DIMENSIONS

SPECIFICATIONS

Pressure Ranges .............................±1", ±2", ±5", ±10", ±20" WC
 

±250 Pa, ±500 Pa, ±1250 Pa, ±2500 Pa, ±5000 Pa

Accuracy ...........................................±1% F.S. @ 22°C (72°F) including hysteresis, non-linearity and repeatability
Measurement Type .......................Static, Velocity, & Total Pressure
Response Time ...............................250 ms
Stability .............................................<±1% F.S.O. per year
Thermal Effects ...............................<±3% over compensated range
Compensated Range....................-25 to 85°C (-13 to 185°F)
Proof Pressure .................................100" W.C. (200" for 5", 10" & 20" models)
Burst Pressure .................................300" W.C. (500" for 20" models)
Operating Conditions ..................0 to 50°C (32 to 122°F), 10 to 90% RH, non-condensing
Power Supply ..................................20-28 Vac/dc (non-isolated half-wave rectified)
Supply Current ...............................<4 mA for voltage output, 20 mA max for current output
Input Voltage Effect ......................Negligible over specified operating range
Protection Circuitry .......................Reverse voltage protected and output limited
Output Signal ..................................4-20 mA (2-wire), 0-10 Vdc (3-wire), field selectable
Output Drive Capabilities ...........

Current:

 400 ohms max @ 24 Vdc

 

Voltage:

 10K ohms min

Zero Adjustments ..........................Push-button auto-zero
Wiring Connections ......................Screw terminal block (14 to 22 AWG)
Pressure Connection ....................Barbed ports for 5 mm (0.170" ID) flexible tubing
Conduit Connection .....................1/2" NPT conduit or cable gland
Enclosure ..........................................Polycarbonate UL94-V0, IP65 (NEMA 4X)
 

F style includes thread adapter (1/2" NPT to M16) and cable gland fitting

Approvals .........................................CE, RoHS
Country of Origin ...........................Canada

 

PRINTED IN C

ANAD

A       

Generally, it is not recommended that the span calibration be performed in the field unless a high quality 

calibrator with low differential pressure ranges is available and the temperature of the sensor can be 

maintained. Contact the factory for information on this type of calibration.

116.5 mm

4.58"

99.7 mm

3.93"

0.5" NPT

96.27 mm

3.79"

49.27 mm

1.94"

112.5 mm

4.43"

53.7 mm

2.11"

IN-GE-ELPXXXXS-01-03      11/19

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Содержание ELP-S

Страница 1: ...e tubing without kinking and to make the electrical connections avoid locations with severe vibrations or excessive moisture Drill a hole in the duct and insert so the probe point is facing into the air flow The enclosure has a standard opening for a 1 2 conduit and may be installed with either conduit and a conduit coupler or a cable gland type fitting See Figure 1 The two mounting holes will fac...

Страница 2: ...s to ensure that the circuit ground point is the same on all devices and the controller This terminal is not used for loop powered 4 20 mA output type 2 wire The analog output signal is available on the OUT terminal This signal is jumper selectable for either a voltage output or a standard loop powered 4 20 mA output signal type The analog output signal is typically connected directly to the Build...

Страница 3: ...ied by measuring the output signal For voltage output configuration measure the voltage between the OUT and COM terminals The voltmeter should read between 0 10 Vdc For current output configuration insert a mA meter in series with the OUT terminal The mA meter should read between 4 and 20 mA OPERATION If the unit is set to a unipolar range such as 0 2 wc then the pressure applied to the High port ...

Страница 4: ...0 10 Vdc 3 wire field selectable Output Drive Capabilities Current 400 ohms max 24 Vdc Voltage 10K ohms min Zero Adjustments Push button auto zero Wiring Connections Screw terminal block 14 to 22 AWG Pressure Connection Barbed ports for 5 mm 0 170 ID flexible tubing Conduit Connection 1 2 NPT conduit or cable gland Enclosure Polycarbonate UL94 V0 IP65 NEMA 4X F style includes thread adapter 1 2 NP...

Отзывы: