WIRING

• 

Use 18 - 24 AWG shielded wiring for all connections. Do not locate the device wires in the same conduit with wiring used to supply inductive 
loads such as motors. Make all connections in accordance with national and local codes.

• 

Pull at least six inches of wire into the enclosure, then complete the wiring connection according to wiring diagrams below.

• 

All thermistors and most RTD's are a two wire hook up and are not polarity sensitive. See Figure 6.

• 

For RTD's that are three wire see Figure 7.

SPECIFICATIONS

Sensor Type: ...................................Various thermistors or RTD

Sensor Accuracy: .........................

Thermistors:

 ±0.2°C (±0.36°F) @ 25°C (77°F)

 

Platinum RTD's:

 ±0.3°C (±0.54°F) @  0°C (32°F)

 

Nickel RTD's:

 ±0.4°C (±0.54°F) @  0°C (32°F)

Probe Material: .............................Machined aluminum heat sink

Probe Dimensions: .....................38.1mm x 12.7mm (1.5” x 0.5”)

Probe Sensing Range: ...............-40 to 100°C (-40 to 212°F)

Ambient Operating Range: ....-40 to 50°C (-40 to 122°F)

Probe Size: ......................................38 mm (1.5") square

Wire Material: ................................PVC insulated, parallel bonded, 22 AWG

Enclosure: ........................................ABS - UL94-V0, IP65 (NEMA4X)

 

C- includes terminal block

 

E - includes thread adapter (1/2" NPT to M16),

 

cable gland fitting, and terminal block

Termination: ..................................A - pigtail, 2 or 3 wire

 

C & E - terminal block, 2 or 3 wire

Country of Origin: .......................Canada

 

PRINTED IN C

ANAD

A       

TYPICAL WIRE RESISTANCE VALUES 

When using low resistance sensors, long wire runs can add 

significant error to the readings.  Use the following chart to 

determine errors due to wire resistance or consider using a 

1000 ohm sensor or a transmitter for better accuracy. Locate 

the type of wire being used. Multiply the total length of the 

wire (distance from the controller to the sensor and back) 

by the number found in the chart below for total resistance. 

Figure 6                                                          2 Wire Termination for Thermistor or RTD

Figure 7                                                          3 Wire Termination for Thermistor or RTD

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

Green

Red

Black

EMT Connector

EMT Connector

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) 

(No Polarity)

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

To Controller 

Analog Input (AI) or

Customer supplied 

transmitter 

Green

Black

Red

EMT Connector

EMT Connector

Wiring for Enclosures C & E

GAUGE WIRE TYPE                       18 AWG       22 AWG       24 AWG 
STRANDED (OHMS/FOOT)        5.85 mΩ    14.75 mΩ    23.29 mΩ 
SOLID (OHMS/FOOT)                    6.4 mΩ    15.85 mΩ    25.72 mΩ

DIMENSIONS

69.8 mm

2.75 “

76.2 mm

3.00"

*For illustrative purposes only, terminal block mounted on inside of cover

*

*

82.5 mm

3.25"

52.0 mm

2.05"

28.6 mm

1.125"

0.5" NPT

254 mm (10")

S/S Pipe Clamp

Quick Release

Machined Aluminum 

Heat Sink

IN-GE-TSSOXXX-02