mm (1.5") square
Wire Material: ................................PVC insulated, parallel bonded, 22 AWG
Enclosure: ........................................ABS - UL94-V0, IP65 (NEMA4X)
C- includes terminal block
E - includes thread adapter (1/2" NPT to M16),
cable gland fitting, and terminal block
Termination: ..................................A - pigtail, 2 or 3 wire
C & E - terminal block, 2 or 3 wire
Country of Origin: .......................Canada
PRINTED IN C
ANAD
A
TYPICAL WIRE RESISTANCE VALUES
When using low resistance sensors, long wire runs can add
significant error to the readings. Use the following chart to
determine errors due to wire resistance or consider using a
1000 ohm sensor or a transmitter for better accuracy. Locate
the type of wire being used. Multiply the total length of the
wire (distance from the controller to the sensor and back)
by the number found in the chart below for total resistance.
Figure 6 2 Wire Termination for Thermistor or RTD
Figure 7 3 Wire Termination for Thermistor or RTD
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI) or
Customer supplied
transmitter
To Controller
Analog Input (AI) or
Customer supplied
transmitter
Green
Red
Black
EMT Connector
EMT Connector
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI)
(No Polarity)
To Controller
Analog Input (AI) or
Customer supplied
transmitter
To Controller
Analog Input (AI) or
Customer supplied
transmitter
Green
Black
Red
EMT Connector
EMT Connector
Wiring for Enclosures C & E
GAUGE WIRE TYPE 18 AWG 22 AWG 24 AWG
STRANDED (OHMS/FOOT) 5.85 mΩ 14.75 mΩ 23.29 mΩ
SOLID (OHMS/FOOT) 6.4 mΩ 15.85 mΩ 25.72 mΩ
DIMENSIONS
69.8 mm
2.75 “
76.2 mm
3.00"
*For illustrative purposes only, terminal block mounted on inside of cover
*
*
82.5 mm
3.25"
52.0 mm
2.05"
28.6 mm
1.125"
0.5" NPT
254 mm (10")
S/S Pipe Clamp
Quick Release
Machined Aluminum
Heat Sink
IN-GE-TSSOXXX-02